Recommendations for installation

•  Ensure the correct location - see Warning.
•  Prior to attaching the AirIM-100, check the length of the connected sensor and the loca-

tion of the scanned device.

•  The working position is arbitrary but the grommet should not be directed upwards.
•  The product does not require special handling and maintenance.

When handling a device unboxed it is important to avoid contact with 
liquids. avoid unnecessary contact with the components of the device. Do 
not touch the metal objects inside the unit.

Safe handling

Function 

Setting functions 1-3, 5-10:

•  Long press SET (> 5s) to enter programming mode.

•  The green LED will fl ash by function (function 1 - 1x, 2 - 2x ...).

•  Short (<1s) by pressing the SET button to move upwards in the function selection, press 

(> 2 / <5s) longer to go down the function selections.

•  Pressing the button (> 5s) long saves the set function and restarts the device.

6. Fill the jumpers onto the adjustment pins (see the Function chapter).

7. Replace and snap the front cover. When closing, the handles have to be snapped to their 

original position. To ensure the degree of protection, tighten the grommet carefully.

* The glue must meet the optimal conditions for product placement (infl uence of tem-

perature, humidity ...)

** For example, a screw or screw of max. Ø 4 mm can be used as a suitable fastener mate-

rial, 13 mm (distance to the partition in the box) must be added to the required length 
for attachment to the substrate.

Restart

•  Open the cover. Power interruption (remove the battery from the device).

•  Press SET> 1min.

•  Connect power (insert battery). Close the cover.

When the power is connected, the transmitter sends the initial message to the server.
Any unauthorized interference with a device, regardless of the feature set, immediately 
sends the message to the server.

1. 

S0

 - pulse counting S0 

•  Checking the correct pulse readings: after setting the longer push (> 2) function of 

the SET button, the LED will be activated, which will fl ash when counting the pulse. 
The LED fl ashes with a short press or automatically after 5 minutes.

•  Measured values send the sensor every 4 hours, or  immediately when the 5000 pulse 

limit is exceeded.

•  Recommended accessories: cable for S0 output

2. 

Energy measurement  

- pulse counting from active sensor LS, MS, WS

•  Checking the correct pulse readings: after setting the longer push (> 2) function of 

the SET button, the LED will be activated, which will fl ash when counting the pulse. 
The LED fl ashes with a short press or automatically after 5 minutes.

•  Measured values send the sensor every 4 hours, or  immediately when the 5000 pulse 

limit is exceeded.

• Recommended accessories

- LS (LED sensor): is particularly suitable for power meters that support LED pulse 

sensing

- MS (magnetic sensor): is particularly suitable for gas meters that support magnetic 

sensing.

- WS (magnetic sensor for water meter): it is particularly suitable for water meters that 

support magnetic sensing.

•  Wiring of LS, MS and WS sensors: (+) brown wire, (-) white wire, (OUT) green wire.

3. 

Flood Detection 

- Flood Sensor 

•  Flood detection - by connecting sensing contacts (by fl ooding with water).
•  Scans every 4 seconds. The status report sends the sensor data every 12 hours, or 

immediately when detected.

•  Recommended accessories: fl ood sensor FP-1

4. 

Opening detection 

- Window / Door Magnetic Sensor (integrated inside the unit)

•  Activation occurs when the magnet is attaching / removed from the sensor.
•  The sensor sends a data message every 12 hours. In case of a state change, it sends 

the data message immediately.

•  Recommended accessories: Magnet D / WD
•  Note: The universal sensor has a magnet sensor located only on one side, so be care-

ful about the correct position relative to the magnet.

5. 

Analog measurement. Voltage 0 - 10 V 

•  Measured at 10 second intervals. Report on the measured values, the sensor sends:

- every hour
- immediately if it measures the change by more than 1V since the last measurement
- Immediately when dropping below 1 V
- immediately when the 9 V is exceeded

6. 

Analog measurement. Current 0 - 20 mA

•  Measured at 10 second intervals. Report on the measured values, the sensor sends:

- every hour
- immediately if it measures the change by more than 1mA since the last measure-

ment

- Immediately when dropping below 4 mA
- immediately when the 19 mA is exceeded

7. 

Battery measurement 12/24 V 

- voltage measurement 0 - 24V

•  Measured at 10 second intervals. Report on the measured values, the sensor sends:

- every hour
- immediately if it measures the change by more than 1V since the last measurement

- Immediately when dropping below 22 V
- immediately when the 24 V is exceeded

8. 

