 09.02.2006 ELKA-Torantriebe GmbH u. Co. Betriebs KG      page  7 

                                      

EST 204, EST 404, EST 804 

8.2.  Output terminals MO 56/S 

Terminal Function 
14Vac for 
LS-transmitter 

Supply for the photocell transmitter. Performs necessary supply interruption during LS 
test. 

14Vac for 
LS-receiver 

Supply for the photocell receiver. 

0Vac 

Common for photocell transmitter and receiver. 

Motor + 
Motor - 

Motor connector, for motor types: 1x 404.258, 2x 404.258, 1x 404.259, 2x 404.259, 1x 
404.458 

Light 

3min. Light. Potential free contact. Maximum load 230V/500W. 

Green traffic light 

Green is on when gate is completely open. 
Potential free contact. Maximum load 230V/120W. 

Red traffic light / 
Warn light 

Red is off, when the gate is completely open or when it is completely closed. Red is on 
during movements, during warning times and when gate stops in between. 
Potential free contact. Maximum load 230V/120W. 

 

8.3.  Indication lights on the MO 56/S 

LED name 

Colour 

Function 

BT 

green 

On, when contact BT is closed. 

LS 

green 

On, when at least one photocell contact (LS) is open. 

SL 

red 

On, when SLA or SLZ safety edge is pressed. 

Vp 

yellow 

On, when power supply is present. 

Diag/Funk yellow 

Diagnosis 

display 

and display for radio receiver. 

 

9. 

Operation modes MO 56/S (DIP switches)

 

Alter only when power supply is switched off. 
After altering the DIP switch mode confirm with the button LERN. 

9.1.  Automatic closure (S1) 

 
When automatic closure is active, the stored pause time starts to elapse, every time the gate has reached 
the position completely open. When the stored time has elapsed, the gate will close automatically. 
If the gate is completely open and a stop command is given (TS), the function automatic closure is blocked. 
Automatic closure will be activated again and the pause time will start new, when button BT or radio 
transmitter is used. 
When the gate is completely open and LS is active, the gate will stay open even after the pause time has 
elapsed. LS prevent the gate from closing, but the pause time is not extended. If LS is not active any more 
and the pause time has elapsed already, the gate will close immediately. 

 

 

S1 off:   

Automatic closure is off 

S1 on: 

If gate is completely open, it will close automatically after the stored pause time has 
elapsed. (choose from 0 up to 300 s, default 30 s) 

9.2.  Warning prior to opening (S2) 

 

When warning prior opening is activated, the open command will start the warning light first. The gate will 
open after the warning time has elapsed. 

 

 

S2 off:   

no warning prior to opening 

S2 on: 

4 s warning time prior to opening is active 

9.3.  Warning prior to closing (S3) 

 

When warning prior to closing is activated, the close command will start the warning light first. The gate will 
close after the stored warning time has elapsed. 

 

 

S3 off:   

no warning prior to closing 

S3 on: 

warning time prior to closing is active (choose from 0 up to 300 s, default 5 s) 

9.4.  Photocell test (S4) 

 

Photocell may be tested prior to every movement of the gate where the observation through photocell is 
active. 

 

 

S4 off:   

Photocell test is off 

 

S4 on: 

Prior to every movement the photocells are tested. The gate can only move when 
photocells are without malfunction. 

 

 

Caution

: The number of photocells has to be stored before using the test.(cha. 9.6) 

Summary of Contents for EST 204

Page 1: ...3 6 Mounting the rack 4 7 Electrical setup Connection examples 5 8 MO 56 S controller for EST 204 404 6 9 Operating modes MO56 DIP switches 7 10 Safety functions MO56 8 11 Learn mode MO56 9 12 After p...

Page 2: ...terminals for button BT BT BT BTA BTZ BTG Input terminal for stop yes redundant yes redundant yes Photo cell functions 2 modes testable 2 modes testable 3 modes Evaluation of safety contact strips ye...

Page 3: ...he back parallel to the gate e Mark the middle of the elongated holes on the foundation f Take the opener from the foundation and drill holes for 8 mm diameter plugs or anchor bolts g Lay the 0 5 mm c...

Page 4: ...y protrude at both ends h Hook the protruding end into the protruding end of the first length Push this rail against the first rail j Screw this length onto the distance pieces k Connect the butt join...

Page 5: ...4 404 opener control box MO 56 S section 8 EST 804 opener control box MO 43 section 10 c Check the setting of DIP switches for the functions you need EST 204 404 opener control box MO 56 S section 9 E...

Page 6: ...e photocell DIP 5 When LS is active the gate cannot be operated or the gate opens immediately Masse Ground for BT TS and LS Sync n c Button for manual release When opener is released the control box i...

Page 7: ...hen the stored time has elapsed the gate will close automatically If the gate is completely open and a stop command is given TS the function automatic closure is blocked Automatic closure will be acti...

Page 8: ...en the gate is still standing and a safety edge reports an obstacle the gate can not move in the direction of the appropriate edge Before a movement the appropriate safety edge is tested An artificial...

Page 9: ...erve step 1 16 default 8 Pause time for automatic closure 0 to 300 s default 30 s Warning time prior to closing 0 to 300 s default 5 s Radio codes for BT and BTG default BT BTG no code You may use the...

Page 10: ...e Diag LED flashes fast c Press the appropriate button on the radio transmitter Receiver and controller receive the code and store it as BTG code The SL LED flashes to confirm After this procedure the...

Page 11: ...nges into normal operation mode If a safety device has a malfunction it is not possible to operate the gate in normal operation mode into the appropriate direction But it is possible to operate the ga...

Page 12: ...opening Masse Earth for BS BZ BA BT BTG LS n c Photocell The opener reacts as determined with the operating mode DIP 1 DW Safety contact strips When activated the opener stops and reverses for a short...

Page 13: ...witch 1 off Interrupting the photo cell stops the gate during the closing phase it then re opens immediately During opening the photo cell has no effect b Switch 2 on The gate closes automatically fro...

Page 14: ...LED turns off 16 2 Setup for the partial opening module The standard setup must be completed The pedestrian opening is automatically set to half of the total distance which the gate opens You may sele...

Page 15: ...ow the allocation of a channel with a one channel transmitter using the switches 8 and 9 as in the receiver Example B Receivers without code switches Logic boards MO 34 or MO 55 These receivers learn...

Page 16: ...nner the user must ascertain that no danger for himself or others will result from this use He should also ascertain that the planned use will have no detrimental effect on the appliance itself The ap...

Reviews: