ELECTRICAL CONNECTIONs

Attention! Make sure the machine is switched off before working on the electrical connections.

The instrument is equipped with screw or disconnectable terminal blocks for connecting electrical cables with a max. 

diameter of 2.5 mm

2

 (one wire per terminal for power connections): for the terminal ratings, see the label on the instrument.

Do not exceed the maximum permissible current; in case of higher loads, use a suitably rated contactor.

Make sure the power supply voltage complies with that required by the instrument. Probes have no connection polarity and 

can be extended using a normal bipolar cable (Note that extending the probes burdens the behaviour of the instrument in 

terms of EMC electromagnetic compatibility: specifically, if Pt100 probes with cable longer than 3 mt are used, an extreme 

care must be taken during wiring operations).

Probe cables, power supply cables and the TTL serial cable should be routed separately from power cables.

CONDITIONS OF USE

Permitted use

For safety reasons, the instrument must be installed and used according to the instructions supplied and, in particular, parts 

under dangerous voltages must not be accessible in normal conditions.

The device must be adequately protected from water and dust with regard to its application, and must only be accessible 

using tools (except for the front panel). The device is suitable for use in household refrigeration appliances and/or similar 

equipment and has been tested for safety aspects in accordance with the harmonised European reference standards.

Improper use

Any use other than that expressly permitted is prohibited. The relay contacts provided are of a functional type and subject 

to failure: any protection devices required by product standards, or suggested by common sense for obvious safety 

requirements, must be installed externally to the instrument.

Summary of Contents for ICPlus 902

Page 1: ...ICPlus 902 Electronic controller with 1 intervention point EN ...

Page 2: ...ns to the previous menu level Confirms parameter value Press for at least 5 sec Function can be configured by the user H33 DOWN Press and release Scroll menu items Decrease values Press for at least 5 sec Function can be configured by the user H32 SET ENTER Press and release Displays alarms if active Opens Machine Status menu Confirm commands Press for at least 5 sec Opens Programming menu ...

Page 3: ...rmanently on displays a humidity Flashing reduced set active and displays a pressure Flashing reduced set active and displays a humidity Relay OUT1 Not Used Permanently on OUT1 output active Flashing a delay a protection or a locked start up Off otherwise Alarm NOTE When switched on the device performs a Lamp Test the display and LEDs will flash for several seconds to check that they all function ...

Page 4: ...zer output only on models where this is provided Measurement range 50 140 C 58 284 F Accuracy better than 0 5 of end of scale 1 digit Resolution 0 1 C 0 1 F up to 199 9 F 1 F over NTC PTC 12V 12 24V Supply Pb1 OUT1 1 2 3 8 9 10 11 NTC PTC 24V 115V 230V Supply Pb1 OUT1 1 2 3 4 5 10 11 TERMINALS 1 2 N C regulator relay OUT1 4 5 Power supply 24Va 115Va and 230Va 1 3 N O regulator relay OUT1 8 9 Power...

Page 5: ...STrelay 16 8 A2Hp 250Va Buzzeroutput only on models where this is provided Measurementrange 50 140 C 58 284 F Accuracy better than 0 5 of end of scale 1 digit Resolution 0 1 C 0 1 F up to 199 9 F 1 F over NTC PTC 12V 2 Hp Supply Pb1 OUT1 4 5 7 8 9 10 11 NTC PTC 230V 2 Hp Supply Pb1 OUT1 4 5 7 6 9 10 11 TERMINALS 4 5 N O regulator relay OUT1 6 7 Power supply 24Va 115Va and 230Va 9 11 Probe Pb1 Inpu...

Page 6: ...Buzzer output only on models where this is provided Measurement range 1999 1999 Accuracy better than 0 5 of end of scale 1 digit Resolution 1 or 0 1 digit according to settings V I 12V 12 24V 12V I V Supply OUT1 1 2 3 7 8 9 10 11 12 V I 24V 115V 230V 12V I V Supply OUT1 1 2 3 7 6 9 10 11 12 TERMINALS 1 2 N O regulator relay OUT1 7 8 Power supply 12Va c and 12 24Va 12 36Vc 1 3 N C regulator relay O...

Page 7: ... models where this is provided Measurement range 150 1350 C 238 2462 F Accuracy see Pt100 TcJ TcK models table Resolution see Pt100 TcJ TcK models table PT100 Tcj Tck 12V 12 24V Supply Pb1 1 2 3 6 7 10 11 12 OUT1 PT100 Tcj Tck 24V 115V 230V Supply Pb1 1 2 3 6 5 10 11 12 OUT1 TERMINALS 1 2 N O regulator relay OUT1 6 7 Power supply 12Va c and 12 24Va 12 36Vc 1 3 N C regulator relay OUT1 10 11 12 Pro...

Page 8: ...git 0 3 from 40 to 800 C RESOLUTION 0 1 C 0 1 F from 199 9 C up to 199 9 C 1 C 1 F beyond MOUNTING DIMENSIONS The device is designed for panel mounting Drill a 29x71 mm hole and insert the instrument secure it with the special brackets provided Do not install the instrument in damp and or dirty places in fact it is suitable for use in places with ordinary or normal levels of pollution Keep the are...

Page 9: ... wires Transducer Transducer brown white 9 10 11 12 EWHS 304 314 3 wires Probe GND only EWHS314 V RH T 9 10 11 12 EWHS 284 2 wires Probe brown blue 9 10 11 12 EWHS 314 4 wires V I model Probe GND V RH T GND ICPlus 1 ICPlus 2 9 10 11 12 9 10 11 12 ...

Page 10: ... If the procedure is a success y will appear on the display otherwise n will appear Format Fr This command is used to format the copy card recommended when using the card for the first time Important the Fr parameter deletes all data present This operation cannot be cancelled Download Connect the Copy Card when the instrument is switched off At power on data is downloaded from the copy card to the...

Page 11: ...assword is enabled by default PS2 15 To modify it PS2 15 press and hold for longer than 5 seconds scroll through the parameters using and until you see the label PA2 press set the value to 15 using and then confirm using Scroll through the folders until you find the label diS and press to enter Scroll through the parameters using and until you see the label PS2 press to display the value modify it...

Page 12: ...ramming menu press the key for more than 5 seconds If specified an access PASSWORD will be requested PA1 for User parameters and PA2 for Installer parameters see PASSWORD paragraph User Parameter When accessed the display will show the first parameter e g diF Press and to scroll through all the parameters on the current level Select the desired parameter by pressing Press and to modify it and to s...

Page 13: ...measuredvaluesareoutside operatingrange Probefaulty short circuited open DisplaylabelE1 Alarmiconpermanentlyon Disablemax minalarmcontroller Compressoroperationbasedon parametersOn1andOF1 checkprobetype H00 checkprobewiring replaceprobe AH1 AlarmforHIGH value Probe1 valuereadbyPb1 HA1after timeof tAO Recordingof labelAH1infolderAL Noeffectonregulation WaituntilvaluereadbyPb1 returnsbelowHA1 AL1 Al...

Page 14: ...5 BusAdapter ICPlus TTL IMPORTANT CHECK THE AVAILABILITY OF MODELS COMPATIBLE WITH REMOTE SUPERVISION SYSTEMS DUTY CYCLE DIAGRAM The device uses parameters On1 e OF1 set for Duty Cycle An error condition in probe1 regulation causes one of the following actions Code E1 is shown on the display The regulator is activated as indicated by parameters On1 and OF1 if set for Duty Cycle On1 OF1 Regulator o...

Page 15: ...ge category II Rated impulse voltage 2500V Temperature Operating 5 55 C Storage 30 85 C Power supply 12Va c 10 24 Va 10 12 24Va 12 36Vc 10 115Va 10 50 60 Hz 230 Va 10 50 60 Hz Consumption 1 5 VA max model 12Va c 3 W max models 24Va 12 24Va 12 36Vc 115Va and 230Va Digital outputs relay refer to the label on the device Fire resistance category D Software class A NOTE check the power supply specified...

Page 16: ...Regulations Electromagnetic compatibility The device conforms to Directive 2004 108 EC Safety The device conforms to Directive 2006 95 EC Food Safety The device complies with standard EN13485 as follows suitable for storage application air climate range A measurement class 1 in the range from 25 C to 15 C exclusively using Eliwell probes NOTE The technical specifications given in this document reg...

