Setting the Data Bus Address and Enrolling Device(s) into the System

Keypads and expander devices communicate over the RS-485 4-wire data bus.  Each device must have a unique address
setting (from 1 to 16) within it's device type.  Keypads are TYPE 1, input (zone) expanders TYPE 2, output expanders TYPE 3, etc.
The purpose of device types is so that the address numbers can be re-used in each different device type.  It’s OK to have a
Keypad, Zone Expander, and Output Expander all set to address 2 and on the same data bus since each device is a different
device type.  

It is NOT OK to have duplications of addresses within the same device type.  I.E. Multiple keypads on the same

control cannot be set to 'like' addresses.

ADDRESS:

 From the factory all  keypads are set to address 1.  Valid addresses are 1 to 16.  The first keypad on the system

(Keypad 1) is automatically enrolled upon power up.  Each additional keypad must be assigned a unique address and then
manually enrolled from “Menu 1 - Bus Module Enrollment”.   (See Menu 01, for complete instructions on Bus Module Enrollment)

1. Press and hold the " * " key, followed by the F5 key . HOLD BOTH keys pressed for 5-10 seconds or until the LCD displays:

 

Exit when done. F1 Set Addr.   

(This is Keypad setup mode)

NOTE: An alternate method is to remove power from the keypad and then power up while holding any key pressed.

2. Press the F1 key to display the current address setting.
3. Set the desired address (from 1 to 16) by using the Up or Down arrow keys.
4. Press the Exit key twice when done.

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

Auth. Required
Enter Valid Pin

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

01-Bus Module
Enrollment

ENROLLING:

1.

Press the ELK key, then 9 (or scroll up) to display 9 - Installation Programming.  Press the RIGHT
arrow key to select this menu.  The Installer Program Code must be entered to access this menu.

2.

Enter the Installer Program Code.  (The default code is 172839)

3.

The first Installer Programming menu display will be “Bus Module Enrollment”

4.

Press the RIGHT arrow key to select this menu.  “Enrolling Bus Modules” will display.

5.

After a few seconds the display will show the total Bus Modules that are enrolled.  To view the
enrolled devices and /or remove a device press the RIGHT arrow key next to the word Edit.

6.

Press the * or Exit keys to exit Installer Programming.

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

12345678901234567890123456

XX Bus Modules
Enrolled, Edit 

rrrrr

The ELK-M1DBHR †  "Active" Data Bus Hub Retrofit splits the Controls' main RS-485 Data Bus into 4 managed RS-485 branches.  Each branch
can have 2 parallel home run cables for a total of 8 home runs.  The last (end of line) device on each home run should be jumper terminated to
insure proper operation and supervision.

JP1

Terminating Jumpers (JP1 - JP5)

JP1 = Terminates Input from Control
JP2 = Terminates Branch 1
JP3 = Terminates Branch 2
JP4 = Terminates Branch 3
JP5 = Terminates Branch 4
See details about Data Bus Termination.

ELK-M1DBHR †

DATA BUS HUB FOR RETROFIT

EL

K PR

ODUCT

S,

 I

N

C

   

HI

LDEBR

AN,

 N.

C.

2

8

6

3

7

, USA

JP2

JP3

JP4

JP5

+VKP

DATA B

DATA A

NEG

RS-485 DATA BUS

BLACK

RED

GREEN

WHITE

A

B

-

+

IN
P

U

T

F

R

O

M

 CO

NT
RO

L

The Maximum length of the

RS-485 Data Bus or any single

Branch is 4000 ft.

Max. devices varies by product.

+VKP protected with 1.25A PTC

Mount M1DBHR inside control.

Connect it to the Data Bus terminals

using a 4 conductor cable.

RED

GREEN

WHITE
BLACK

A

+

B

-

DATA BUS
BRANCH 1

RED

GREEN

WH

IT

E

BL

ACK

Keypad

A

+

B

-

DATA BUS
BRANCH 2

Keypad

RED

GREEN

WH

IT

E

BL

ACK

Keypad

Single Keypad /Bus Device:

If only one (1) Keypad or Bus Device
is connected to a branch (# 1 in this
example), place terminating jumper
on the Keypad/Bus Device AND on
JP2 of the M1DBHR.

Two Keypad /Bus Devices:

If two (2) Keypad/Bus Devices are connected to
a branch (#2 in this example), place terminating
jumper on both Keypads/Device and REMOVE
jumper JP3 on the M1DBHR

.

Multiple Keypads/Bus Devices
(Series Connected):

If more than two (2) Keypad/Bus
Devices are connected to a
branch (#3 in this example), they
MUST be series connected on no
more than 2 homerun wires.
Place terminating jumpers on
LAST device connected to each
homerun.  REMOVE jumper JP4
on the M1DBHR

.

ELK-M1XIN

ELK-M1XOV

Jumper

Terminate

these two

devices.

DO NOT Jumper Terminate

these devices.

ELK-M1KP

Keypad

Keypad

Keypad

RED

GR

EEN

WH

IT

E

BL

ACK

A

+

B

-

DATA BUS
BRANCH 3

A

+

B

-

DATA BUS
BRANCH 4

ELK-M1XIN

Jumper

Terminate

these two

devices.

One Keypad and one
Zone Expander:

When two (2) Bus
Devices are connected
to a branch (#4 in this
example), place
terminating jumper on
both Bus Devices and
REMOVE jumper JP5
on the M1DBHR

.

Jumper

Terminate

these two

devices.

Keypad

Jumper Terminate

this device AND JP2

on the M1DBHR.

DO NOT Jumper JP3.

DO NOT

Jumper JP5

DO NOT Jumper JP4.

This diagram illustrates the M1DBHR Hub as a single
branch on a Control.  Terminate JP3 on Control and JP1
on the M1DBHR.  If a second hub is wired to the Control
terminate JP1 on the hubs but DO NOT terminate JP3 on
Control.  NEVER place more than two (2) terminating
jumpers on any branch of the RS-485 Data Bus!

Diagram for Home run wiring using M1DBHR Active Data Bus Hub

† 

  Not evaluated by UL

††

  Not for use in UL Listed Systems

Summary of Contents for EZ8 ELK-M1EZ8

Page 1: ...Cross Platform Control Part ELK M1EZ8 A member of the M1 Family Specifications Installation and Programming M1 includes the SIA CP 01 Standards for False Alarm Reduction TM L523 Rev I 08 06 08 Current...

Page 2: ...or low temperatures as well as large swings in temperature may all reduce the actual battery life in a given installation This wireless system however can identify a true low battery situation thus a...

Page 3: ...keover 19 3 4 Area Partitioning 19 3 5 Communicator Setup Checklist 20 3 6 Entering Installer Level Programming 20 Menu 01 Bus Module Enrollment 22 Menu 02 User Code Options 23 Menu 03 Area Definition...

Page 4: ...ever event can have one or more ANDs and THENs conditions and commands Total number of Rules Supported 528 Rules utilize easy to understand text based references Control lighting using RS 232 serial o...

Page 5: ...Green Red Black 1 1 8 Conductor Cat5 cable from EZ8MSI Main Serial Port Interface End view Brn Wht Wht Brn Grn Wht Wht Blue Blue Wht Wht Grn Org Wht Wht Org 1 Wht Org Org Wht Wht Grn Blue Wht Wht Blu...

Page 6: ...M1EZ8InstallationandProgramming Page 6 Intentionally Left Blank...

Page 7: ...h those in the figure above to familiarize yourself with the part names Mount the control using the upper center slotted hole to level Install and connect all necessary wiring for the power transforme...

Page 8: ...lower back side of the board EG PC096E Boards with a letter F or later provide the output as a switched positive Load 50mA max i e Relay LED To Red Pos Wire To Brown Wire KP Zone Output Address 1 193...

Page 9: ...ower unplug the outputs for approx 20 seconds after a short to allow the PTC to reset Even if the short is no longer present the remaining residual current draw may be so high that the PTC cannot dete...

Page 10: ...Rules Programming and can be triggered by multiple conditions events Do not exceed the current limits on voltage only outputs Output 2 Connect a UL Listed Bell or Siren self contained Current limited...

Page 11: ...ch device directly to the M1 s VKP and Neg terminals DO NOT SERIES THE POWER WIRES as this will cause unnecessary voltage loss The ELK M1DBH Data Bus Hub accepts CAT5 or CAT6 cable with RJ45 plugs on...

Page 12: ...ming 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 123456...

Page 13: ...e User s Guide contains a description of operations accessible to the user codes Control operations accessed by the installer passcode are slightly different Factory Default for User Code 1 is 3 4 5 6...

Page 14: ...rogrammed for Force arm Keypad Models and Feature Comparison PART NUMBER ELKM1KP ELKM1KP2 ELKM1KPAS PHYSICAL DIMENSIONS 6 87 W x 5 25 H x 1 32 D 4 65 W x 5 5 H x 95 D 1 3 W x 2 62 H x 3 D actual keypa...

Page 15: ...789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 12345678901234567890...

Page 16: ...123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 8 System r Settings 123456789012345678901234567890...

Page 17: ...3456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 1234567890123456...

Page 18: ...012345678 1234567890123456789012345678 1234567890123456789012345678 0 Select Keypad Alternate Area r 1234567890123456789012345678 1234567890123456789012345678 1234567890123456789012345678 123456789012...

Page 19: ...d log on serial number and dealer assigned RP access code The serial identifies the control to RP while the RP access code identifies the computer to the control prior to a programming session RP load...

Page 20: ...omatic SIA or Contact ID codes program a 1 01 5 Under Menu 12 Sys Report Code Options Codes select and program each desired option such as AC Fail Low Battery Automatic Test and other system wide opti...

Page 21: ...als 1 Receiver Size Menu 03 Menu 05 4 Celcius Disp 45 Default Control Options 18 Name 2 ZnBank Start Zn Area Defs Zone Defs 5 DST Observe 81 Default User Codes 3 Reg Supv Hrs Area 1 Zone 1 6 Fast Loop...

Page 22: ...89012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890123456789012...

Page 23: ...n the same area Default value for both these options is No code not required for bypass A Yes allows this code to activate the Access Keypad Events 1313 1328 for the keypad where code is entered Use t...

Page 24: ...entry delay time in seconds for zones programmed as Entry Delay 1 Range is 030 to 255 seconds Default value is 030 The amount of exit delay time in seconds for zones programmed as Exit Delay 2 Range i...

Page 25: ...press the right or left arrow keys While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys toggle between upper and lower case P...

Page 26: ...ogram or press the up or down arrow keys to select another keypad To jump to any keypad enter the number 1 16 The keypad name displays on the bottom A keypad can only be assigned as primary for a sing...

Page 27: ...ich will cause the key to light up See Event Codes in Appendix A Press the RIGHT arrow key and enter 4 digits The bottom line displays the description of the event Press the RIGHT arrow key to move to...

Page 28: ...STAY INSTANT arm modes 07 Burglar Interior Nite Delay For motion detectors interior doors etc that are not close to sleeping areas Same as an Interior Nite zone except that Interior Nite Delay zones...

Page 29: ...mentary Away Mode Intended for a spring loaded momentary key switch Arms the area in the AWAY mode with each trip 28 Keyswitch Momentary Stay Mode Intended for a spring loaded momentary key switch Arm...

Page 30: ...the right or left arrow keys While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys move between upper and lower case Press the...

Page 31: ...1234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 123456789012345678901234567890...

Page 32: ...this option Default is No 4 digits NOTE The Installer code is ALWAYS 6 digits To prevent a would be thief or hacker from being able to hunt for a valid user code the system can automatically lock out...

Page 33: ...rted from a siren driver into a voltage only output If set to No the control produces alarm sounds for use with 8 Ohm speakers If set to Yes the control will produce 12 Volts for use with self contain...

Page 34: ...123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 G28 No Out2 r SingleAlmLockout 123456789012345678901234567890121234 123456789012345678901...

Page 35: ...7890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123...

Page 36: ...7890121234 T1 01 Format 0 r 0 Disabled 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890123...

Page 37: ...While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys toggles between upper and lower case Press the ELK key when complete 1234...

Page 38: ...567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 12...

Page 39: ...23 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 AR1 15 Code 00r O...

Page 40: ...g with the SIA and Contact ID formats is to set the programmed code to a non zero 0 value See below Press RIGHT arrow key to select this menu Press UP or DOWN arrow keys to select another menu The ELK...

Page 41: ...012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 1234567890123...

Page 42: ...789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901...

Page 43: ...ssion as a verification that the control was accessed Range is 00 to FF Default is 00 no report Phone Line Fault T Trouble will be reported if the Voltage and Current is lost on the telephone line Pho...

Page 44: ...1234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890...

Page 45: ...4 123456789012345678901234567890121234 123456789012345678901234567890121234 RO2 00 ZnBank r StartingZone xxx 1234567890123456789012345678901212345 1234567890123456789012345678901212345 123456789012345...

Page 46: ...890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 12345678901234567...

Page 47: ...omatic RP dials the control phone number and listens for the control to answer on it s rings until answer setting If an answering machine answers RP will transmit codes to override it automatically Pr...

Page 48: ...word restricted M1 Dealers ONLY location NOTE Firmware updating can only be done from a Direct to PC Com port connection or an optional Ethernet Network connection Due to the amount of data that has t...

Page 49: ...to happen at a given time or in response to a set of circumstances The following information is intended to provide an overview of the vast automation features in the control TASKS A Task is similar t...

Page 50: ...ew Z Wave wireless devices Even if a lighting product is not directly supported it is always possible to use RS 232 ASCII strings for communicating lighting control OUTPUTS These can be in the form of...

Page 51: ...23 59 COUNTERS These memory locations often called flags can be set incremented decremented or compared by an automation rule to track an event or keep up with how many times an event has occurred The...

Page 52: ...ut a serial port might be a series of ASCII characters formatted to a certain manufacturers protocol Special options built into this menu include automatic display of temperature readings from Zone Te...

Page 53: ...iggering event in order to be started A triggering event can be a time of day occurrence a zone opening or closing the security system going from armed to disarmed a light changing from on to off or l...

Page 54: ...OF THE WEEK IS ARE M W F Example 5 AND IT IS DARK OUTSIDE Example 6 AND John s House Area 1 IS ARMED AWAY THEN The third and final element of a rule is the action that you wish to occur as a result o...

Page 55: ...nal AND element could be added to prevent the fan from operating on certain days or at certain times Rule 4 is another energy savings example It adjusts the cooling setpoint of the Main Floor Thermost...

Page 56: ...2 Keypad 01 Code Lockout N 1113 Keypad 02 Code Lockout N 1114 Keypad 03 Code Lockout N 1115 Keypad 04 Code Lockout N 1116 Keypad 05 Code Lockout N 1117 Keypad 06 Code Lockout N 1118 Keypad 07 Code Loc...

Page 57: ...Back B 1310 Area 6 Closing Ring Back B 1311 Area 7 Closing Ring Back B 1312 Area 8 Closing Ring Back B 1313 Access Keypad 1 TM 1314 Access Keypad 2 TM 1315 Access Keypad 3 TM 1316 Access Keypad 4 TM 1...

Page 58: ...M1EZ8InstallationandProgramming Page 58 Appendix B C Unused Intentionally left blank...

Page 59: ...M1EZ8InstallationandProgramming Page 59 Intentionally left blank...

Page 60: ...1st ring and allow the Operator to press 55 to initiate a two way session 2 Once a two way session has begun it will continue for 3 minutes before automatically disconnecting To extend the two way ses...

Page 61: ...y another zone Programmable from 1 to 255 seconds For all non fire zones shut down at 1 trip Depends on Panel and Sensors Call waiting cancel prefix code may be dialed on initial attempt ONLY Enabled...

Page 62: ...M1EZ8InstallationandProgramming Page 62 Appendix F Unused Intentionally left blank...

Page 63: ...M1EZ8InstallationandProgramming Page 63 Appendix F Unused Intentionally left blank...

Page 64: ...M1EZ8InstallationandProgramming Page 64 Not evaluated by UL Intentionally left blank Appendix F Unused...