Figure 4
–
Terminal layout and mode selection
Dual-Path power transmission monitoring feature
41.
The 2401ST PSU has an optional mode designed to
work with systems that require dual-power
transmission paths. When enabled, the PSU compares
the outputs and reports a load imbalance of more than
10% as an OUTPUT FAULT (LED 4 x6 Flashes) and is
enabled by removing the header marked
OP1
≠
OP2
This mode meets the requirements of EN54-13 Section
5.3.3.1 S
FAULT
and Section 5.3.4.2 P
FAULT
warning
conditions, for loads above 200mA.
It is still necessary for the connected equipment to be
designed to accept two separate power inputs, such
that a short to ground of either power transmission
path, will not inhibit the equipment performance.
PSU Addressable Data link communication protocol
42.
The 2401ST PSU has an addressable RS485 communication port, that can be enabled to provide the
internal PSU data, and includes; Mains Voltage; Output1 Voltage/Current; Output2 Voltage/Current;
Battery Voltage; Charger Current; GEN Fault condition; EPS Fault condition; Diagnostics fault status
(condition 1-6), Battery temperature, Charger status, unit address
43.
To enable this feature and obtain the protocol guide, please contact Elmdene Technical Support
D
ISPOSAL OF
P
RODUCT AT
E
ND OF
L
IFE
This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and 2013/56/EU (Battery). At
the end of life, the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route
in accordance with all national and local regulations.
Before disposal of the product, any batteries must be removed, and disposed separately via an appropriate approved battery disposal route in
accordance with all national and local regulations. Package used batteries safely for onward transport to your supplier, collection point or
disposal facility.
Caution: Risk of fire or explosion if bare battery wires are allowed to touch.
See Specification for battery type information. The battery is marked with the crossed-out wheelie bin symbol, which may include lettering to
indicate cadmium (Cd), lead (Pb), or mercury (Hg).
For more information see:
The packaging supplied with this product may be recycled. Please dispose of packaging accordingly.
Mains
Input
Load
Outputs
Battery
Connection
GEN & EPS
Relay Outputs
‘No battery’
Select
Unit Add
Select
RS485
Link
Temp Probe
Inputs
OP2
Fuse
PTC Battery
Fuse
OP1 ≠ OP2
Select
LED Status
Indicators
Charger
Setting
OP1
Fuse
Mains
Fuse
OP1≠OP2
DUAL-PATH ACTIVE
DUAL-PATH MODE FAULT SIGNALLING
-
PSU LOAD OUTPUT
1 & 2
+
DU AL PATH LOAD I NPUT
-
+
-
+
•
FA ULT SIGNALLED WHEN
M O RE T HAN 1 0%
I M BALANCE BETWEEN
P A THS
RE F: E N 54-13 5 .3 .4.1 S
FAULT
& 5 .3 .4 .2 P
FAULT
V ALUES
+
-
* E quipment mus t be have 2 s eparate power inputs c apable of
withs tanding a s hort to ground on one path