ELREHA MSR eco 3140 Technical Manual Download Page 12

Technical Manual  Stage Controller MSR 

eco

 3140

Page 12

SDS - 

Suction  Pressure  Optimization  by 

Setpoint  Shifting  with  Cold  Storage 

Controllers

Cold Storage Controllers with EEx-Valves:

When there is a reduced-power requirement, the 

setpoint of the compound should be higher than the 

set value. If there is a demand for power at a cold 

storage location, then it must ensured that the setpoint 

shifts down enough to allow the cold storage to reach 

its low setpoints. 

Within a fixed time interval it will be checked if the 

opening rate of the EEx-Valves of the connected 

controllers have exceeded a specific limit (

r18

).

If the limit has been exceeded at least at one 

cooling position, then the setpoint of the compound 

is  reduced by a certain value (

r19

). 

If the actual value of the alarm probe exceeds the 

limit at even one of the cold storage locations, the 

setpoint must be lowered.  The limit value is based 

on the switch-ON point + 

d3

.

If the following conditions occur, then the setpoint of 

the compound can be raised by a set value, ‚

r19

‘, up 

to to the maximum setpoint defined by ‚

r03

‘:

1. At least one EEx-Valve of a cold storage location  

  is below the limit ‚

r17

‘.

2. No units are running above the upper limit.

3. No cold storage location has exceeded the 

  safety limit.

Cold Storage Controllers without EEx-Valves:

In these cases, if the actual value of the alarm probe 

has  exceeded  the  limit  value,  (switching  point  + 

d03

), a reduction of the suction pressure setpoint 

will be needed. If the actual value is equal to or less 

than the limit value, the suction pressure setpoint 

can be raised. 

The setpoint utilized by the compressor control is 

based on the adjusted setpoint, ‚

r01

 or 

r02

‘, and the 

offset values, which are generated by the optimi-

zation process. The entered setpoint is the lowest 

possible setpoint.

For  each  connected  cold  storage  controller  with 

EEx-Valves two parameters are available at which 

this influence can be set up:  

d02

 .....0=off/no effect, 1=Limitation Temperature,

 

2=Limitation Temperature

 

+ Opening Degree

d03

 .....Suction Pressure Shift - Temp. Offset

The current increase/decrease values, which have 

been  produced  by  this  function,  can  be  read  at  

L31/L32

.

SP-Optimized switching by variable Forerun/

Backrun Runtimes (VBR)

If the difference between setpoint and actual value 

is small, the number of switching events should 

be reduced. Rapid changes in suction pressure 

require a quick delivery of power, which requires 

a quick reduction in the power reserve.  

This can be achieved by variable switching delays 

depending on the actual offset from the setpoint.  
This  function,  ‚

r40

‘,  is  located  on  the  Setpoint 

Page.
The forerun/backrun times will be activated if the 

suction pressure goes beyond the hysteresis 

range. Above and below the hysteresis range are 

definable areas (

VBR Forerun Range 

r41

 

respective VBR Backrun Range 

r42

). If the 

suction pressure actual value moves within this 

areas, the forerun/backrun times will be varied 

within the ranges set by 

r43

 (

VBR Forerun/

Backrun Time min

) and 

r44 

(

VBR Forerun/

Backrun Time max

). 

The bigger the difference between actual value 

and  setpoint,  the  shorter  the  time  delay.  If  the 

actual  value  leaves  the  set  range,  always  the 

smallest set delay value will be used.

If the elapsed time increases the current calcula-

ted time, the function begins to switch. 
For information 

L34

 (

Remaining time of Forerun/

Backrun

)  shows  the  current  calculated  delay 

time.

Forerun/Backrun 

Time max.

Forerun/Backrun 

Time min.

C

ur

re

nt

 s

et

po

in

t

(e

.g

. 3

.0

 b

ar

)

Backrun 

(switch off) 

Delay

Forerun 

(switch off) 

Delay

Backrun Area

Forerun Area

Hysteresis 

Range

Suction Pressure

Machines with Feedback (SP, Motor 1-4)

To detect the real state of a machine, the safety chain 

can be checked using a digital input, which has a 

feedback function, (

h31

...

h34

).

The controller switches a machine on and waits for a 

feedback signal while power is being applied to the 

digital input. If no feedback is detected, the machine 

will be switched off and a different machine will be 

selected.

r21

‘ can be used to set the waiting time. If the swit-

ching of a machine is unsuccessful, a new starting 

attempt can be initiated after an automatically 

calculated time delay.   

Switching Behaviour of the Stage Relays

The switching behaviour can be set to active (relay 

switches on) or passive (relay switches off) with the 

parameters (

h61

...

h68, SP) 

and (

h81...h88, HP

). 

With the setting '1' the stage will be inverted, with 

'0' the stage switches normally.

Load Limitation (SP)

A load limitation can be established for each of the 4 

digital inputs. This can be used during peak opera-

tion periods. Two inputs can be assigned their own 

maximum number (

r11

...

r12

) of running machines to 

provide more opportunity for energy savings.

