PAR.
DESCRIPTION
RANGE
APP1 APP2 APP3 APP4 M.U.
OAO Alarm signalling delay after disabling of digital input
0 ... 10
0
0
0
0
hours
tdO Delay in door open alarm activation
0 ... 250
0
0
0
0
min
tAO Time delay for temperature alarm indication
0 ... 250
0
0
0
0
min
dAt Alarm signalling end of defrost due to timeout
n/y
n
n
n
n
flag
rLO External alarm locks controllers.
n
= does not lock;
y
= locks
n/y
n
n
n
n
flag
SA3 Probe 3 alarm Setpoint
-58,0...302
0,0
0,0
0,0
0,0
°C/°F
dA3 Probe 3 alarm differential
1,0 ... 50,0
1,0
1,0
1,0
1,0
°C/°F
LIGHTS & DIGITAL INPUTS (“Lit” folder)
dOd Digital input for switching off utilities.
0
=disabled;
1
=disables fans;
2
=disables the compressor;
3
=disables fans and compressor
0/1/2/3
0
0
0
0
num
dAd Activation delay for digital input
0 ... 255
0
0
0
0
min
dCO Compressor deactivation delay after door opened
0 ... 255
1
1
1
1
min
AuP Aux output activation when door opened. n = not linked; y = linked
n/y
n
n
y
n
flag
PRESSURE SWITCH (“PrE” folder)
Pen Number of errors allowed per maximum/minimum pressure switch input
0 ... 15
0
0
0
0
num
PEI Minimum/maximum pressure switch error count interval
1 ... 99
1
1
1
1
min
PEt Delay in activating compressor after pressure switch deactivation
0 ... 255
0
0
0
0
min
COMMUNICATION (“Add” folder)
PtS Communication protocol selection.
t
= Televis;
d
= Modbus
t/d
t
t
t
t
flag
dEA Index of the device inside the family (valid values from 0 to 14)
0 ... 14
0
0
0
0
num
FAA Device family - valid values from 0 to 14
0 ... 14
0
0
0
0
num
Pty Modbus parity bit.
n
= none;
E
= even;
o
= odd
n/E/o
n
n
n
n
num
StP Modbus stop bit
1b/2b
1b
1b
1b
1b
flag
DISPLAY (“diS” folder)
LOC Basic commands modification lock. It is still possible to enter parameter programming
mode and modify them. y = yes; n = no
n/y
n
n
n
n
flag
PS1 PAssword1: if
PS1≠0
is the access key to
User
parameters
0 ... 250
0
0
0
0
num
PS2 PAssword2: if
PS2≠0
is the access key to
Installer
parameters
0 ... 250
15
15
15
15
num
ndt Display with decimal point.
y
= yes;
n
= no
n/y
y
y
y
y
flag