ET083 2G/3G COMMUNICATOR V1.0

• 

Contact ID –

 Ademco Contact ID data format.

• 

Scancom

*** - Data format complying with Scancom/BSIA Fast Format protocol requirements.

8.  On eT083: Open 

Events Log

 section to monitor the activity.

9.   On eT083****: If required, the Account number set on the alarm panel can be overridden under 

System 

 Security Panel Settings  

section. For 

more details, please refer 

9. MONITORING STATION PHONE NUMBER AND ACCOUNT REPLACEMENT

.

*  

Necessary only when using RING/TIP interface communication wiring method.

**  

Necessary     only when using Keybus interface communication wiring method. When using RING/TIP interface communicates wiring meth-

od, it might be useful to replace the monitoring station phone number retrieved from the alarm panel.

***  

Supported only when using RING/TIP interface communication wiring method.

****   Useful only when using RING/TIP interface communication wiring method.
 

For more details on the parameters located under 

Voice Calls Settings 

section, please refer to

 

ELDES Configuration Tool

 software’s HeLP 

file.

7.2.2. SMS Method

Based on the communication wiring method that is being used, using this method the communicator:

• 

RING/TIP interface

 – Retrieves Ademco Contact ID data from the alarm panel, converts it into user-understandable text and delivers to up 

to 5 listed users by SMS text message. Before proceeding with any further configuration, please complete the steps provided in 

6.1. RING/TIP 

Interface

.

• 

Keybus or Serial interface

 – Retrieves serial data from the alarm panel, converts it into Ademco Contact ID data  followed by conversion into 

user-understandable text and delivery to up to 5 listed users by SMS text message. Before proceeding with any further configuration, please 

complete the steps provided in 

6.2. Keybus and Serial Interfaces

.

To set the communicator to transmit data using this communication method, please proceed as follows:

1.  On alarm panel*: enable Ademco Contact ID mode.

2.  On alarm panel*: Set random Account number.

3.  On alarm panel*: Set random monitoring station phone number; single digit is sufficient.

4.  On eT083: Connect the device to the computer via USB cable and run 

ELDES Configuration Tool

 software.

5.  On eT083: Open 

System 

 Settings

 section and proceed as follows:

a.  enable 

Advanced Mode

.

b.  Set SMS as Primary connection. In addition, 

Backup 1

 and 

Backup 2

 connections can be set under this section.

6.  On eT083: Open

 Messaging Settings

 section and proceed as follows:

a.  Set up to 5 user phone numbers that will be permitted to receive the data converted into user-understandable text by SMS text message. The 

supported phone number formats are the following:

•  International (with plus) 

– The phone numbers must be entered starting with plus and an international country code in the following 

format: +[international code][area code][local number], example for 

UK: +44170911XXXX1

.

•  International (with 00) 

– The phone numbers must be entered starting with 00 and an international country code in the following for-

mat: 00[international code][area code][local number], example for 

UK: 0044170911XXXX1

.

•  Local 

– The phone numbers must be entered starting with an area code in the following format: [area code][local number], example for 

UK: 0170911XXXX1

.

b.  Manage SMS text message content reflecting the Ademco Contact ID data message structure.

c.  Based on the alarm panel’s documentation, ensure that all CID event codes supported by the alarm panel are added under the Messaging 

Settings section, otherwise the communicator will be unable to deliver a certain event.

7.  On eT083: Open 

Events Log

 section to monitor the activity.

*   Necessary only when using RING/TIP interface communication wiring method.
  For more details on the parameters located under 

Messaging Settings 

section, please refer to

 

ELDES Configuration Tool

 software’s HeLP file.

7.2.3. IP Method

Based on the communication wiring method that is being used, using this method the communicator:

• 

RING/TIP interface

 – Retrieves Ademco Contact ID data from the alarm panel, converts it into eGR100, Kronos or SIA IP protocol and transmits 

to the monitoring station via 2G/3G network or ethernet connection using eLAN3-ALARM device. Before proceeding with any further configu-

ration, please complete the steps provided in 

6.1. RING/TIP Interface

.

• 

Keybus or Serial interface

 – Retrieves serial data from the alarm panel, converts it into Ademco Contact ID

 

followed by data conversion to 

eGR100, Kronos or SIA IP protocol and transmission to the monitoring station via 2G/3G network or ethernet connection using eLAN3-ALARM 

device. Before proceeding with any further configuration, please complete the steps provided in 

6.2. Keybus and Serial Interfaces

.

To set the communicator to transmit data using this communication method, please proceed as follows:

1.  On alarm panel*: enable Ademco Contact ID mode.

Summary of Contents for ET083

Page 1: ...2G 3G COMMUNICATOR ET083 en...

Page 2: ...y additional device you connect to the device such as a computer must also be powered by an EN 60950 1 approved supply When connecting the power supply to the device mind the polarity terminals DO NOT...

Page 3: ...asic Mode 17 7 2 Advanced Mode 21 8 2G 3G MODEM SETTINGS 24 9 SMS FORWARD 24 10 MONITORING STATION PHONE NUMBER AND ACCOUNT REPLACEMENT 25 11 SMS PASSWORD 25 12 USER PHONE NUMBERS 25 13 INPUTS 26 14 O...

Page 4: ...a hardware defect at no charge using new or refurbished replacement parts or b exchange the product with a product that is new or which has been manufactured from new or serviceable used parts and is...

Page 5: ...cument or pass to a third party without an advanced written au thorization from ELDES UAB ELDES UAB reserves the right to update or modify this document and or related products without a warning Hereb...

Page 6: ...ol by free of charge phone call and SMS text message Automatic output control in accordance with a specified event Up to 3 users for minor device configuration by SMS text messages acceptance of input...

Page 7: ...for PSTN state supervision set up F1 0 5A fuse Connector Functionality L1 L4 Terminals for connection to PSTN PBX RING TIP Terminals for connection to alarm panel s RING TIP interface C1 C3 Open colle...

Page 8: ...sumption of up to 700mA Otherwise please use an external power supply unit for ET083 2 4 2 Output Wiring C1 DC COM C2 C3 ALARM PANEL OR OTHER APPLIANCE ELECTRICAL APPLIANCE 12 24 AUX AUX ET083 4 2 4 3...

Page 9: ...6 Power up the device and wait until indicator STATUS lights up 7 The device starts up in less than a minute Indicator STATUS should be steady ON indicating successful micro controller operation 8 The...

Page 10: ...input to a non 2G 3G alarm panel s PGM output up to 3 listed user phone numbers will be able to receive an SMS text message as well as to notify the monitoring station regarding arming disarming and o...

Page 11: ...ormat international code area code local number example for UK 44170911XXXX1 International with 00 The phone numbers must be entered starting with 00 and an international country code in the following...

Page 12: ...tically expire in 20 minutes Before the last 5 minutes the software will offer the user to extend the session for another 20 minutes Alternatively the connection with the server can be terminated at a...

Page 13: ...ink between the alarm panel and the monitoring station is established using ET083 device in the middle The communicator retrieves data from the alarm panel and transmits it to the monitoring station v...

Page 14: ...or s RING and TIP terminals to the alarm panel s RING and TIP terminals respectively 2 Connect the communicator s L1 and L2 terminals in parallel to the external PSTN line of the PBX connected to PSTN...

Page 15: ...t the communicator s Z2 and Z1 terminals to the alarm panel s GRN and YEL terminals respectively b Serial interface connection Connect the communicator s SERIAL interface to the alarm panel s SERIAL i...

Page 16: ...mco Contact ID converted into user understandable text IP 2G 3G Ethernet via ELAN3 ALARM 1 destina tion IP address EGR100 Kronos SIA IP IP 2G 3G Ethernet via ELAN3 ALARM up to 3 destination IP address...

Page 17: ...m ELAN3 ALARM ELAN3 ALARM ELAN3 ALARM ELAN3 ALARM EGR100 EGR100 EGR100 EGR100 EGR100 EGR100 EGR100 EGR100 Kronos Kronos Kronos Kronos Kronos Kronos Kronos Kronos SIA IP SIA IP SIA IP SIA IP SIA IP SIA...

Page 18: ...g format 00 international code area code local number example for UK 0044170911XXXX1 Local The phone numbers must be entered starting with an area code in the following format area code local number e...

Page 19: ...urther configuration please complete the steps provided in 6 1 RING TIP Interface To set the communicator to transmit data using this communication method please proceed as follows 1 On alarm panel En...

Page 20: ...achine running EGR100 Kronos SIA IP based software Kronos and SIA IP based soft ware require communicates via TCP port while EGR100 supports both TCP and UDP UDP is highly recommended for EGR100 in or...

Page 21: ...nsmit the next data messages by primary connection g If the device ends up with all unsuccessful attempts by all connections it will return to the primary connection When Advanced KissOff mode is enab...

Page 22: ...ion Backup 1 and Backup 2 connections can be set under this section 6 On ET083 Open Messaging Settings section and proceed as follows a Set up to 5 user phone numbers that will be permitted to receive...

Page 23: ...Test Period For SIA IP protocol please enable Contact ID Ping parameter and change the CID event code by default 602 if required 8 On ET083 Open Events Log section to monitor the activity 9 On ET083...

Page 24: ...persists when testing with the maximum parameter value of 15 try decreasing the value by value of 1 2 until a successful Kissoff signal is achieved To manage Microphone Gain and Speaker Level paramet...

Page 25: ...Value wwww 4 digit default SMS password ssss 4 digit new SMS password range 0001 9999 Example 0000_PSW 1111 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool...

Page 26: ...ontent ssss_Zn OFF Value ssss 4 digit SMS password n input number range 1 3 Example 1111_Z1 OFF Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software By...

Page 27: ...s Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Set Account for input alarm restore data reports Config Tool This operation may be carried out f...

Page 28: ...sing the ELDES Configuration Tool software View output names SMS SMS text message content ssss_STATUS Value ssss 4 digit SMS password Example 1111_STATUS Config Tool This operation may be carried out...

Page 29: ...t state 14 3 Output Control by Event The device comes equipped with output control by event feature allowing to to assign a certain output to operate based on a specific event occur rence in the devic...

Page 30: ...please refer to 13 INPUTS Ethernet Data Link Lost The output action will be carried out in case the Ethernet connection is lost For more details on Ethernet connection supervision please refer to 18 P...

Page 31: ...value by default 20 seconds the communicator will turn the specified output ON and OFF by default output C1 respectively followed by if enabled notification to the listed user phone number see 12 USER...

Page 32: ...link restored Ethernet data link lost and Ethernet data link restored In addition the device supports data link test periodically reported to the specified listed user phone number by SMS text messag...

Page 33: ...TIP interface of ET083 until the 2G 3G network registration is successful or data link is restored 2 When Data Link Test Enabled located under System Data Link Test tab parameter is disabled while Ad...

Page 34: ...owing configuration method Manage periodic test data report Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Set Account for periodic test data rep...

Page 35: ...can be found at the manufacturer s website eldesalarms com 24 2 Restoring Default Parameters 1 Unplug the USB cable 2 Power down the device 3 Short circuit connect the DEF pins 4 Power up the device...

Page 36: ...o preserve the configuration and notify by SMS text message once the update process has been completed or if it has failed The firmware file MUST be stored in a folder titled Firmware In order to init...

Page 37: ...37 EN ET083 2G 3G COMMUNICATOR V1 0 25 RELATED PRODUCTS Plastic enclosure Power supply ESR100 digital receiver...

Page 38: ...Made in the European Union eldesalarms com...

Reviews: