background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200790_02A Oct 2019                        ©2019 ELMDENE INTERNATIONAL LTD  

16.

 

Connect the load (output) wiring as shown here. Cable tie to fixing point provided (adjacent to exit 
hole).  

17.

 

If only one load is connected, the PSU will continue to monitor both outputs 

Warning: do not overload the PSU, the ImaxA and ImaxB value is shared between both outputs 

 

18.

 

Re-apply mains. Verify the following 

 

LED # 

Symbol 

LED Colour

 

Function

 

Mains 

Constant Green 

Indication: Mains supply = OK 

Batt 

Constant Yellow 

Indication: Battery Fault = missing battery indicated

 

Fault 

Yellow FLASH x1 

(repeating) 

Indication: Fault with PSU = due to missing battery 

Diagnostic 

Red FLASH x2 (repeating) 

Indication: Fault = missing battery indicated 

OP1* 

Constant Green 

Indication: Output 1 = OK 

OP2* 

Constant Green 

Indication: Output 2 = OK 

 

19.

 

If connected, verify that the EPS Fault monitor shows a (com to n/c) 

CLOSED

 contact and the GEN PSU 

Fault monitor shows an (com to n/c) 

OPEN

 contact. 

20.

 

Perform a full functional test of the connected system (load) including full alarm condition, then 
disconnect the mains supply. 
 

Battery Charger 

21.

 

Set the correct charger mode by fitting the jumper to the appropriate charger mode header.  
Use the table below to select the appropriate charger mode 

 

EN54-4 

Continuous Output Current 

No charging (

Imax B

With Charging (

Imax A

)) 

 
 

1.35 A  

 (b) 1.0 A 

Constant current charge 

0.35 A 

EN12101-10 (ImaxB) 

For 180s at end of standby period

 

1.35 A 

Battery Capacity (2x 12V) 

1.2Ah

 

2.1Ah

 

7Ah

 

EN12101-10 Max 

Standby current

  

(Imax Standby)

 

4hr standby 

0.19A 

0.35A 

1.10 A 

24hr standby 

Not Specified 

0.80 A 

(a) 0.25 A 

72hr standby 

Not Specified 

Not Specified 

0.10 A 

 
 
 
 

a.

 

EXAMPLE (a):

  for EN12101 AOV systems, an 2401ST, with 2x 7Ah batteries, can maintain 

250mA

 load for 

24hrs

 and will be able to deliver 

1.35A

 (ImaxB) for 180s at the end of that 

period 

 

b.

 

EXAMPLE (b):

 for EN54 Fire systems, an 2401ST, with 2x 2.1Ah batteries, can support a 

maximum of 

1.0A

 (ImaxA) load whilst charging the batteries 

 
 
 
 
 
 
 
 

 

Summary of Contents for 2401ST

Page 1: ...ion remote fault signalling Load connection 5 Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final c...

Page 2: ...HF Current Limitation Short circuit protection From In to In 15 for an output voltage 50 Un Fuse Load OP1 and OP2 F1 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacit...

Page 3: ...ns 3 Where the PSE is used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the app...

Page 4: ...isconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED CO...

Page 5: ...to n c CLOSED contact and the GEN PSU Fault monitor shows an com to n c OPEN contact 20 Perform a full functional test of the connected system load including full alarm condition then disconnect the...

Page 6: ...SE and CIE in separate enclosures is used all cabling between the two boxes should be routed to use separate case entry exit holes from other cabling using suitable cable glands to protect the cables...

Page 7: ...w Fault LED 3 starts to flash indicating that the PSE is running from its standby batteries 32 If connected verify that the EPS Fault output shows an open contact com and n c terminals open circuit an...

Page 8: ...with the battery leads Continue to observe caution with all exposed conductors when inserting or removing the meter and when restoring normal battery wiring 40 Close cover and secure using fastening...

Page 9: ...se Action GREEN YELLOW Fast Flash Battery in process of connecting Battery connecting No action Wait for battery connection to complete GREEN Flash x1 Normal operation Battery connected Battery in bul...

Page 10: ...charger Return to manufacturer RED Flash x5 Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condi...

Page 11: ...This product falls within the scope of EU Directives 2012 19 EU Waste Electrical and Electronic Equipment WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic...

Page 12: ...A2 EN12101 10 2005 Environmental Class I Equipment Class A Suitable for all systems VdS 2541 1996 12 Environmental Class III Certification Bodies AFNOR CNPP VdS Declaration of Performance DOP2018 020...

Page 13: ...ezifikation des Netzteils 3 Installation Netzeinspeisung Kabelquerschnitt Montagegeh use 4 Installation Forts Netzanschluss Fernfehlermeldung Lastanschluss 5 Installation Forts Einstellungen des Batte...

Page 14: ...ung HF Strombegrenzung Kurzschlussschutz Von In bis In 15 f r eine Ausgangsspannung 50 Un Sicherung Last OP1 und OP2 F 1 0 A Typ IEC 60127 2 Aufladen der Batterie Aufladen mit konstantem Ladestrom Vol...

Page 15: ...ndungen eingesetzt wird sollte sie gem allen f r diese Anwendungen relevanten Sicherheitsvorschriften installiert werden Kabelquerschnitt 4 Das Netzkabel muss dem geltenden Standard entsprechen und ei...

Page 16: ...P1 Konstant gr n Anzeige Ausgang 1 OK 6 OP2 Konstant gr n Anzeige Ausgang 2 OK F r vollst ndige Details der LED Anzeigen siehe auch Tabelle LED Anzeige f r Status und Fehlerdiagnose 13 Trennen Sie die...

Page 17: ...hlender Batterie 4 Diagnose Rot BLINKEND x2 wiederholt Anzeige Fehler fehlende Batterie wird angezeigt 5 OP1 Konstant gr n Anzeige Ausgang 1 OK 6 OP2 Konstant gr n Anzeige Ausgang 2 OK 19 Wenn angesch...

Page 18: ...r jede Batterieoption 24 Stellen Sie sicher dass alle Batterieklemmen ausreichend isoliert sind um ein unbeabsichtigtes Kurzschlie en untereinander oder mit den Metallteilen des Geh uses zu verhinder...

Page 19: ...lossen werden Dies wird jedoch NICHT EMPFOHLEN da dies auf besch digte Batterien hindeuten k nnte Um Batterien bis zu einer Spannung von 19V anzuschlie en trennen Sie vorsichtig einen wei en Temperatu...

Page 20: ...als 1 Minute die folgenden Bedingungen erf llt sind LED Symbol Gr n EIN Funktion 1 Batt Konstant gelb Anzeige Batteriefehler fehlende Batterie wird angezeigt 2 Fehler Gelb blinkend x1 wiederholt Anzei...

Page 21: ...ladenen Batterie Der Fehler sollte behoben werden bevor die Stromversorgung der PSE wiederhergestellt wird Wenn eine der Sicherungen ausgetauscht werden muss stellen Sie sicher dass die richtige Siche...

Page 22: ...2 Zustand M gliche Ursache Ma nahme GR N GELB Schnelles Blinken Batterie wird gerade angeschlossen Batterieanschluss Keine Ma nahme Warten bis die Batterieverbindung abgeschlossen ist GR N blinkend x...

Page 23: ...ehler des Batterietemperaturf hlers berwachungsger t der Batterietemperatur nicht angeschlossen oder besch digt Netzteil l uft im abgesicherten Modus Anschl sse des Temperatursensors und Zustand des S...

Page 24: ...et Netzspannung Ausgang1 Spannung Strom Ausgang2 Spannung Strom Batteriespannung Strom des Ladeger ts GEN Fehlerzustand EPS Fehlerzustand Diagnose Fehlerstatus Zustand 1 6 Batterietemperatur Status de...

Page 25: ...der Quecksilber Hg beinhalten Weitere Informationen finden Sie unter www recyclethis info Die mit diesem Produkt gelieferte Verpackung kann recycelt werden Bitte entsorgen Sie die Verpackung entsprech...

Reviews: