Elgar CW-M Series
The following notes apply to Table 3–1 and to the power cable definition:
1.
The above figures are based upon insulated copper conductors at 25
C (77
F),
two current carrying conductors in the cable plus a safety (chassis) ground.
Columns 3 and 4 refer to “one way” ohms and IR drop of current carrying
conductors (e.g., a 50-foot cable contains 100 feet of current carrying conductor).
2.
Determine which wire gauge for the application by knowing the expected peak
load current (I
peak
), the maximum tolerated voltage loss (V
loss
) within the cable,
and the one way cable length.
The formula below determines which ohms/100 feet entry is required from
Column 3. Read the corresponding wire gauge from Column 1.
(Column 3 value) =
V
loss
/[I
peak
x 0.02 x (cable length)]
Where:
Column 3 value =
Entry of the table above.
Cable length =
One way cable length in feet.
V
loss
=
Maximum loss, in volts, permitted within cable.
Special case: Should the V
loss
requirement be very loose, I
peak
may exceed the
maximum amperes (Column 2). In this case, the correct wire gauge is selected
directly from the first two columns of the table.
Example: A 20 ampere (I
peak
) circuit which may have a maximum 0.5 volt
drop (V
loss
) along its 15-foot cable (one way cable length) requires (by formula)
a Column 3 resistance value of 0.083. This corresponds to wire gauge size 8
AWG.
If the cable length was 10 feet, the Column 3 value would be 0.125 and the
corresponding wire gauge would be 10 AWG.
3.
Aluminum wire is not recommended due to soft metal migration at the terminals
which may cause long term (on the order of years) poor connections and
oxidation. If used, increase the wire gauge by two sizes (e.g., specify 10 gauge
aluminum instead of 14 gauge aluminum).
11
Summary of Contents for CW 1251M
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank...
Page 12: ...Elgar CW M Series This page intentionally left blank 2...
Page 24: ...Elgar CW M Series Figure 3 2 Mounting Dimensions Front and Rear Views CW 801M CW 1251M 14...
Page 25: ...Elgar CW M Series Figure 3 3 Mounting Dimensions Front and Rear Views CW 2501M 15...
Page 26: ...Elgar CW M Series Figure 3 4 Mounting Dimensions Top and Side Views CW 801M CW 1251M 16...
Page 27: ...Elgar CW M Series Figure 3 5 Mounting Dimensions Top and Side Views CW 2501M 17...
Page 34: ...Elgar CW M Series This page intentionally left blank 24...
Page 38: ...Elgar CW M Series 4 3 2 Setup for Six in Parallel Configuration 28...
Page 39: ...Elgar CW M Series 4 3 3 Setup for Six Phase Configuration 29...
Page 40: ...Elgar CW M Series 4 3 4 Setup for Two Phase Configuration 30...
Page 42: ...Elgar CW M Series This page intentionally left blank 32...
Page 48: ...Elgar CW M Series This page intentionally left blank 38...