11-14
CONTROL SYSTEM
Revision Y05-02
Service Manual - K DCI
11.12.2
Outdoor Unit Controller
JP9 JUMPER LAYOUT
Reserved
(PIN
9)
ODU3
(PIN 7)
ODU2
(PIN 5)
ODU1
(PIN 3)
ODU0
(PIN 1)
GND
(PIN 10)
GND
(PIN 8)
GND
(PIN 6)
GND
(PIN 4)
GND
(PIN 2)
ODU MODEL SELECTION
ODU3
ODU2
ODU1
ODU0
ODU Model
OFF
OFF
OFF
OFF
Reserved
OFF
OFF
OFF
ON (PIN1 & PIN2)
A (DCI 25)
OFF
OFF
ON (PIN3 & PIN4)
OFF
B (DCI 35)
OFF
OFF
ON (PIN3 & PIN4)
ON (PIN1 & PIN2)
C (DCI 50)
OFF
ON (PIN5 & PIN6)
OFF
OFF
D
OFF
ON (PIN5 & PIN6)
OFF
ON (PIN1 & PIN2)
E (Duo)
OFF
ON (PIN5 & PIN6)
ON (PIN3 & PIN4)
OFF
F
OFF
ON (PIN5 & PIN6)
ON (PIN3 & PIN4)
ON (PIN1 & PIN2)
G
ON (PIN7 & PIN8)
OFF
OFF
OFF
H
ON (PIN7 & PIN8)
OFF
OFF
ON (PIN1 & PIN2)
I
ON (PIN7 & PIN8)
OFF
ON (PIN3 & PIN4)
OFF
J
ON (PIN7 & PIN8)
OFF
ON (PIN3 & PIN4)
ON (PIN1 & PIN2)
K
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
OFF
OFF
L
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
OFF
ON (PIN1 & PIN2)
M
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
ON (PIN3 & PIN4)
OFF
N
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
ON (PIN3 ? PIN4)
ON (PIN1 & PIN2)
O
11.13
Test Mode
11.13.1
Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
Mode
l, Set point 16, Room temper
= Coo
=
ature = 27±1, Outdoor temperature = 35±1
Or
Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1
Manually when entering diagnostics with the following settings:
Mode = Cool, Set point = 16
Mode = Heat, Set point = 30
CONTENTS
CONTENTS
Summary of Contents for K 25 DCI INV
Page 71: ...FRANCAIS ENGLISH DEUTSCH ESPANOL ITALIANO APPENDIX A...
Page 72: ...ENGLISH APPENDIX A...
Page 73: ...2 3 5 6 APPENDIX A...
Page 76: ...3 APPENDIX A...
Page 77: ...4 APPENDIX A...
Page 78: ...5 OR Latch E F G C B A D APPENDIX A...
Page 79: ...6 APPENDIX A...
Page 80: ...7 APPENDIX A...
Page 81: ...8 APPENDIX A...
Page 82: ...9 APPENDIX A...
Page 83: ...APPENDIX A...
Page 84: ...11 APPENDIX A...
Page 85: ...APPENDIX A...