22

ST 3 Pin 15  NC 
 
ST 3 Pin 16  Program cycle counter – 

switches actual values into the display

 

With activating 

ST3 Pin 6

, the counter value of the program cycle counter is displayed 

in the actual value windows:  

Actual value X = Counter value 
Actual value X = Counter value 

 

ST 3 Pin 17 NC 
 
 
ST 3 Pin 18  Retract X 

Activating of 

ST3 Pin 18,

 starts the 

retract function

 of the 

X axis

 

  a.   

R 18/X=X0XXXX

 

Æ

  retract distance = actual value + value in 

R6

 

 b.   

R 18/X=X1XXXX

 

Æ

  retract to value in 

R5

 

 c.   

R 18/X=X2XXXX

 

Æ

  retract to time in 

R10

 

 

 

ST 3 Pin 19  Retract Y 

Activating of 

ST3 Pin 19,

 starts the 

retract function

 of the 

Y axis

 

 a.  

R 18/X=X0XXXX

 

Æ

  retract distance = actual value + value in 

R6

 

 b.   

R 18/X=X1XXXX

 

Æ

  retract to value in 

R5

 

 c.   

R 18/X=X2XXXX

 

Æ

  retract to time in 

R10

 

 

 
 
ST 3 Pin 20  NC 
 
ST 3 Pin 21  NC 

 

Summary of Contents for P8822-000-R Series

Page 1: ...P8822 000 R SERIES P8822 000 P D_25 04 Dual axes position controller 2 or 3 switched speed operation manual inching mode single set operation 200 line program memory...

Page 2: ...unction of the displays 6 3 2 Function of the keypad 6 4 CONTROLLER IN OPERATION 8 4 1 Single operation 8 4 2 Program line operation R 8 4 0 8 4 3 Table operation R8 4 1 9 4 4 Manual inching 10 5 REGI...

Page 3: ...8 FUNCTION OF INPUTS ST3 CONNECTIONS 21 9 FUNCTIONS OF THE OUTPUTS ST4 ST6 CONNECTIONS 23 11 CONNECTIONS 25 12 TECHNICAL SPECIFICATIONS 26 13 INSTALLATION AND WIRING 27 14 ONLY FOR SERVICE 28 15 TYPE...

Page 4: ...Functions The P8822 controller can be operated with 2 or 3 different speeds 2 1 Two speed operation switched NB R1 R2 R3 The value in Register 1 must be the same value as R2 2 2 Three speed operation...

Page 5: ...st be present The controller monitors the pulses at intervals set in Register R19 X Y If the Register R19 X Y is set to 0 the monitoring features will be disabled Should a failure occur the ERROR01 is...

Page 6: ...on can be entered The Y Axis target position can be entered with pressing 2 With renewed pressing of Hand Single LED Hand shines additionally and using the keys 7 8 9 NR the selected axis can be proce...

Page 7: ...e preset windows sequentially On completion of a line the next press of will select the next address line LEDs 1 3 indicate the selected Window E This button will Set the end of program and reset the...

Page 8: ...Y will be positioned The next positions can be operated by renewed using of the steps 3 6 then 4 2 Program line operation R 8 4 0 4 2 1 Selection of a program block The P8822 is equipped with a progr...

Page 9: ...is complete now Third step End or continue Press E to end programming Press to continue resp programming the next line 4 3 Table operation R8 4 1 With setting R8 4 1 R8 XXX1XX the controller operates...

Page 10: ...n pressed When closed loop analog control is used the respective speeds are set in R60 R63 in rpm The proportional analog output voltage is given when the button is pressed 5 Register Input 5 1 Unlock...

Page 11: ...set the old value Type in 200 The window shows 200 i e 20 0 mm Press E The new value is saved now All windows are 0 and the decimal point is reinstated Any Register from 1 to 97 can be selected and ch...

