Electrolux EACM-09 HR/N6 User Manual Download Page 14

14   

should be used.

Leak detection method:

For systems with refrigerant R290, electronic 

leak detection instrument is available to detect 

and leak detection should not be conducted 

in environment with refrigerant. Make sure 

the leak detector will not become a potential 

source of ignition, and is applicable to the 

measured refrigerant. Leak detector shall be 

set for the minimum ignitable fuel concentra-

tion (percentage) of the refrigerant. Calibrate 

and adjust to proper gas concentration (no 

more than 25%) with the used refrigerant.

The fluid used in leak detection is applicable 

to most refrigerants. But do not use chloride 

solvents to prevent the reaction between 

chlorine and refrigerants and the corrosion of 

copper pipeline.

If you suspect a leak, then remove all the fire 

from the scene or put out the fire.

If the location of the leak needs to be welded, 

then all refrigerants need to be recovered, or, 

isolate all refrigerants away from the leak site 

(using cut-off valve). Before and during the 

welding, use OFN to purify the entire system.

Removal and Vacuum Pumping

1.  Make sure there is no ignited fire source 

near the outlet of the vacuum pump and 

the ventilation is well.

2.  Allow the maintenance and other opera-

tions of the refrigeration circuit should be 

carried out according to the general pro-

cedure, but the following best operations 

that the flammability is already taken into 

consideration are the key. You should fol-

low the following procedures:

•  Remove the refrigerant.

•  Decontaminate the pipeline by inert gases.

•  Evacuation.

•  Decontaminate the pipeline by inert gases 

again.

•  Cut or weld the pipeline.

3.  The refrigerant should be returned to the 

appropriate storage tank. The system 

should be blown with oxygen free nitrogen 

to ensure safety. This process may need to 

be repeated for several times. This opera-

tion shall not be carried out using com-

pressed air or oxygen

Through blowing process, the system is 

charged into the anaerobic nitrogen to reach

the working pressure under the vacuum state, 

then the oxygen free nitrogen is emitted

to the atmosphere, and in the end, vacuumize 

the system. Repeat this process until all

refrigerants in the system is cleared. After the 

final charging of the anaerobic nitrogen,

discharge the gas into the atmosphere pres-

sure, and then the system can be welded.

This operation is necessary for welding the 

pipeline.

Procedures of Charging Refrigerants

As a supplement to the general procedure, the 

following requirements need to be added:

•  Make sure that there is no contamination 

among different refrigerants when using a 

refrigerant charging device. The pipeline 

for charging refrigerants should be as short 

as possible to reduce the residual of refrig-

erants in it.

•  Storage tanks should remain vertically up.

•  Make sure the grounding solutions are 

already taken before the refrigeration sys-

tem is charged with refrigerants.

•  After finishing the charging (or when it is 

not yet finished), label the mark on the 

system.

•  Be careful not to overcharge refrigerants

Scrap and Recovery

Scrap:

Before this procedure, the technical personnel 

shall be thoroughly familiar with the equipment 

and all its features, and make a recommended 

practice for refrigerant safe recovery. For recy-

cling the refrigerant, shall analyze the refriger-

ant and oil samples before operation. Ensure 

the required power before the test.

1.  Be familiar with the equipment and opera-

tion.

2.  Disconnect power supply.

3.  Before carrying out this process, you have 

to make sure:

•  If necessary, mechanical equipment opera-

tion should facilitate the operation of the 

refrigerant tank.

•  All personal protective equipment is effec-

tive and can be used correctly.

•  The whole recovery process should be car-

ried out under the guidance of qualified 

personnel.

•  The recovering of equipment and stor-

age tank should comply with the relevant 

national standards.

4.  If possible, the refrigerating system should 

be vacuumized.

5.  If the vacuum state can't be reached, you 

should extract the refrigerant in each part 

of the system from many places.

6.  Before the start of the recovery, you should 

ensure that the capacity of the storage 

Summary of Contents for EACM-09 HR/N6

Page 1: ...USER S MANUAL EACM 09 HR N6 EACM 12 HR N6 ...

Page 2: ...able EACM 09 HR N6 EACM 12 HR N6 WE THINK ABOUT YOU Thank you for purchasing an Electrolux appliance You have chosen a product backed by decades of professional experience and innovations Unique and stylish it was created with care for you Therefore whenever you use it you can be sure that the results will always be excellent Welcome to Electrolux Content Safety information 3 Parts Description 4 C...

Page 3: ... may cause harm or damage to people properties etc The seriousness is classified by the following indications WARNING This symbol indicates the possibility of death or serious injury CAUTION This symbol indicates the possibility of injury or damage to properties WARNING This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabiliti...

