26/44
HPA702L-LG/N
3.1 FACTORY PROGRAMMING
Siren options are programmable through a series of cutting-wire jumpers, that can be identified with letters “A”
to “N”.
3.2 SOUND TIME OUT PROGRAMMING
This function allows programming the maximum delay after which, should the
block signal go on missing, the siren automatically stops (useful function in case
of cable cutting).
The siren will generate a new alarm cycle with a following lack of the block signal.
Programming is performed through jumpers A and B, according to the table.
3.3 INPUT TYPE PROGRAMMING
This function allows programming BL and TC inputs, of the normally closed or
balanced types (6K8 +/- 5%).
Programming is performed through jumper C, according to the table.
3.4 INPUT REFERENCE PROGRAMMING
This function allows programming the reference of BL and TC inputs to positive or
negative.
Programming is performed through jumper D, according to the table.
Jumper Function
A, B
Sound time-out
C Input
type
D Input
reference
E Alarms
count
F Scaffolds
function
G, H, I, L
Sound mode
M,N not
used
A B
Sound
Time-out
3 minutes
6 minutes
9 minutes
15 minutes
C Input
Type
Balanced
Normally closed
D Input
Reference
To positive
To negative
Sound modes..................................................1
Sound time-out ...............................................3 minutes
Input type ........................................................Balanced
Input reference................................................Positive
Alarms count...................................................Disabled
Scaffolds function ..........................................Disabled