Page 12: ...ning 0 2 R 18 5 Keyboard interlock 0 3 R 18 6 Option R 19 Pulse time of encoder monitoring 0 1 sec R 20 Decimal place see page 18 R 28 System Register 3 see page 18 R 29 Time delay for drive inhibit 0...

Page 13: ...tion will be overrun by the value of R4 and drive back to the target position with creep speed after the time delay of R10 R05 Retract distance X Y There are different modes available in the P8822 sel...

Page 14: ...2 speeds independent outputs for speed and direction 5 2 speeds independent speed and direction separate reverse 6 2 speeds separate outputs for each condition 7 2 speeds separate outputs for each co...

Page 15: ...X X X X output activated R8 5 2 2 speeds separate outputs for each condition Output signals ST4 X ST6 Y 1 5 2 6 3 7 4 8 Creep forwards X Slow forwards X Fast forwards X Creep reverse X Slow reverse X...

Page 16: ...ed R8 5 7 2 speeds separate outputs for each condition Output signals ST4 X ST6 Y 1 5 2 6 3 7 4 8 Creep forwards X Slow forwards X Fast forwards X Creep reverse X Slow reverse X Fast reverse X X outpu...

Page 17: ...rect adjustment of R1 R4 other values can be used here R13 R14 Min Max software limits Target Limit R13 error message ERR04 Target Limit R14 error message ERR05 Single operation Immediately after a st...

Page 18: ...link 0 none R19 cycle time of encoder monitoring If after positioning is initiated no encoder pulses are sensed after a time set in R19 0 1 9 9 s positioning will be aborted and Fault ERROR01 will be...

Page 19: ...to R47 the output ready drop of and cycle count is displayed in actual position window The external and front panel Start are disabled To clear the output to allow positioning again R47 must be set t...

Page 20: ...2 Display brightness With the setting of this register the brightness of the display can be altered digitally 0 0 dark 9 9 max brightness R96 Pulse scaling factor A factor 0 00001 9 9999 can be entere...

Page 21: ...ual value announcements and length parameters are converted in inch ST 3 Pin 6 Keyboard interlock With activating ST3 Pin 6 the keyboard interlock adjusted in R18 5 is unlocked ST 3 Pin 7 Reference Da...

Page 22: ...ST 3 Pin 18 Retract X Activating of ST3 Pin 18 starts the retract function of the X axis a R 18 X X0XXXX retract distance actual value value in R6 b R 18 X X1XXXX retract to value in R5 c R 18 X X2XXX...

Page 23: ...n process With pressing START the output positioning in process will be set The output resets first after reaching the target position of both axes and completion of the time in R29 ST 5 Pin 17 progra...

Page 24: ...24 10 Rear of the unit ST9 INPUTS ST3 ST4 ST7 Power Supply RS 232 ST2 Encoder Y Fuse 0 4 A 1 2 3 OUTPUTS ST5 ST6 ST1 Encoder X...

Page 25: ...IN Standard 0 Customer 2 LD Customer 3 AD Customer 1 DR 1 24V EN 0V 24V EN 0V 24V EN 0V 24V EN 0V 2 Start X Y NC Start X Y Start X Y 3 Stop X Y Stop X Y Stop X Y Stop X Y 4 Datum X Datum X Datum X Dat...

Page 26: ...aused short circuit proof with a max load of 50 mA with integrated recovery diode Power down memory E2 Prom service life 105 power on off cycles Connectors D SUB Displays Red LED displays height 10 mm...

Page 27: ...be connected centrally low ohm to PE earth potential connect only one sided at the P8822 Controller IMPORTANT 1 Don t connect the P8822 s GND to PE earth potential 2 Don t connect the shielding on bot...

Page 28: ...5 Type designation P position controller Series Program memory 1 without 2 with Number of axes Version 000 Standard 001 1 Special version Power supply 024 24 VDC 115 115 VAC 230 230 VAC Encoder Inputs...

Page 29: ...eep all rights reserved for any technical modifications without any notice ELGO Electric does not assume any liability for possible errors or mistakes The guarantee period is one calendar year from th...