2 / 2
HRN-57
HRN-57N
Umin
UOFF
Umax
Umin
UOFF
Umax
Umin
UOFF
Umax
L1
L2
L3
15-18
L2
L3
t1
t2
Warning
Technical parameters
Device is constructed for connection in 3-phase 400 / 230 V main alternating current voltage
and must be installed according to norms valid in the state of application. Connection
according to the details in this direction. Installation, connection, setting and servicing
should be installed by qualifi ed electrician staff only, who has learnt these instruction and
functions of the device. This device contains protection against overvoltage peaks and
disturbancies in supply. For correct function of the protection of this device there must
be suitable protections of higher degree (A, B, C) installed in front of them. According
to standards elimination of disturbancies must be ensured. Before installation the main
switch must be in position “OFF” and the device should be de-energized. Don´t install the
device to sources of excessive electro-magnetic interference. By correct installation ensure
ideal air circulation so in case of permanent operation and higher ambient temperature
the maximal operating temperature of the device is not exceeded. For installation and
setting use screw-driver cca 2 mm. The device is fully-electronic - installation should be
carried out according to this fact. Non-problematic function depends also on the way of
transportation, storing and handling. In case of any signs of destruction, deformation,
nonfunction or missing part, don´t install and claim at your seller it is possible to dismount
the device after its lifetime, recycle, or store in protective dump.
Function
Monitoring terminals:
Supply terminals:
Supply / measured voltage Un:
Power input:
Max. dissipated power
(Un + terminals):
Level Umax:
Level Umin:
Hysteresis:
Max. permanent overload:
Peak overload < 1 ms:
Time delay T1:
Time delay T2:
Output
Number of contacts:
Current rating:
Breaking capacity:
Inrush current:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage category:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight:
Standards:
L1, L2, L3 L1, L2, L3, N
L1, L2, L3 L1, L2, L3, N
3x 400 V / 50-60 Hz 3x 400 V / 230 V / 50-60 Hz
max. 2 VA / 1 W
2 W
105 - 125 % Un
75 - 95 % Un
2 %
AC 3x 460 V AC 3x 265 V
AC 3x 500 V AC 3x 288 V
max. 500 ms
adjustable 0.1 - 10 s
1x changeover / SPDT (AgNi / Silver Alloy)
8 A / AC1
2000 VA / AC1, 240 W / DC
10 A
250 V AC / 24 V DC
red LED
1x10
7
1x10
5
-20 °C to 55 °C (-4 °F to 131 °F)
-30 °C to 70 °C (-22 °F to 158 °F)
4 kV (supply - output)
any
DIN rail EN 60715
IP40 from front panel / IP10 terminals
III.
2
solid wire max. 2x 2.5 or 1x 4 /
with sleeve max. 1x 2.5 or 2x 1.5 (AWG 12)
90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)
62 g (2.19 oz.) 63 g (2.22 oz.)
EN 60255-6, EN 61010-1
Relay in 3-phase main monitors size of phase voltage. It is possible to set two independent
voltage levels and thus it is possible to set two independent voltage levels and monitor
e.g. undervoltage and overvoltage independently. In normal state when voltage is
within set levels, output relay is closed and red LED shines. In case voltage exceeds or
falls below the set levels, output relay breaks and red LED shines (LED indicates faulty
state - fl ashes when timing). In case of In case supply voltage falls below 60 % Un (U
OFF
lower level) relay immediately breaks without delay and faulty state is indicated by
red LED. In case timing is progress and faulty state is indicated, timing is immediately
stopped.
green LED
red LED
hysteresis
hysteresis