Temperature measurement

•  The temperature is measured every 5 minutes. The sensor reads out the measured 

value message:
- every hour
- immediately if it measures the change of ± 5 ° C since the last measurement
- immediately at 30 °C
- Immediately when the temperature drops below 0 °C

•  Recommended accessories: TC or TZ temperature sensor

9. 

HTM2500LF

 - Temperature and Humidity Sensor Measurement HTM2500LF

•  Temperature and humidity read every 5 minutes. Report on the measured values, 

the sensor sends:
- every hour
- immediately if it measures the change of ± 5 °C since the last measurement
- Immediately when  a change is measured  of more than ± 20% RH from the last 

measurement

•  Recommended accessories: HTM2500LF sensor
•  HTM2500LF sensor wiring: (+) white wire, (-) black and brown wire, (H) yellow wire, 

(T) green wire.

10. 

Alarm function 

- check the contact

•  A contact status message is sent every 12 hours. When there is change (connection / 

disconnection contact) message is sent immediately.

Summary of Contents for iNELS Air AirIM-100S

Page 1: ...egory describes the Low Power Wide Area LPWA This technology is designed to provide full range coverage both inside and outside buildings energy saving and low cost operation of individual devices The Sigfox network is available to use this standard Sigfox network information The network supports bidirectional communication but with a limited number of feed backs It uses the free frequency band di...

Page 2: ...is exceeded Recommended accessories LS LED sensor is particularly suitable for power meters that support LED pulse sensing MS magnetic sensor is particularly suitable for gas meters that support magnetic sensing WS magnetic sensor for water meter it is particularly suitable for water meters that support magnetic sensing Wiring of LS MS and WS sensors brown wire white wire OUT green wire 3 Flood De...

Page 3: ...the body consult a doctor immediately Give the doctor information about the type of battery from battery case device or its manual etc to determine the chemical composition of the battery Batteries must be recycled or returned to an appropriate location e g collection container in accordance with local legal provisions power supply external or battery reset unit error MAC error MODULU start unit o...

Page 4: ...s threshold Threshold 2H 2L 0 65535 Input 2 pulses threshold Name Unit Example Counter 0 3 pulse Counter 0 0x01 Counter 1 0x02 Counter 2 0x03 Counter 3 0x04 Counter 0x01020304 16909060 pulses Function 0 1 2 3 4 5 6 7 FLOOD_SENSOR 0x03 Heartbeat period Measurement period 0x00 0x00 0x00 0x00 0x00 WINDOW_SENSOR 0x04 Heartbeat period Blocking time 0x00 0x00 0x00 0x00 0x00 Heartbeat period 0 127 x min ...

Page 5: ... mV 0 200 100 uA Threshold level for Voltage Current 1 input 2 Threshold 2L 0 100 100 mV 0 200 100 uA Threshold level for Voltage Current 2 input 2 Name Unit Example Voltage 0 1 mV Voltage 0 0x15 Voltage 1 0x7C Voltage 0x157C 5500mV Current 0 1 μA Current 0 0x2E Current 1 0xE0 Current 0x2EE0 12000μA Function 0 1 2 3 4 5 6 7 TEMPERATURE_SENSOR 0x08 Heartbeat period Measurement period Threshold diff...

Page 6: ...eat period Measurement period Threshold Temperature difference Threshold Humidity 1 Threshold Humidity 2 Threshold Temperature 1 Threshold Temperature 2 Heartbeat period 0 127 x min Heartbeat message period 128 255 x 127 h Measurement period 1 255 s Measurement period for temperature humidity Threshold Temperature difference 0 50 C Threshold difference for temperature humidity Threshold Humidity 1...

Page 7: ...t message period 128 255 x 127 h Blocking time 0 10 s Blocking time after closing opening of contact Byte 0 1 2 3 Function Bit 7 6 0 7 6 5 4 3 2 1 0 ALARM First message flag 1 first message 0 others 0x0A Reserved for future use External contact 1 closed 0 opened Reserved for future use Tamper 1 opened 0 closed Battery 1 low level 0 OK Version FW Subversion FW ...

Page 8: ...alculated under ideal conditions and may vary depending on the type of sensor connected Not included in the package Depending on network coverage Sigfix Ready Certification Certificate ID for AirIM 100S Universal Sensor P_0094_56EE_01 Power supply Battery power Battery life by frequency 1x 10 minutes 1x 60 minutes 1x 12 hours 1x 24 hours External power supply Supply voltage tolerance Standby consump...