CONNECTING TO THE MAINS
TERMINAL
We recommend you use a new length of 6mm
2
twin core and earthed cable to ensure your
safety.
Make connection as shown in Fig. 12 by
proceeding as follows:-
Preform wires to the appropriate shape to suit
fitting into the mains terminal block.
Strip inner insulation on wires using
wirestrippers.
Twist the bared wires using pliers.
Cut bared wires 10mm away from the end of the
inner insulation. Where uninsulated Earth wires
are used ensure they are suitably sheathed to
leave 10mm bare wire to fit into the terminal.
Clamp bare wires into the relevant terminal and
check they are held by tugging each one in turn.
Clamp the mains cable securely ensuring 5mm
of the outer insulation is inside the terminal
block and that the wires are not taught but not
so slack as to cause any fouling. See Fig. 12.
Connect the remaining end of the mains cable
to the cooker point / junction box.
Place fuse / miniature circuit breaker in circuit
and switch on at mains.
INSTALLATION INSTRUCTIONS
Warning: This appliance must be
earthed.
Fig. 12