Page 4: ...k fire or personal injury 1 The plug must be plugged into an outlet that is properly installed and grounded 2 Do not use an extension cord or plug adaptor with this unit CAUTION Don t apply the cold air to the body for a long time It will deteriorate your physical conditions and cause health problems Don t block air inlet or air outlet otherwise the cooling heating capacity will be weakened even c...

Page 5: ...rol Panel TEMP indicator TEMP indicator In cooling or heating mode when or button is pressed the setting temperature is displayed and be adjusted 1 In auto cool and heat mode TEMP indica tor display is setting temperature 2 In dry and fan mode TEMP indicator dis play is room temperature Function buttons 1 button Press this button to make the unit run or stop 2 button a The running time of the unit...

Page 6: ...G Failure to follow the below precaution could result in electrical shock fire explosion or personal injury 1 The plug must be plugged into an individual socket that is properly installed and grounded 2 Do not use an extension cord or plug adaptor with this unit Before starting the unit 1 Select a suitable location make sure the unit is near to an electrical outlet 2 Install the flexible exhaust h...

Page 7: ...se it 2 No automatic wind sweep function models air louver minimum opening angle from air louver closed state breaking up 5 grid air louver opening angle can not be less than the minimum open angle when use it Unpacking Inspection Open the box and check unit in area with good ventilation open the door and win dow and without ignition source Note Operators are required to wear anti static devices I...

Page 8: ...m The space shall not be less than usable space i2m2 in the specification The unit shall be installed at a well ventilated place Check the surrounding environment of installation site R290 shall not be installed in the enclosed reserved space of a build ing Installation Guide of customer The customer should have a qualified power supply coincident with that printed on the tag of the air conditione...

Page 9: ... Screw A window slide kit Wall exhaust adaptor Adaptor B round mouth 2 Attach the window slider kit to the window sash Adjust the length of the Window Slider Kit Loose the screw A to adjust the length of the Window Slider Kit then tight the screw when the length is suitable Note the length of the Window Slider Kit is 67 5cm to 120cm Screw B 3 Carefully lower the window Secure the vent panel in pla...

Page 10: ...efficiency As the following fig Shows Do not Yes Without installation If the unit does not have the window slider kit and wall exhaust and the Adaptor В is like this as shown in Fig H You can open the window slightly and position as shown in Fig I Fig H Fig I Water drainage During dehumidifying mode remove the upper drain plug from the back of the unit Attach the drain hose to the hole Place the o...

Page 11: ...ouring water directly over any of the surface areas as this will cause deterioration of electrical components and wiring insulation Clean the unit When the unit is contaminated clean it gently with a wrung towel using tepid water below 40 C 104 F Clean the Air Filter 1 Remove the air filter Take out the upper air filter and the lower air filter Note There are two types about the low air intake gri...

Page 12: ...itioner with R290 refrigerant and maintain the air conditioner in strictly accordance with manufacturer s requirements The chapter is mainly focused on special maintenance requirements for appliance with R290 refrigerant Ask repairer to read after sales technical service handbook for detailed information Qualification requirements of maintenance personnel 1 Special training additional to usual ref...

Page 13: ... correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant con taining parts are installed The ventilation mach...

Page 14: ... to reach the working pressure under the vacuum state then the oxygen free nitrogen is emitted to the atmosphere and in the end vacuumize the system Repeat this process until all refrigerants in the system is cleared After the final charging of the anaerobic nitrogen discharge the gas into the atmosphere pres sure and then the system can be welded This operation is necessary for welding the pipeli...

Page 15: ... and they should be in a good condition If possible empty tanks should be evacu ated and maintained at room temperature before use 3 The recovery equipment should be kept in a good working condition and equipped with equipment operating instructions for easy access The equipment should be suitable for the recovery of R290 refriger ants Besides there should be a quali fied weighting apparatus which...

Page 16: ...ay be considered as expendable supplies or which are made of glass The warranty is void if the defect is caused by damage ensuing by misuse poor maintenance for example a failure occurred due to ingress of foreign objects or liquids or if changes or repairs were performed by persons not authorized by the Manufacturer For the correct use of the product the user must strictly follow all included in ...

Page 17: ...in technical and typing errors Changes to technical characteristics and assortment are subject to change without notice Mistakes and typing errors may be permitted in texts and numeric notations Product design and technical data may vary from the one pictured on the packaging Please refer to a sales consultant for more detailed information ...

Page 18: ......

Page 19: ...Seller Seal Date of sale Model Product Details populated upon sale Serial number ...

Page 20: ...via Estonia and CIS countries only Electrolux is a registered trademark used under license from AB Electrolux publ This manual may contain technical and typing errors Changes to technical characteristics and assortment are subject to change without notice ...

Reviews: