5-7
PERFORMANCE DATA
Revision Y05-02
Service Manual - K DCI
5.5 K35S
DCI
5.5.1
Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC
]
DATA
22/15
24/17
27/19
29/21
32/23
-10 - 20
(protection range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC
3.38
3.60
3.83
4.05
4.27
SC
2.65
2.70
2.75
2.81
2.86
PI
0.68
0.70
0.71
0.72
0.74
30
TC
3.22
3.44
3.66
3.88
4.11
SC
2.58
2.63
2.69
2.74
2.79
PI
0.76
0.78
0.79
0.80
0.82
35
TC
3.06
3.28
3.50
3.72
3.94
SC
2.51
2.57
2.62
2.67
2.73
PI
0.84
0.86
0.87
0.88
0.90
40
TC
2.89
3.12
3.34
3.56
3.78
SC
2.45
2.50
2.55
2.61
2.66
PI
0.92
0.94
0.95
0.96
0.98
46
TC
2.70
2.92
3.14
3.36
3.58
SC
2.37
2.42
2.47
2.53
2.58
PI
1.02
1.03
1.05
1.06
1.07
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.5.2
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20
25
30
35
40
45
Outdoor Temperature [deg C]
Capa
ci
ty
Rat
ion
CONTENTS
CONTENTS
Summary of Contents for K 25 DCI INV
Page 71: ...FRANCAIS ENGLISH DEUTSCH ESPANOL ITALIANO APPENDIX A...
Page 72: ...ENGLISH APPENDIX A...
Page 73: ...2 3 5 6 APPENDIX A...
Page 76: ...3 APPENDIX A...
Page 77: ...4 APPENDIX A...
Page 78: ...5 OR Latch E F G C B A D APPENDIX A...
Page 79: ...6 APPENDIX A...
Page 80: ...7 APPENDIX A...
Page 81: ...8 APPENDIX A...
Page 82: ...9 APPENDIX A...
Page 83: ...APPENDIX A...
Page 84: ...11 APPENDIX A...
Page 85: ...APPENDIX A...