Operating Mode of the Motors (Manual/Auto)

Each motor can be set to manual „ON/OFF“ operation 

via ‚

r61-r68

‘ for 

SP

, and ‚

d61-d68

‘ for 

HP

.  

Default „ON/OFF“ operation is set to „Auto“.

Second Setpoint (Ex. Night Operation)

Alternate setpoints can be established for energy 

savings. ‚

r01

‘ can be established as a day setpoint, 

and ‚

r02

‘ for night time.  These can be alternated via 

internal timer settings ‚

P21

‘/‘

P22

‘, or any digital input 

h31

...

h34

‘, setting 

dnl

 or 

dnh

If one of the DI inputs is configured for day/night 

switching  and  it  has  been  activated,,  the  2nd 

setpoint is active all time and cannot be changed 

by the internal timer.

If you want to use external switching only, please 

set '

P21

' and '

P22

' to „oFF“.

For night operation, the high pressure controller 

has a night offset (

d10

) and additionally a night 

limitation (

d11

) for the analogue output. 

Summary of Contents for MSR eco 3140

Page 1: ...n the Actual Values Page at L98 and L99 Programming The MSR eco parameters are simple to access view and change During normal operation or if no key is pressed for at least 3 minutes the MSR eco will...

Page 2: ...current typ 1mA 4 20 mA max shunt resistance 500 ohms Display Parameter Ranges see parameter pages Data Interfaces 3x RS 485 Data Storage unlimited Real Time Clock automatic summer winter switch 10 d...

Page 3: ...pecific sensor So1 40 25 C customer specific sensor So2 50 50 C The type of sensor can be set by h20 Assignment Page Pressure Transmitter Pressure Transmitters with 4 20mA output can be used They must...

Page 4: ...SP 0 8 stages L43 X 3 2 1 Number of running stages of motor 3 SP 0 8 stages L44 X 3 2 1 Number of running stages of motor 4 SP 0 8 stages L45 X 3 2 1 Number of running stages of motor 5 SP 0 8 stages...

Page 5: ...nimal superheat 0 0 25 0 K 0 0 K 0 0 K 0 0 K 0 0 K 0 0 K switched off P15 oem 3 2 Compound lock delay minimal superheat 5 900 sec 5 sec 5 sec 5 sec 5 sec P20 oem 3 2 Sending date and time to connected...

Page 6: ...0 sec 1 sec 1 sec 1 sec 1 sec r29 oem 3 2 VBR Forerun Backrun Range Time max 1 900 sec 20 sec 20 sec 20 sec 20 sec r41 3 2 1 Forerun Delay Time stage 1 the first turn on stage 0 900 sec 10 sec 10 sec...

Page 7: ...sec 0 sec 0 sec 0 sec d51 tec 3 2 Backrun Delay Time Stage 1 the last off stage 0 900 sec 10 sec 0 sec 0 sec 0 sec d52 tec 3 2 Backrun Delay Time Stage 2 0 900 sec 10 sec 0 sec 0 sec 0 sec d53 tec 3...

Page 8: ...tages SP motor 3 0 8 0 1 1 1 h54 tec 3 2 Number of stages SP motor 4 0 8 0 0 0 0 h55 tec 3 2 Number of stages SP motor 5 0 8 0 0 0 0 h56 tec 3 2 Number of stages SP motor 6 0 8 0 0 0 0 h57 tec 3 2 Num...

Page 9: ...ng S2 Relais K2 1 2 4 3 5 Relais K1 Digital eingang DI 1 6 10 7 9 8 Relais K3 Relais K4 Digital eingang DI 2 20 23 24 21 22 19 16 17 18 DO NDO GND Netz werk 13 14 relay K1 N 1 2 3 L 4 5 6 7 8 9 1 24 2...

Page 10: ...cted to the device Wire should be 0 5mm at a minimum Mounting the device in close proximity to power relays is NOT recommended Strong electro magnetic interference may cause the device to malfunction...

Page 11: ...trol method can be activated by the pa rameter h49 With this method only one of the compressors can be controlled Characteristicforthiscompressortypeisthefactthat the first stage generates no refriger...

Page 12: ...ctivated if the suction pressure goes beyond the hysteresis range Above and below the hysteresis range are definable areas VBR Forerun Range r41 respective VBR Backrun Range r42 If the suction pressur...

Page 13: ...01 h09 Any of these relays can also be switched on manually The relay output is switched OFF on The relay output is switched ON manually permanent alA Warning Alarm SuA Warning Suction Overheat L1 The...

Page 14: ...bus which enables up to 78 controllers to communicate For communication the E LINK transmission protocol is used Each controller in a network has its individual address P90 Mode Page Never use address...

Page 15: ...valve 1 3 St 4 CRII valve 1 2 St 3 Motor 1 CR St 1 CRII valve 1 1 St 2 1 0 1 1 1 4 0 0 0 1 Conv Compressor 20 2x1 stages Alarm Motor 1 Stage1 Motor 2 Stage 2 0 0 0 0 0 1 1 0 0 0 21 3x1 stages Alarm M...

Page 16: ...11 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D...

Reviews: