background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200607_01D    Jan 2021                    ©2019 ELMDENE INTERNATIONAL LTD  

 
 

Fault Diagnostic table 

 Internal - Engineer 

Orange LED 

Diagnostic 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal operation 

Mains present 
Battery fully charged 

None 

O

FF

 

Standby 

Operation 

Mains Lost. No faults present 
Battery driving load 

Investigate loss of mains 

F

LASH 

C

ONTINUOUS

 

O

N

 or O

FF

 

No output 

Output fuse blown 
Output overload 
Output short circuit 

Check and replace output 
fuse 
Disconnect output load 
and test load 

1

 

P

ULSE

 

O

N

 

Battery Charging 

No faults active 
Battery charging normally but 
 < 90% of full charge 

None 

2

 

P

ULSES

 

O

N

 

No Battery 

Battery disconnected 
Battery fuse blown 
Battery heavily discharged 

Check battery 
connections 
Check battery fuse 
Check battery condition 
Replace battery if aged 

O

FF

 

Low Battery Volts 

Standby Mode 
Battery almost discharged 

Restore mains 

3

 

P

ULSES

 

O

N

 or O

FF

 

Battery Fault 

High impedance in battery 
connection 
Battery internal fault 

Check battery 
connections for 
corrosion. Replace 
battery if aged 

4

 

P

ULSES

 

O

N

 or O

FF

 

Charger Fault 

Internal failure of battery charger 

Return to manufacturer 

5

 

P

ULSES

 

O

N

 or O

FF

 

Battery 

Temperature 

Probe Fault 

Battery temperature monitor 
disconnected or damaged 
PSU running in Safe Mode  

Check temperature 
sensor connections and 
condition of sensor. 
Replace if suspect 

 

Summary of Contents for STX2401-MOD

Page 1: ...arge protection prevents premature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault cha...

Page 2: ...charging Imax A 1 5A 1 2A 1 5A 1 2A Battery Capacity eg PowerSonic model Yuasa model 2 x 1 2Ah 12V PS12021 NP1 2 12 2 x 7Ah 12V PS12070 NP7 12 Battery Charging Constant current bulk charging to 80 cap...

Page 3: ...S Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains C...

Page 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Page 5: ...ard with a 5A or greater current capacity i e 0 75mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 2 The low voltage output cable must be sized to carry the rated load curr...

Page 6: ...Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figure 2 and 3 13 Connect the battery temperature sensor two white wires to the PCB terminals Temp...

Page 7: ...ENANCE This unit is intended for use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing and replacemen...

Page 8: ...ed via an appropriate approved WEEE disposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an app...

Reviews: