ELREHA MSR eco 3140 Technical Manual Download Page 6

Technical Manual  Stage Controller MSR 

eco

 3140

Page 6

Param Co   Level  Note 

Range 

Cf1 

Cf2 

Cf3 

Cf4

r01

  ......--- .......3, 2, 1 ...... Setpoint 1 (day)  ....................................................................-99,9...+100,0°C .......-10,0°C  .....-10,0°C ....... -10,0°C ........-10,0°C

r02

  ......--- .......3, 2, 1 ...... Setpoint 2 (night)  ..................................................................-99,9...+100,0°C .......-10,0°C ......-10,0°C ....... -10,0°C ........-10,0°C

r03

  ......--- .......3, 2, 1 ...... Setpoint maximum ................................................................-99,9...+100,0°C .......0,0°C .........10,0°C ........ 10,0°C .........10,0°C

r04

  ......--- .......3, 2, 1 ...... Hysteresis ..............................................................................0,1...20,0K.................2.0 K ..........2.0 K ........... 2.0 K ............2.0 K

r05

  ......oem ....3, 2 .......... Hysteresis Position ...............................................................H-- = symmetrical .....H-- .............H-- .............. H-- ................H--

   

     

 

H-- = below the 

   

     

 

         setpoint

   

     

 

H-- = above the 

   

     

 

         setpoint

r06

  ......oem ....3, 2 .......... Alarm limit ..............................................................................-99,9...+100,0°C .......-20,0°C ......-99,9°C .......-99,9°C ........-99,9°C

r07

  ......oem ....3, 2 .......... Pre-alarm limit  ......................................................................-99,9...+100,0°C .......-18,0°C ......-99,9°C .......-99,9°C ........-99,9°C

r08

  ......oem ....3, 2 .......... Pre-alarm delay .....................................................................1...600 sec. ...............10 sec........600 sec .......600 sec .......600 sec

r11

  ......oem ....3, 2 .......... Load Limitation 1 (max. running motors) .............................0...8 motors ...............8 ................8 ..................8 ..................8

r12

  ......oem ....3, 2 .......... Load Limitation 2 (max. running motors) .............................0...8 motors ...............8 ................8 ..................8 ..................8

r13

  ......oem ....3, 2 .......... PI analogue output proportional band/range .......................0.1...30.0 K................5.0 K ..........5.0 K ...........5.0 K ............5.0 K

r14

  ......oem ....3, 2 .......... PI analogue output integral time ...........................................0...600 sec.  ..............60 sec........60 sec. ........60 sec. ........60 sec

r15

  ......oem ....3, 2 .......... PI analogue output output delay...........................................0...100 sec. ...............20 sec........20 sec. ........20 sec. ........20 sec

r16

  ......oem ....3, 2 .......... PI analogue output step size ................................................1...100% ....................10% ...........10% .............10% .............10%

r17

  ......oem ....3, 2 .......... Suction pressure shifting EEx-Valve percentage 

   

 

   

 

of opening lower limit (of connected controllers) ....................0...100% ....................20% ...........20% .............20% .............20%

r18

  ......oem ....3, 2 .......... Suction pressure shifting EEx-Valve percentage  

   

 

   

 

of opening upper limit (of connected controllers) ....................0...100% ....................80% ...........80% .............80% .............80%

r19

  ......oem ....3, 2 .......... Suction pressure shifting step width ..................................... 0...20,0K ....................1,0K ...........1,0K ............1,0K .............1,0K

   

 

   

 

(of connected controllers)

r20

  ......oem ....3, 2 .......... Stage controller - Steady state time .....................................10...540 min...............540 min. .....540 min. ...... 540 min. ......540 min.

r21

  ......oem ....3, 2 .......... Stage controller - Operational-Feedback Time ....................5...600 sec. ................30 sec. .......30 sec. ........ 30 sec. ........30 sec.

r22

  ......oem ....3, 2 .......... Stage controller - Base Load Change (Stage Sequencing) ..000 = off/off/off  .........hr1 .............hr1 ...............hr1 ...............hr1

   

     

 

....a..../....b..../....c....  

   

     

 

At position a, these base load functions can be set: 

rr0=runt./runt./off

   

     

 

0=off, r=forerun dep. on runtime, h=for. dep. on stop time  hr0=stopt./runt./off 

   

     

 

At position b, these base load function can be set: 

rr1=runt./runt./on

   

     

 

0 = off, r = backrun dep. on runtime, 

hr1=stopt./runt./on

   

     

 

At position c, these base load functions can be set: 

   

     

 

Switch optimization: 0 = off, 1 = on

r23

  ......oem ....3, 2 .......... Idle Time of the stage with 0% load .....................................0...900 sec. ...............5 sec. ......... 5 sec. .......... 5 sec. ..........5 sec.

r24

  ......oem ....3, 2 .......... Timeout of 0% control. If no power stage is activated,  

   

 

 

   

 

the motor switches off after: ..................................................0...900 sec.  ..............120 sec.  120 sec. ...... 120 sec. ......120 sec.

r25

  ......oem ....3, 2 .......... Variable forerun-/backrun delays  .........................................on, oFF ......................oFF ............ oFF ............. oFF .............oFF

   

        

 

(

VBR

, Switching Frequency Optimization)

r26

  ......oem ....3, 2 .......... VBR Forerun Range .............................................................0,5...20,0 K................0,5 K .......... 0,5 K ........... 0,5 K ...........0,5 K

r27

  ......oem ....3, 2 .......... VBR Backrun Range ............................................................0,5...20,0 K................0,5 K .......... 0,5 K ........... 0,5 K ...........0,5 K

r28

  ......oem ....3, 2 .......... VBR Forerun/Backrun Range Time min. .............................1...900 sec. ...............1 sec. ......... 1 sec. .......... 1 sec. ..........1 sec.

r29

  ......oem ....3, 2 .......... VBR Forerun/Backrun Range Time max. ............................1...900 sec. ...............20 sec........ 20 sec. ........ 20 sec. ........20 sec.

r41

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 1 (the first turn on stage) ...........0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r42

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 2 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r43

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 3 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r44

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 4 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r45

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 5 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r46

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 6 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r47

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 7 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r48

  ......--- .......3, 2, 1 ...... Forerun Delay Time stage 8 .................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r51

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 1 (the last off stage) ..................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r52

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 2 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r53

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 3 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r54

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 4 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r55

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 5 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r56

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 6 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r57

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 7 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r58

  ......--- .......3, 2, 1 ...... Backrun Delay Time stage 8 ................................................0...900 sec. ................10 sec. ....... 10 sec..........10 sec. ........10 sec.

r61

  .......oem ...3, 2 ...........Motor 1 automatic / manually ...............................................oFF, Aut (autom.)  ......Aut ...............Aut .................Aut .............Aut

   

 

 

 

 

on (permanent on)

r62

  .......oem ...3, 2 ...........Motor 2 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r63

  .......oem ...3, 2 ...........Motor 3 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r64

  .......oem ...3, 2 ...........Motor 4 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r65

  .......oem ...3, 2 ...........Motor 5 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r66

  .......oem ...3, 2 ...........Motor 6 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r67

  .......oem ...3, 2 ...........Motor 7 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r68

  .......oem ...3, 2 ...........Motor 8 automatic / manually ...............................................ditto. ............................Aut ...............Aut .................Aut .............Aut

r71

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 1 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r72

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 2 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r73

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 3 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r74

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 4 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r75

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 5 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r76

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 6 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r77

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 7 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

r78

  .......--- .......3, 2, 1 .......Minimum Idle Time Motor 8 ..................................................0...20 min. .................0 min. .........0 min. ...........0 min. ........0 min.

Setpoint Page Suction Pressure 

(r)

Notice

If this point is ON while displaying a 

parameter number, this parameter 

is active at present.

Hinweis

Parameters marked by "

nA

" are for information only 

and cannot be changed.

"

Co

" is the password/code for this parameter.

