PAR.
DESCRIPTION
RANGE
App1 App2 App3 App4 M.U.
dCt
Selection of count mode for the defrost interval.
0
= compressor running time;
1
= appliance running time;
2
= A defrost cycle is run at each compressor stop
0/1/2
1
1
1
1
num
dOH Delay for start of first defrost after request
0 ... 59
0
0
0
0
min
dEt Defrost timeout; determines the maximum defrost duration
1 ... 250
30
30
30
30
min
dSt Defrost end temperature - determined by the evaporator probe
-50,0...150
8,0 50,0 8,0 50,0
°C/°F
dPO Determines whether the instrument must enter defrost mode at start-up
n/y
n
n
n
n
flag
FANS (“FAn” folder)
FSt Fans stop temperature
-58,0...302 50,0 50,0 50,0 50,0
°C/°F
FAd Fan activation differential
1,0 ... 50,0
2,0
2,0
2,0
2,0
°C/°F
Fdt Fan activation delay after a defrost cycle
0 ... 250
0
0
0
0
min
dt Coil drainage time
0 ... 250
0
0
0
0
min
dFd Allows evaporator fan exclusion to be selected or not selected during defrosting.
y
= yes (fans excluded);
n
= no
n/y
y
y
y
y
flag
FCO Selects or deselects fan deactivation at compressor OFF.
0
= fans off;
1
= fans active;
2
= duty cycle
0/1/2
0
0
0
0
num
FOn Fans ON time in day duty cycle
0 ... 99
0
0
0
0
min
FOF Fans OFF time in day duty cycle
0 ... 99
0
0
0
0
min
Fnn Fans ON time in night duty cycle
0 ... 99
0
0
0
0
min
FnF Fans OFF time in night duty cycle
0 ... 99
0
0
0
0
min
ESF Night mode activation.
n
= no;
y
= yes
n/y
n
n
n
n
flag
ALARMS (“AL” folder)
Att Can be used to select absolute (
Att=0
) or relative (
Att=1
) values for HAL and LAL
parameters
0/1
0
0
0
0
num
Afd Alarm differential
1,0 ... 50,0
2,0
2,0
2,0
2,0
°C/°F
HAL Maximum temperature alarm
LAL...302
50,0 50,0 50,0 50,0
°C/°F
LAL Minimum temperature alarm
-58.0...HAL -50,0 -50,0 -50,0 -50,0 °C/°F
PAO Alarm exclusion time after re-activation following a power failure
0 ... 10
0
0
0
0
hours
dAO Temperature alarm exclusion time after defrost
0 ... 999
0
0
0
0
min