PAR. DESCRIPTION
MODEL
RANGE
VALUE M.U. LEVEL
CA1
Calibration 1. Positive or negative temperature value added to the value read by
Pb1
, according to the setting of parameter
CAI
.
NTC/PTC
-30.0...30.0
0.0
°C/°F
User/Inst
PT100-Tc
-30.0...30.0
0.0
°C/°F
V/I
-30...30
0
num
CAI
Intervention of the offset on display, temperature control or both.
0
= only the temperature shown is modified;
1
= sum with only the temperature used by the controllers and not for the
display, which remains unchanged;
2
= sum with the displayed temperature, which is also used by the regulators.
ALL
0/1/2
2
num
Inst
LdL
Minimum value that can be displayed by the device.
NTC/PTC
-199.9...HdL
-50.0
°C/°F
Inst
PT100-Tc
-328...HdL
-199.9
°C/°F
V/I
-199...HdL
-199
num
HdL
Maximum value that can be displayed by the device.
NTC/PTC
LdL...199.9
140.0
°C/°F
Inst
PT100-Tc
LdL...1350
1350
°C/°F
V/I
LdL...199
199
num
dro
Select the unit of measurement of probe 1.
• NTC/PTC
:
C
(0) = °C,
F
(1) = °F
• PT100-Tc
:
C
(0) = °C,
F
(1) = °F
• V/I
:
n
(0) = no unit of measure selected,
t
(1) = temperature,
P
(2) = pressure,
H
(3) = humidity
NTC/PTC
C/F
C
flag
Inst
PT100-Tc
C/F
C
flag
V/I
n/t/P/H
n
num
CONFIGURATION (folder ‘CnF’)
If one or more parameters are changed, the controller MUST be switched off and switched on again.
H00
Probe type selection.
• NTC/PTC
:
Ptc
(0) = PTC,
ntC
(1) = NTC
• PT100-Tc
:
Jtc
(0) = TcJ,
Htc
(1) = Tck,
Pt1
(2) = PT100.
• V/I
:
420
(0) = 4...20mA,
020
(1) = 0...20mA,
t10
(2) = 0...10V,
t05
(3) = 0...5V,
t01
(4) = 0...1V.
NTC/PTC
Ptc/ntC
ntc
flag
User/Inst
PT100-Tc
Jtc/Htc/Pt1
Jtc
num
V/I
420/020
t10/t05/t01
420
num
H01
Output link:
0
= independent;
1
= dependent;
2
= Neutral Zone (or window).
ALL
0/1/2
0
num
Inst