The 3 code numbers are:

-  OEM-Code (

oem

) : Month + Hour + 20

-   Technician Code (

tec

) : 88

-   Customer Code (

---

): without code

Summary of Contents for MSR eco 3140

Page 1: ...n the Actual Values Page at L98 and L99 Programming The MSR eco parameters are simple to access view and change During normal operation or if no key is pressed for at least 3 minutes the MSR eco will...

Page 2: ...current typ 1mA 4 20 mA max shunt resistance 500 ohms Display Parameter Ranges see parameter pages Data Interfaces 3x RS 485 Data Storage unlimited Real Time Clock automatic summer winter switch 10 d...

Page 3: ...pecific sensor So1 40 25 C customer specific sensor So2 50 50 C The type of sensor can be set by h20 Assignment Page Pressure Transmitter Pressure Transmitters with 4 20mA output can be used They must...

Page 4: ...SP 0 8 stages L43 X 3 2 1 Number of running stages of motor 3 SP 0 8 stages L44 X 3 2 1 Number of running stages of motor 4 SP 0 8 stages L45 X 3 2 1 Number of running stages of motor 5 SP 0 8 stages...

Page 5: ...nimal superheat 0 0 25 0 K 0 0 K 0 0 K 0 0 K 0 0 K 0 0 K switched off P15 oem 3 2 Compound lock delay minimal superheat 5 900 sec 5 sec 5 sec 5 sec 5 sec P20 oem 3 2 Sending date and time to connected...

Page 6: ...0 sec 1 sec 1 sec 1 sec 1 sec r29 oem 3 2 VBR Forerun Backrun Range Time max 1 900 sec 20 sec 20 sec 20 sec 20 sec r41 3 2 1 Forerun Delay Time stage 1 the first turn on stage 0 900 sec 10 sec 10 sec...

Page 7: ...sec 0 sec 0 sec 0 sec d51 tec 3 2 Backrun Delay Time Stage 1 the last off stage 0 900 sec 10 sec 0 sec 0 sec 0 sec d52 tec 3 2 Backrun Delay Time Stage 2 0 900 sec 10 sec 0 sec 0 sec 0 sec d53 tec 3...

Page 8: ...tages SP motor 3 0 8 0 1 1 1 h54 tec 3 2 Number of stages SP motor 4 0 8 0 0 0 0 h55 tec 3 2 Number of stages SP motor 5 0 8 0 0 0 0 h56 tec 3 2 Number of stages SP motor 6 0 8 0 0 0 0 h57 tec 3 2 Num...

Page 9: ...ng S2 Relais K2 1 2 4 3 5 Relais K1 Digital eingang DI 1 6 10 7 9 8 Relais K3 Relais K4 Digital eingang DI 2 20 23 24 21 22 19 16 17 18 DO NDO GND Netz werk 13 14 relay K1 N 1 2 3 L 4 5 6 7 8 9 1 24 2...

Page 10: ...cted to the device Wire should be 0 5mm at a minimum Mounting the device in close proximity to power relays is NOT recommended Strong electro magnetic interference may cause the device to malfunction...

Page 11: ...trol method can be activated by the pa rameter h49 With this method only one of the compressors can be controlled Characteristicforthiscompressortypeisthefactthat the first stage generates no refriger...

Page 12: ...ctivated if the suction pressure goes beyond the hysteresis range Above and below the hysteresis range are definable areas VBR Forerun Range r41 respective VBR Backrun Range r42 If the suction pressur...

Page 13: ...01 h09 Any of these relays can also be switched on manually The relay output is switched OFF on The relay output is switched ON manually permanent alA Warning Alarm SuA Warning Suction Overheat L1 The...

Page 14: ...bus which enables up to 78 controllers to communicate For communication the E LINK transmission protocol is used Each controller in a network has its individual address P90 Mode Page Never use address...

Page 15: ...valve 1 3 St 4 CRII valve 1 2 St 3 Motor 1 CR St 1 CRII valve 1 1 St 2 1 0 1 1 1 4 0 0 0 1 Conv Compressor 20 2x1 stages Alarm Motor 1 Stage1 Motor 2 Stage 2 0 0 0 0 0 1 1 0 0 0 21 3x1 stages Alarm M...

Page 16: ...11 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D...

Reviews: