9MA10011
16/52
4.4.1 Analogue Inputs
This menu shows the list of onboard analogue inputs.
4.4.1 ANALOGUE INPUTS
01
ONBOARD-P1
|
02
ONBOARD-P2
|
03
ONBOARD-P3
|
04
ONBOARD-P4
|
05
ONBOARD-P5
|
06
ONBOARD-P6
|
07
ONBOARD-P7
|
08
ONBOARD-P8
Select the required analogue input using the UP and DOWN keys and press OK.
A page displaying the following information will open:
(example Index 01 Input, pressure probe).
4.4.1 ANALOGUE INPUTS
Index
1/8
|
Name
ONBOARD-P1
|
Probe type
4..20mA
|
Unit of measure Bar
|
Decimal points
1
|
Value = 04mA
0.0
|
Value = 20mA
30.0
|
Offset
0.7
|
Read
13.3
|
View Text
YES
•
Index
: Input Index***
•
Name
: Name of Input. The default names are
ONBOARD-P1
..
ONBOARD-P8
and can be modified as required (max. 10 characters)
• Probe type: set automatically between
[ 4…20mA and NTC 103AT]
•
Unit of Measure
: see
Units of Measure table
•
Decimal Points
: values [0…3] for 4..20mA, [0…1] for NTC
• If
Probe Type
= 4…20 mA :
-
Value = 04 mA
: indicates start of scale
-
Value = 20 mA
indicates full scale
• If
Probe Type
= NTC :
• Minimum Value***
• Maximum Value***
•
Offset
: Probes Calibration. Note: the modification on the Value Read (see next
item) is immediate.
•
Read Value
read in real time***
•
View Text
: if YES then the value is entered in a list of elements to be viewed in
Default View.
*** Read-only information.
Summary of Contents for Memory 1000