Page 17: ...atatemperaturevalueequaltoT SP1 dF1relativetoHC1 NTC PTC 0 0 30 0 1 0 C F User Inst PT100 Tc 0 0 30 0 1 0 C F V I 0 30 1 num HS1 MaximumvalueassignabletosetpointSP1 NTC PTC LS1 HdL 140 0 C F User Inst PT100 Tc 1350 C F V I 199 num LS1 MinimumvalueassignabletosetpointSP1 NTC PTC LdL HS1 50 0 C F User Inst PT100 Tc 199 9 C F V I 199 num HA1 MaximumtemperaturealarmonOUT1 See Max Min temperature alarm...

Page 18: ...er1switch off timeintheeventof faultyprobe if OF1 1andOn1 0 thecontrollerremainsoff if OF1 1andOn1 0 thecontrolleroperatesinDutyCyclemode ALL 0 250 1 min Inst ALARMs folder AL AFd Alarmdifferential NTC PTC 1 0 50 0 2 0 C F Inst PT100 Tc 1 0 50 0 2 0 C F V I 1 50 2 num tP Enableallkeystoacknowledgeanalarm n 0 no y 1 yes ALL n y y flag Inst COMMUNICATION folder Add PtS Selectionof communicationproto...

Page 19: ...hevaluereadby Pb1 accordingtothesettingof parameterCAI NTC PTC 30 0 30 0 0 0 C F User Inst PT100 Tc 30 0 30 0 0 0 C F V I 30 30 0 num CAI Interventionof theoffsetondisplay temperaturecontrolorboth 0 onlythetemperatureshownismodified 1 sumwithonlythetemperatureusedbythecontrollersandnotforthe display whichremainsunchanged 2 sumwiththedisplayedtemperature whichisalsousedbytheregulators ALL 0 1 2 2 n...

Page 20: ...nst PT100 Tc V I 1999 1999 0 num H04 Uppercurrent voltagelimitforinput only present on modelV I NTC PTC User Inst PT100 Tc V I 1999 1999 1000 num H05 Windowfilter 2 veryfast 1 fast 0 normal 1 slow 2 veryslow ALL 2 1 0 1 2 0 num Inst H06 KeyorDigitalInputwithaux lightordoorswitchactivewiththedeviceOFF but powered n 0 notactive y 1 active ALL n y y flag Inst H08 Stand byoperatingmode 0 onlydisplaysw...

Page 21: ...rsfromCopyCardtoinstrument ALL Inst Fr Format CancelsalldataenteredintheCopyCard IMPORTANT If parameterFr CopyCardformatting isused thedataentered inthecardwillbepermanentlylost Thisoperationcannotbereversed ALL Inst FUNCTIONS folder FnC Function Function label ACTIVE Function label NOTACTIVE D I KEY Alarm signaling Reduced setpoint OSP SP 2 2 ON Icon Stand by On OF 6 6 ON Icon Alarm acknowledgeme...

Page 22: ... during wiring operations Probe cables power supply cables and the TTL serial cable should be routed separately from power cables CONDITIONS OF USE Permitted use For safety reasons the instrument must be installed and used according to the instructions supplied and in particular parts under dangerous voltages must not be accessible in normal conditions The device must be adequately protected from ...

Page 23: ...not complying with current standards and regulations DISCLAIMER Thisdocumentistheexclusiveproperty of ELIWELLCONTROLS SRLandmay not be reproducedor circulated unlessexpressly authorised by ELIWELL CONTROLS SRL itself Every care has been taken in preparing this document nevertheless ELIWELL CONTROLS SRL cannot accept liability for any damage resulting from its use The same applies to any person or ...

Page 24: ...9 0437 989 066 www eliwell com Technical Customer Support Technical helpline 39 0437 986 300 E mail techsuppeliwell invensys com Sales Telephone 39 0437 986 100 Italy 39 0437 986 200 other countries E mail saleseliwell invensys com cod 9IS44315 1 ICPlus 902 EN rel 09 13 Eliwell Controls s r l 2013 Tutti i diritti riservati ...

Reviews: