GB DIP-804/00 /2
3
IGNITION KEY
TWIN-FUNCTION INDICATORS
ENGINE PROTECTIONS
- REST
- MANUAL STOP
- RESET PROTECTION
- DEVICE SUPPLY
- START ENGINE
0
AUT.
START
These are on when the key is turned to "AUT".
They switch off when the engine is running and
the oil pressure and battery recharger are
regular.
The engine protections are enabled when the ENGINE PROTECTIONS ACTIVE
indicator is
on (20 seconds after turning the key to "AUT" or, in any case 20 seconds after the end of the start
impulse).
The interventions of the protection probes (mounted on the engine), shown by the relevant visual
indicators, stop the engine and can be divided into two groups:
These are enabled after the PROTECTIONS
ACTIVE indicator
switches on, and they
switch on when the relevant anomaly is
detected.
- OIL AND BATTERY INDICATORS
- ANOMALY INDICATORS
After a 3 second delay for:
Immediately for:
- OIL PRESSURE SWITCH
- OVERHEATING THERMOSTAT
- BATTERY CHARGE ALTERNATOR
(ALTERNATOR BELT BREAKAGE)
MAIN ALARM
This is obtained in three ways:
By turning the ignition key to zero
Because of protections intervention
-
-
The protection device uses two different types of stoppage:
- activating the ELECTROMAGNET which pulled the STOP lever for 20 seconds
- disconnecting the supply to the SOLENOID which closes the gasoline passage.
Enabled when the ignition key is turned to "AUT", without stopping the engine.
This can be obtained by mounting a visual and/or acoustic indicator externally connected to the
relevant output.
This is continuously activated if the protections or fuel reserve alarm intervene.
RESET: This is obtained by turning the ignition key to zero.
(MOUNTED EXTERNALLY)
STOPPING
ALARM
(FUEL RESERVE
)
FUNCTIONING