ELCOS CIM250/10 Instruction And User'S Manual Download Page 6

CIM-250/10 - EN

6

The pump protection is enabled with the switching on of the ACTIVE PUMP PROTECTION (after 2

consecutive

minutes of stable water pressure, indicated by the visual signal REGULAR PUMP PRESSURE

and, in any

case, 10 minutes after the start of the motor pump).

The intervention of the protection (5 seconds after the increase or decrease of the pressure) stops the engine and
is indicated by the visual signal for

LOW PUMP WATER PRESSURE

or

WATER PUMP OVERPRESSURE

.

The control unit shuts down the engine in four conditions:
- turning the starter key onto "ZERO”
- protection intervention
- timer intervention at the end of the work period
- through intervention of the external emergency.
The unit adapts to two different stop systems
- by working the ELECTROMAGNET for 20 seconds which pulls the STOP lever
- by cutting off power to the SOLENOID VALVE shutting off the flow of fuel.

It can be obtained in all functioning conditions, mounting one or more release-type buttons. It is indicated by the
visual signal

and enables the general alarm.

This can be obtained by fitting on the outside an optical and/or acoustic signaller to be connected to the RED/GREEN
wire. It is activated on protection intervention.

!

The control unit comprises six instruments:

INSTRUMENTS WHICH CAN BE SELECTED IN SEQUENCE BY PRESSING THE BUTTON

HOUR METER - Total hours of operation (with the engine running the signal

pulsates, to

indicate the correct functioning of the HOUR-METER).

Each time it is pressed, IT SHOWS the next instrument. WHEN THE TIMER IS set, the duration of the display of
the instrument is limited to 30 seconds from the activating of the button; the TIMER then reappears.

h

- PRESSURE GAUGE - Engine oil pressure
- THERMOMETER - Engine oil and water temperature

TRANSMITTERS FITTED ON ENGINE
ON REQUEST

bar

C

RMP
BAR

%

}

RESET: is obtained by turning the start key onto "ZERO".

OPERATION

PUMP PROTECTION

STOPPING THE ENGINE PUMP

GENERAL ALARM

EMERGENCY STOP

INSTRUMENT SELECTION

- INDICATOR

- Fuel level percentage

- PRESSURE GAUGE - Pump water pressure

- TACHOMETER

- Speed of motor pump

CONTROLLING THE CONNECTION OF THE PUMP WATER

ELECTRONIC PRESSURE GAUGE (Transmitter)

Turning the key to the AUT position stops the electronic pressure gauge.

Control is activated 1 minute after the completion of the starting pulse.

Intervention is highlighted by the relevant indicators

flashing warning light

and stops the motor pump after 2 seconds.

To exclude intervention, press the push-button

PUMP PROTECTION EXCLUSION.

DISCONN'ED

Summary of Contents for CIM250/10

Page 1: ...panel the functions of hour meter oil pressure gauge water or oil thermometer tachometer pump water pressure gauge timer fuel level gauge pump protection exclusion battery and oil lights protections...

Page 2: ...PRESSURE CUMULATIVE ALARM STOP BAR PRESS UNTIL THE 2 SIGNS START FLASHING TO EXCLUDE PUMP PROTECTION TO RE ACTIVATE PROTECTION PRESS AGAIN UNTIL THEY SWITCH OFF PUMP PROTECTION IS ACTIVE WATER PRESSUR...

Page 3: ...e indicated by the relevant lights stop the engine they are memorised and can be split into two groups Delayed by 2 seconds for Delayed by 5 seconds for A1 BATTERY CHARGE ALTERNATOR ALTERNATOR BELT BR...

Page 4: ...IN STOP MODE 85 30 86 87 SOLENOID t o c l o s e the fuel WARNING IT IS NOT POSSIBLE TO MOUNT THE EMERGENCY STOP BUTTON ON A STOP SYSTEM WITH ELECTRO MAGNETS YELLOW 85 30 86 87 2 7 TACHOMETER ADJUSTME...

Page 5: ...LPROBE 173 WATER PRESSURETRANSMITTER SUPPLIED 26 PERMANENTMAGNETS CHARGEALTERNATOR 27 BATTERYCHARGEALTERNATOR REGULATOR 28 PRE EXCITATION CHARGEALTERNATOR 40 STARTING MOTOR 41 BATTERY 157 GENERALALARM...

Page 6: ...e RED GREEN wire It is activated on protection intervention The control unit comprises six instruments INSTRUMENTS WHICH CAN BE SELECTED IN SEQUENCE BY PRESSING THE BUTTON HOUR METER Total hours of op...

Page 7: ...ABLE FOR OPERATING IN THE FOLLOWING CONDITIONS Where the environmental temperature is outside the limits indicated in the Technical Data on page 8 Where there are high levels or heat from radiation ca...

Page 8: ...5 Kg 3 2 Kg BATTERYVOLTAGE SUPPLY VOLTAGE SUPPLY 32V CIRCUITLOADING WITH KEY ATZERO MAX LOAD OFTHE OUTPUT STOPPING YELLOW STARTING MOTOR BLACK GENERALALARM RED GREEN AUXILIARY BROWN TEMPERATURE RANGE...