background image

ELOE171ZKE001

 

        

 

 

1.0 

Introduction 

Fiber  Optic  (SINGLE  MODE  and/or  MULTI  MODE)  has  been  used  for  signal 

transmission in automation for communication more and more often. 

The  main  advantage  of  Fiber  Optic  is  its  immunity  to  electromagnetic  interference, 

slight radiation and high transmission capacity 

 

1.1 

Use of the converter 

Conversion of metallic media to more expensive fiber optic is mainly suitable: 

 

 

1] in the environment of high interference level, 

2] if the higher isolation is required, (switching stations, transformers), 

 

 

3] if the metallic line can not be used because of EMI , 

 

 

4] if the higher transport security and safety is necessary, 

 

 

5] if isolation via the optocouplers is not suitable for  

 

 

    different reasons 

These problems can be solved if the converter ELO E 171 (MULTI MODE) is applied. 

 

2.0 

Operation principles 

ELO E171 transfers signal received from RS-485 interface to transmitting fiber of the 

optic cable and the signal from receiving fiber is transmitted to RS-485. 

Besides the signal transfer, the converter matches the full duplex fiber to the half duplex 

RS-485 (data-flow direction switching). 

Its independent operation is based on the set data rate (1200 to 115200 bps) and data 

format  which  must  be  asynchronous  of  10  and/or  11bits  (start  bit,  8  to  9  information 

bits, stop bit).  The switching speed is sufficient to use the converter in data transmission 

network organized as MASTER-SLAVE and MULTI MASTER. 

The converter also corrects bits width distortion which could occur during transmission. 

For fiber optic connection optical connector ST is used as standard. 

 

3.0 

Installation 

There are two different problems of installation to discuss: 

RS-485  link  and  fiber  optic  link  connection  and  setting 

characteristics of the converter. 

The  converter  needs  data  range  and  data  format  setting 

(asynchronous word length). There is the rotating switch on 

the top converter case (see the figure). Switch slot points to 

the light and dark scale sector at the same time. If the LED “data format” is alight, 9 bits 

data format is set (e.g.8 data bits and a parity bit), if it is not alight 8 bits format is 

    1.2

     2.4

     4

.8

    

 9.

6

    

19

.2

    3

8.4

    5

7.6

   1

15.2

9 bits

run

data 

format

8 bits

Summary of Contents for E171

Page 1: ...RS 485 to Multimode Fibre Optic Converter ELO E171 Operation manual ...

Page 2: ...onverter 3 2 0 Operation principles 3 3 0 Installation 3 3 1 RS 485 Interface Connection 4 3 2 Fibre Link Connection 5 3 3 Power Connection 5 4 0 Specification 5 4 1 Parameters 5 4 2 Other 6 5 0 Testing 6 6 0 Troubleshooting 6 7 0 Ordering Information 6 ...

Page 3: ...s the signal transfer the converter matches the full duplex fiber to the half duplex RS 485 data flow direction switching Its independent operation is based on the set data rate 1200 to 115200 bps and data format which must be asynchronous of 10 and or 11bits start bit 8 to 9 information bits stop bit The switching speed is sufficient to use the converter in data transmission network organized as ...

Page 4: ...d they influence the transfer immunity against interference Inserting the optical converter into the metallic link terminates this link right on the A B clamps of the converter therefore it is necessary to connect the passive converter There are also the active terminators beside the passive ones Only one active terminator can be installed to one metallic section of the link and its role is as fol...

Page 5: ... is on operation the indicator RUN switches on The converter contains two isolated zones The RS 485 circuits are separated from the other ones and supplied via the internal isolated DC DC converter If it is necessary to keep this separation the external power supply must be isolated from the signal grounds of all RS 485 partners 4 0 Specification 4 1 Parameters Transmitted signals differential sig...

Page 6: ...be alight The TxD and RxD indicators must blink during transmission 6 0 Troubleshooting Symptom Action ELO 171 does not work Check if the RUN is alight after installation Check the power supply Check the RS 485 link connection Connection in normal Check the power supply operation quit working Check if the cables are OK Turn off and on the power supply and detect if the converter starts again 7 0 O...

Page 7: ...ELOE171ZKE001 7 Note ...

Page 8: ...ELOE171ZKE001 8 ...