Technical Manual MiniMEP Data Loggers

page 2

  Contents

page

General Description ............................................. 2
Operating ............................................................. 3

Programming Access Authorization,
Reset Error Messages, Buzzer/Relay Test,
Error Messages / -codes

Functional Description ......................................... 4

Programming designations .............................. 4

Parameter listing (2)434A, (2)534A .................... 5
Parameter listing (2)404S, (2)424A, (2)524A ..... 6
Connection, Versions 4xx .................................... 7
Connection, Versions 5xx .................................... 9
Dimensons ........................................................... 10
Processing of Data, PC connection,
Unlock of recording system ................................. 11
Installation ........................................................... 12

Cable lenghts ................................................... 12

Connection and Safety Notes

....................... 12

Accu operation

............................................... 12

Start-up ................................................................ 12
Technical Data / Accessories .............................. 13
CE-Statement of Conformity ............................... 14

Appendix: Drilling template, calibration and start-up report

 General Description

The MiniMEP data logger series is developed for paperless
recording of temperature resp. humidity values and to store them
for a long period of time.
The unit measures temperatures by high accurate platinium
sensors and stores the values in a non-volatile memory for
unlimited time.

Without additional utilities, the user is able to recall every
recorded value with its date, time and position designation.

If this memory is full, the oldest recorded values will be erased to
get space for the newest values.

The units are available in 2 different housings and memory sizes
(see overview below).

A special version (MiniMEP 434 A/534 A) can record 2 temperature
values and the values of two 4...20 mA-humidity transmitters.

Type-

Housing

Inputs

Recording

Digital

Alarm Limits

LC-

Input for

Memory Cap- Supply

Overview

Range

inputs

Alarm relays Display additional- acity with 15

Accu

min. interval

MiniMEP 404 S

wall mounting

4x temp.

-110/+600°C --

--

X

--

366 days

230V

MiniMEP 2404 S

wall mounting

4x temp.

-110/+600°C --

--

X

--

366 days

115V

MiniMEP 424 A

wall mounting

4x temp.

-110/+600°C 3x 230V

1x SPDT

X

X

appr. 6 years

230V

MiniMEP 2424 A

wall mounting

4x temp.

-110/+600°C 3x 115V

1x SPDT

X

X

appr. 6 years

115V

MiniMEP 424/12V

wall mounting

4x temp.

-110/+600°C 3x 12VDC

1x SPDT

X

X

appr. 6 years

12V

MiniMEP 434 A

wall mounting

2x temp.

-110/+600°C 3x 230V

1x SPDT

X

X

appr. 6 years

230V

2x humidity  0/100% r.F.

MiniMEP 2434 A

wall mounting

2x temp.

-110/+600°C 3x 115V

1x SPDT

X

X

appr. 6 years

115V

2x humidity  0/100% r.F.

MiniMEP 524 A

panel mounting 4x temp.

-110/+600°C 3x 230V

1x SPDT

X

X

appr. 6 years

230V

MiniMEP 2524 A

panel mounting 4x temp.

-110/+600°C 3x 115V

1x SPDT

X

X

appr. 6 years

115V

MiniMEP 534 A

panel mounting 2x temp.

-110/+600°C 3x 230V

1x SPDT

X

X

appr. 6 years

230V

2x humidity  0/100% r.F.

MiniMEP 2534 A

panel mounting 2x temp.

-110/+600°C 3x 115V

1x SPDT

X

X

appr. 6 years

115V

2x humidity  0/100% r.F.

 Note

The temperature recording system MiniMEP corresponds to
the requirements of the european standard EN 12830.

Please note  that according to the standard EN 13486, the
end-user is bound to a continuous check of the units for
operation and accuracy.

Summary of Contents for MiniMEP 2404S

Page 1: ...minute interval Example 2 6 years with a 15 min interval z Data storage is unlimited even without mains voltage z Real time clock with typ 10 years battery backup z Continuous recording by external le...

Page 2: ...4A 534A canrecord2temperature values and the values of two 4 20 mA humidity transmitters Type Housing Inputs Recording Digital Alarm Limits LC Input for Memory Cap Supply Overview Range inputs Alarm r...

Page 3: ...01 07 96 14 15 sensor 2 21 0 C 01 07 96 14 30 01 07 96 14 45 01 07 96 15 00 P P MINIMEP serial no 000000 01 07 96 14 30 01 07 96 15 00 01 07 96 14 45 correction probe selection push for longer than 1...

Page 4: ...abled during accu operation Real time clock The integrated x tal controlled real time clock can be corrected by only 24 hours Theautomaticsummer winter shiftcanbedisabledforexportpurposes Without main...

Page 5: ...delay is run down an alarm message will be generated 0 01 4 00 h min 1 00 h min name transm 3 individual name for this probe input max 8 characters see table transmitter 3 probe 4 corr 1 the last fou...

Page 6: ...l be generated 0 01 4 00 h min 1 00 h min name probe 3 individual name for this probe input max 8 characters see table probe 3 probe 4 corr 1 the last four corrections of this input with time to date...

Page 7: ...mains ph L report input 2 al2 mains ph alarm relay N O contact Mains neutral alrm relay N C contact alarm relay common PE 1 2 3 4 5 6 7 8 9 RS 232 Interface MiniMEP 4xx RS 232 interface connector The...

Page 8: ...14 input 1 4 20mA 15 input 1 4 20mA 16 probe 2 17 probe 2 com 18 input 3 4 20mA 19 input 3 4 20mA 20 probe 4 21 probe 4 com 22 n c 23 RxD RS 232 24 GND RS 232 25 TxD RS 232 51 R 51 R 11 13 15 17 19 21...

Page 9: ...t A don t need the cables between terminals 37 and 38 TxD data out RxD data in 1 4 2 3 5 Stecker SUB D 9 polig male 7 6 9 8 GND 31 32 16 17 to controller unit PE Mains N Mains Line L Input 1 L Input 2...

Page 10: ...16 17 18 19 ELREHA 63 47 34 35 36 37 38 34 35 36 37 38 93 105 L Eing 1 NK L Eing 2 TK L Ein 3 T r Dimensions of MiniMEP 4xx types Dimensions Terminals of MiniMEP 2 524 A 2 534 A Operating Unit Verbin...

Page 11: ...ler an unlock code must be entered while start up You get this unlock code with the software please see software manual for further information Without this code retrieve and processing of data with t...

Page 12: ...y please contact the manufacturer first Electrical installation and putting into service must be done from authorized personnel Please note the local safety instructions Before installation Check the...

Page 13: ...m relay SPDT isolated 4A cos phi 1 250V Interfaces RS 232 RS 485 Accu interface Chargecontrollerfor1 3AhLeadAccus not types 404 S 2404 S 424 12V Data memory see type overview Real time clock automatic...

Page 14: ...heir companies copy We state the following When operated in accordance with the technical manual the criteria have been met that are outlined in the guidelines of the council for alignment of statutor...