PAR. DESCRIPTION
MODEL
RANGE
VALUE M.U. LEVEL
dO1
Delay time after switching off. The indicated time must elapse between
deactivation of the controller 1 relay and the next switch-on.
0
= not active.
ALL
0...250
0
min
Inst
di1
Delay between switch-ons. The indicated time must elapse between two
consecutive switch-ons of regulator 1.
0
= not active.
ALL
0...250
0
min
Inst
dE1
Switch-off delay. The indicated time must elapse between the request for
deactivation of the controller 1 relay and switch-off.
0
= not active.
ALL
0...250
0
min
Inst
On1
Controller 1 switch-on time in the event of faulty probe.
if
On1
=1 and
OF1
=0, the controller remains on;
if
On1
=1 and
OF1
>0, the controller operates in Duty Cycle mode.
ALL
0...250
0
min
Inst
OF1
Controller 1 switch-off time in the event of faulty probe.
if
OF1
=1 and
On1
=0, the controller remains off;
if
OF1
=1 and
On1
>0, the controller operates in Duty Cycle mode.
ALL
0...250
1
min
Inst
ALARMs (folder ‘AL’)
AFd
Alarm differential.
NTC/PTC
1.0...50.0
2.0
°C/°F
Inst
PT100-Tc
1.0...50.0
2.0
°C/°F
V/I
1...50
2
num
tP
Enable all keys to acknowledge an alarm.
n
(0) = no;
y
(1) = yes.
ALL
n/y
y
flag
Inst
COMMUNICATION (folder ‘Add’)
PtS
Selection of communication protocol.
t
= Televis;
d
= Modbus.
ALL
t/d
t
flag
Inst
dEA
Index of the device within the family (valid values from 0 to 14).
ALL
0...14
0
num
Inst
FAA
Device family (valid values from 0 to 14).
ALL
0...14
0
num
Inst
Adr
Modbus protocol controller address.
ALL
1...255
1
num
Inst
bAU
Baudrate selection.
48
(0) = 4800;
96
(1) = 9600;
192
(2) = 19200;
384
(3) = 38400.
ALL
48/96/
192/384
96
num
Inst
Pty
Modbus parity bit.
n
(0) = none;
E
(1) = even;
o
(2) = odd.
ALL
n/E/o
E
num
Inst
StP
Modbus stop bit.
1b
(0) = 1 bit;
2b
(1) = 2 bit.
ALL
1b/2b
1b
flag
Inst