T 3000 - T 3500
31
5. Terminals
21 + 22
Safety contact profile CLOSE (SLZ)
8.2kOhm
resistor
Table 9
After installing and connecting all the equipment, the following LEDs have to
light:
1.
Vp
Is lit, when the supply voltage is switched on.
2.
BTZ2 Is lit, when contact BTZ2 is closed.
3.
BTS
Is lit, when contact BTS is closed.
4.
Bm.
Is lit, when the boom-missing contact is closed.
Table 10
Plug Socket
label
Function
1
12V
Uext 12V, max. 500mA
2 Gnd
Ground
3
24V
Uext 24V, in total with terminal 5 and 7 max.
1500mA
4 Gnd
Ground
5
24V
Uext 24V, in total with terminal 3 and 7 max.
1500mA
6 Gnd
Ground
7
24V
Uext 24V, in total with terminal 3 and 5 max.
1500mA
8 Gnd
Ground
9
Multi1
Multi-functional relay 1, potential-free, max.
24VDC/1A
10
11
Multi2
Multi-functional relay 2, potential-free, max.
24VDC/1A
12
13
Multi3
Multi-functional relay 3, potential-free, max.
24VDC/1A
14
15
Multi4
Multi-functional relay 4, potential-free, max.
24VDC/1A
16
17
Multi5
Multi-functional relay 5, potential-free, max.
24VDC/1A
18
19
Multi6
Multi-functional relay 6, potential-free, max.
24VDC/1A
20
21
SLZ
Safety contact profile CLOSE, 8.2kOhm
22 Gnd
Ground
23
LS
Photoelectric barrier (NC contact)
Summary of Contents for T 3000
Page 12: ...T 3000 T 3500 11 4 Declaration of incorporation Drawing 2...
Page 18: ...T 3000 T 3500 17 7 2 Mounting dimensions Drawing 3...
Page 34: ...T 3000 T 3500 33 8 4 Circuit diagram Drawing 21...
Page 35: ...T 3000 T 3500 34 Drawing 22...
Page 36: ...T 3000 T 3500 35 Drawing 23...
Page 37: ...T 3000 T 3500 36 Drawing 24...
Page 38: ...T 3000 T 3500 37 Drawing 25...
Page 39: ...T 3000 T 3500 38 Drawing 26...
Page 40: ...T 3000 T 3500 39 Drawing 27...
Page 42: ...T 3000 T 3500 41 10 Layout exploded drawing Drawing 28...