Brief Description / Applications

•  Suction Pressure Controller and/or High Pressure Controller, 

  configurable for:

  -  Standard Compressors 

  -  Compressors with CRII-System Control Stages 

  -  Condensation High Pressure Control

•  For up to 8 Suction Pressure Stages respective High Pressure Stages usable

•  For use as a single controller or in a network

•  Direct connection of up to 64 Cold Storage Controllers, 

  Data Exchange for Energy Optimization

•  4 Sensor-, 2 Pressure Transmitter- , 4 Digital Inputs, 

  5 Relay Outputs (2 Relays, 3 SSR-Relays), Analogue Output

•  Capable of handling up to 4 additional stages. 

  (When used in conjunction with Expansion Module 

BMR 3002

).

•  For Single- and Multi-Stage Loads

• 

Peak Load Limitation, Suction Pressure Shifting

•  Automatic Stage Sequencing

• 

Fixed or Autoadaptive Delay Times for Switching Frequency Optimization

• 

Capturing of Machine Feedback Signals and Plant Errors

•  Analogue Output for P/PI-Control

• 

In-/Outputs configurable

• 

Manual Operation of all Machines

• 

Night Operation via internal clock

Please note Safety Instructions 

on page 10 !

 Operating / Operating Elements

ELEKTRONISCHE  REGELUNGEN  GMBH

Actual

Values

Page

Setpoint

Page

Suction 

Pressure

increase 

 

values
decrease 

 

values

Attention

The displayed setpoint 

is active

Some functions may not be available on devices 

with older software versions.

1

2

3

4

EVP

ELREHA

P

Convenient 3 key control for all functions clearly appear on a 7 segment LED 

display. 4 symbols to the right indicate active control function(s). (Relay status 

is indicated separately on „Actual Page“).

programming key

LED blinking = Alarm

The current states of the Digital Inputs, the Relay Outputs and the Data 

Transmission can be read on the Actual Values Page at L98 and L99.

Programming

The 

MSR 

eco

 parameters are simple to access, view and change. During 

normal operation, or if no key is pressed for at least 3 minutes, the 

MSR 

eco

 

will display the following:
1st priority:       current failure display (blinking)

2nd priority:      operation status display (ex. „oFF“)

3rd priority:       selected „permanent parameter“ display

Selecting and Changing of Parameters
Key 

Action

P

 (> 2 sec.)  ....Page name will be displayed



  .................Select desired page 

P

    ..................Enter the page



  .................Select parameter

P

    ..................Prepare programming. Enter access code if necessary



  .................Change value.

 

 

If you hold the key, the values change continuously

P

   ..................Confirm programming

P

 (> 2 sec.)  ....Page name will be displayed again

Access Protection

All adjustable parameters/set-points are protected by an access code.  

They are divided into 3 groups or levels with 3 operator codes. 

An access code will be required to change an adjustable parameter, (see 

parameter listing). To change an adjustable parameter that requires an access 

code, begin by pressing the „P“ key.:

The screen will display C00, prompting the user for access 

code entry.

The Access Codes are divided into 3 access levels, (OEM, Technician, and 

Customer Codes).

OEM Code „oem“

: Month + Hour + 20

  The OEM Code grants access to all adjustable parameters on the  

 

  device.

Technician Code „tec“

 : 88

  The Technician Code grants access only to „Technician“ and „Customer“  

  assigned adjustable parameters.

Customer Code „---“

 : no access code required.

  The Customer Code grants access only to „Customer“ assigned 

  adjustable parameters.
If no key has been pressed for 3 minutes, the operator code must be 

re-entered. 

(00

Parameter Pages

P

(L)

> 2 sec.

P

(r)

(P)

Mode

Page

(A)

Address

Page

(h)

Assign-

ment

Page

L01

r01

P10

A01

h01

1st. Parameter

on the 

P

P

P

P

(d)

d01

P

Setpoint

Page

High 

Pressure

Technical Manual 

5311437-03/02

e

/01

Stage Controller

 

            

2018-06-25, tkd/jr

 

 

from Software Vers. 2.04

 

MSR 

eco

 3140

Summary of Contents for MSR eco 3140

Page 1: ...n the Actual Values Page at L98 and L99 Programming The MSR eco parameters are simple to access view and change During normal operation or if no key is pressed for at least 3 minutes the MSR eco will...

