Recommendations for installation
• Ensure the correct location - see Warning.
• Prior to attaching the AirIM-100, check the length of the connected sensor and the loca-
tion of the scanned device.
• The working position is arbitrary but the grommet should not be directed upwards.
• The product does not require special handling and maintenance.
When handling a device unboxed it is important to avoid contact with
liquids. avoid unnecessary contact with the components of the device. Do
not touch the metal objects inside the unit.
Safe handling
Function
Setting functions 1-3, 5-10:
• Long press SET (> 5s) to enter programming mode.
• The green LED will fl ash by function (function 1 - 1x, 2 - 2x ...).
• Short (<1s) by pressing the SET button to move upwards in the function selection, press
(> 2 / <5s) longer to go down the function selections.
• Pressing the button (> 5s) long saves the set function and restarts the device.
6. Fill the jumpers onto the adjustment pins (see the Function chapter).
7. Replace and snap the front cover. When closing, the handles have to be snapped to their
original position. To ensure the degree of protection, tighten the grommet carefully.
* The glue must meet the optimal conditions for product placement (infl uence of tem-
perature, humidity ...)
** For example, a screw or screw of max. Ø 4 mm can be used as a suitable fastener mate-
rial, 13 mm (distance to the partition in the box) must be added to the required length
for attachment to the substrate.
Restart
• Open the cover. Power interruption (remove the battery from the device).
• Press SET> 1min.
• Connect power (insert battery). Close the cover.
When the power is connected, the transmitter sends the initial message to the server.
Any unauthorized interference with a device, regardless of the feature set, immediately
sends the message to the server.
1.
S0
- pulse counting S0
• Checking the correct pulse readings: after setting the longer push (> 2) function of
the SET button, the LED will be activated, which will fl ash when counting the pulse.
The LED fl ashes with a short press or automatically after 5 minutes.
• Measured values send the sensor every 4 hours, or immediately when the 5000 pulse
limit is exceeded.
• Recommended accessories: cable for S0 output
2.
Energy measurement
- pulse counting from active sensor LS, MS, WS
• Checking the correct pulse readings: after setting the longer push (> 2) function of
the SET button, the LED will be activated, which will fl ash when counting the pulse.
The LED fl ashes with a short press or automatically after 5 minutes.
• Measured values send the sensor every 4 hours, or immediately when the 5000 pulse
limit is exceeded.
• Recommended accessories
- LS (LED sensor): is particularly suitable for power meters that support LED pulse
sensing
- MS (magnetic sensor): is particularly suitable for gas meters that support magnetic
sensing.
- WS (magnetic sensor for water meter): it is particularly suitable for water meters that
support magnetic sensing.
• Wiring of LS, MS and WS sensors: (+) brown wire, (-) white wire, (OUT) green wire.
3.
Flood Detection
- Flood Sensor
• Flood detection - by connecting sensing contacts (by fl ooding with water).
• Scans every 4 seconds. The status report sends the sensor data every 12 hours, or
immediately when detected.
• Recommended accessories: fl ood sensor FP-1
4.
Opening detection
- Window / Door Magnetic Sensor (integrated inside the unit)
• Activation occurs when the magnet is attaching / removed from the sensor.
• The sensor sends a data message every 12 hours. In case of a state change, it sends
the data message immediately.
• Recommended accessories: Magnet D / WD
• Note: The universal sensor has a magnet sensor located only on one side, so be care-
ful about the correct position relative to the magnet.
5.
Analog measurement. Voltage 0 - 10 V
• Measured at 10 second intervals. Report on the measured values, the sensor sends:
- every hour
- immediately if it measures the change by more than 1V since the last measurement
- Immediately when dropping below 1 V
- immediately when the 9 V is exceeded
6.
Analog measurement. Current 0 - 20 mA
• Measured at 10 second intervals. Report on the measured values, the sensor sends:
- every hour
- immediately if it measures the change by more than 1mA since the last measure-
ment
- Immediately when dropping below 4 mA
- immediately when the 19 mA is exceeded
7.
Battery measurement 12/24 V
- voltage measurement 0 - 24V
• Measured at 10 second intervals. Report on the measured values, the sensor sends:
- every hour
- immediately if it measures the change by more than 1V since the last measurement
- Immediately when dropping below 22 V
- immediately when the 24 V is exceeded
8.
Temperature measurement
• The temperature is measured every 5 minutes. The sensor reads out the measured
value message:
- every hour
- immediately if it measures the change of ± 5 ° C since the last measurement
- immediately at 30 °C
- Immediately when the temperature drops below 0 °C
• Recommended accessories: TC or TZ temperature sensor
9.
HTM2500LF
- Temperature and Humidity Sensor Measurement HTM2500LF
• Temperature and humidity read every 5 minutes. Report on the measured values,
the sensor sends:
- every hour
- immediately if it measures the change of ± 5 °C since the last measurement
- Immediately when a change is measured of more than ± 20% RH from the last
measurement
• Recommended accessories: HTM2500LF sensor
• HTM2500LF sensor wiring: (+) white wire, (-) black and brown wire, (H) yellow wire,
(T) green wire.
10.
Alarm function
- check the contact
• A contact status message is sent every 12 hours. When there is change (connection /
disconnection contact) message is sent immediately.