Product Description
AEROTOP T
6
Enclosure and Special Components
The enclosure consists of a frame that
is completely free of thermal bridging,
sound dampened, and specifically
developed for use with heat pumps.
The cladding and panels feature a
high-grade insulation to sound-dampen
and thermally insulate the unit.
A pedestal or base is not required
since the feet of the unit feature a
vibration-dampening design.
All panels can be detached for easy
access to the internal elements of the
unit and for control or configuration
tasks.
The high-performance radial fan
ensures the unit runs efficiently and
quietly.
The high performance cooling circuit
is mounted on a vibration-dampened
support and features a thermostatic
expansion valve, filter dryer, inspection
glass, high-pressure pressure controller
with manual reset, and a low-pressure
pressure controller with automatic
reset function. The hermetic scroll
compressor is mounted on a double
vibration-dampened support.
The evaporator consists of a large-area
finned tube heat exchanger made from
aluminum and copper; the condenser
consists of a welded chromium steel
high performance plate heat ex-
changer. The environmentally friendly
refrigerant R407C is used as the
working medium. A flow monitor on
the consumer side ensures trouble-free
cooling for reversible heat pumps.
Operating the heat pump is prohibited if
the following conditions exist:
•
Construction drying
•
System/unit used in unfinished
buildings
•
Windows or exterior doors
unfinished and locked.
These cases require the use of a
specific construction heating system.
Functional heating or surface-ready
heating with the heat pump acc. to
DIN EN 1264 is only permitted when
complying with these conditions.
Furthermore, it must be noted that the
design of the heat pump concerning
its standard operation may not yield the
full extent of the required heat output.
The following notes must be observed
as well:
•
Comply with the corresponding
standards and rules of the floor/
screed
manufacturer!
•
Proper function is only ensured
with a correctly installed system
(hydraulics, electrical, settings)!
Deviations may damage the floor/
screed!
Brief Description of the LOGON B
WP61 Controller
Plain text display unit, control and
protection of the cooling circuit, defrost
logic, malfunction display and dia-
gnostics, control of a sliding or mixed
heating circuit, service water heating,
storage tank charging, control of the
electrical auxiliary heater, expandable
for several mixed heating circuits.
LPB system bus with up to 15 heating
circuits per segment, bivalent operation
with additional heat generator (oil/gas),
cascade of several HPs. cooling
function, improved solar function
(heating support, pool, PWH), pool
function, controlling the multi-phase
electrical heating elements.
Selectable Connections
The connections for heater flow and
return, condensate drain, and electrical
connections can be placed on the left
or right side during the on-site installa-
tion and even directed towards the
bottom when installed outdoors.