Page 2: ...current typ 1mA 4 20 mA max shunt resistance 500 ohms Display Parameter Ranges see parameter pages Data Interfaces 3x RS 485 Data Storage unlimited Real Time Clock automatic summer winter switch 10 d...

Page 3: ...pecific sensor So1 40 25 C customer specific sensor So2 50 50 C The type of sensor can be set by h20 Assignment Page Pressure Transmitter Pressure Transmitters with 4 20mA output can be used They must...

Page 4: ...SP 0 8 stages L43 X 3 2 1 Number of running stages of motor 3 SP 0 8 stages L44 X 3 2 1 Number of running stages of motor 4 SP 0 8 stages L45 X 3 2 1 Number of running stages of motor 5 SP 0 8 stages...

Page 5: ...nimal superheat 0 0 25 0 K 0 0 K 0 0 K 0 0 K 0 0 K 0 0 K switched off P15 oem 3 2 Compound lock delay minimal superheat 5 900 sec 5 sec 5 sec 5 sec 5 sec P20 oem 3 2 Sending date and time to connected...

Page 6: ...0 sec 1 sec 1 sec 1 sec 1 sec r29 oem 3 2 VBR Forerun Backrun Range Time max 1 900 sec 20 sec 20 sec 20 sec 20 sec r41 3 2 1 Forerun Delay Time stage 1 the first turn on stage 0 900 sec 10 sec 10 sec...

Page 7: ...sec 0 sec 0 sec 0 sec d51 tec 3 2 Backrun Delay Time Stage 1 the last off stage 0 900 sec 10 sec 0 sec 0 sec 0 sec d52 tec 3 2 Backrun Delay Time Stage 2 0 900 sec 10 sec 0 sec 0 sec 0 sec d53 tec 3...

Page 8: ...tages SP motor 3 0 8 0 1 1 1 h54 tec 3 2 Number of stages SP motor 4 0 8 0 0 0 0 h55 tec 3 2 Number of stages SP motor 5 0 8 0 0 0 0 h56 tec 3 2 Number of stages SP motor 6 0 8 0 0 0 0 h57 tec 3 2 Num...

Page 9: ...ng S2 Relais K2 1 2 4 3 5 Relais K1 Digital eingang DI 1 6 10 7 9 8 Relais K3 Relais K4 Digital eingang DI 2 20 23 24 21 22 19 16 17 18 DO NDO GND Netz werk 13 14 relay K1 N 1 2 3 L 4 5 6 7 8 9 1 24 2...

Page 10: ...cted to the device Wire should be 0 5mm at a minimum Mounting the device in close proximity to power relays is NOT recommended Strong electro magnetic interference may cause the device to malfunction...

Page 11: ...trol method can be activated by the pa rameter h49 With this method only one of the compressors can be controlled Characteristicforthiscompressortypeisthefactthat the first stage generates no refriger...

Page 12: ...ctivated if the suction pressure goes beyond the hysteresis range Above and below the hysteresis range are definable areas VBR Forerun Range r41 respective VBR Backrun Range r42 If the suction pressur...

Page 13: ...01 h09 Any of these relays can also be switched on manually The relay output is switched OFF on The relay output is switched ON manually permanent alA Warning Alarm SuA Warning Suction Overheat L1 The...

Page 14: ...bus which enables up to 78 controllers to communicate For communication the E LINK transmission protocol is used Each controller in a network has its individual address P90 Mode Page Never use address...

Page 15: ...valve 1 3 St 4 CRII valve 1 2 St 3 Motor 1 CR St 1 CRII valve 1 1 St 2 1 0 1 1 1 4 0 0 0 1 Conv Compressor 20 2x1 stages Alarm Motor 1 Stage1 Motor 2 Stage 2 0 0 0 0 0 1 1 0 0 0 21 3x1 stages Alarm M...

Page 16: ...11 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D...

Reviews: