elco AEROTOP T User Manual Download Page 45

 

 

Technical Data  
 
  
 
AEROTOP T07RX-T10RX  

45 

Heat pump type AEROTOP T..RX 

T07RX

 

T10RX

 

Heating operation 

  

 

For 

A2/W35 

Heating Capacity 

Qh 

kW 

6.4 9.1 

Power input 

Pel 

kW 

2 2.8 

Performance number EN14511 

COP 

3.3 3.3 

Cooling operation 

  

for 

A35/W18 

Cooling Capacity 

 

kW 

6.7 

9.7 

Power input 

 

kW 

2.6 

3.7 

Condenser 

 

 

  

Scroll hermetically 

Maximum current consumption 

Imax 

17.3 23.5 

Start-up current with smooth starter 

VSA 

40 40 

Current intensity with blocked rotor 

LRA 

76 114 

Current connection 

  

V-f-Hz 

230-1-50 

Fuse WP 

 

A/T 

20 20 

Fuse WP with electrical insert: 2 kW 

 

A/T 

32 40 

Fuse WP with electrical insert: 4 kW 

 

A/T 

40 50 

Fuse WP with electrical insert: 6 kW 

 

A/T 

50 63 

Condenser, heater side 

 

 

  

Material: Chrome steel AISI 304, 1.4301 

Hydraulic connections  

IG 

R" 

1” 1” 

Water content incl. connection hoses AEROTOP T 

 

2.6 3 

Volume stream heating operation nom/min 

1

)  

l/h 

1500/568 2100/835 

Pressure loss heating operation 

 

kPa 

28.3/4.4 

32.9/4.1 

Minimum volume stream cooling operation (

t= 5 K) 

 

l/h 

1'150 1'670 

Pressure loss cooling operation 

 

kPa 

17.4 16.1 

Max working pressure 

p baar 

3 3 

Evaporator/fan 

 

  

  

Volume stream 

 

m

3

/h 

2'500 3‘300 

Available pressure 

2)

  

Pa 

150 92 

Power consumption fan 

3)

 P 

kW 

0.035 0.100 

Maximum current consumption fan 

Imax 

1.6 1.6 

Coolant 

 - 

R407C 

Coolant filling AEROTOP TRX 

 

kg 

5 7.5 

Coolant circuit oil 

 

Ester Oil 

Oil quantity 

 

1.1 

1.36 

Weight heat pump 

 

kg 

207 

250 

Sound Level

 

3)

 Outdoor installation

 

 

 

 

Standard configuration 

4)

 

Lwa dB(A) 

62.0 65.3 

Sound Level

 

3)

  Indoor setup  

 

 

 

 

Sound power level  On suction 

Lwa 

dB(A) 

53.0 56.0 

                                 On exhaust  

Lwa 

dB(A) 

48.0 

                                 Inside 

Lwa 

dB(A) 

50.0 54.0 

53.0 

1)       Min: 

t max= 10 K, with PHW-preparation 

tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*

t[K]*

ρ

[kg/l])*3600) 

2) 

At maximum fan rotational speed.  

3) 

Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the dis-
tance; it describes the totality of   the sound power of the corresponding source radiating in all directions.  Information to determine 
the noise level see planning documents.  

4)       With Rain Guard

 

Summary of Contents for AEROTOP T

Page 1: ...User Manual For Authorized Service Technicians AEROTOP T Air Water Heat Pump with LOGON B WP61 12 2012 Art 420010520000...

Page 2: ...oise Dampers 20 Corner Installation 21 Cutout Insulation Installation 22 Parallel Setup with Rigid Duct 24 Parallel Setup with Rigid Duct with Noise Damper 25 General Duct Installation Information 26...

Page 3: ...Up to models AEROTOP T12C and AEROTOP T10CX the heat pumps are compact design with integrated buffer tank electrical resistance expansion vessel and circulation pump Single phase models X Up to modes...

Page 4: ...ctory values Failure to follow directions in the instructions for use The warranty for heat pumps for heating is 24 months from the date of delivery For the rest the condi tions of sale delivery and w...

Page 5: ...lly suited and provide a limited cooling effect Radiator heaters are unsuitable Cascade Thanks to the new heat pump controller LOGON B WP61 it is possible to link and operate several heat generators o...

Page 6: ...ruction drying System unit used in unfinished buildings Windows or exterior doors unfinished and locked These cases require the use of a specific construction heating system Functional heating or surf...

Page 7: ...te is very firm and can support the load The installation room must have at least one exterior wall Rooms with high humidity are unsuitable as installation locations for AEROTOP T heat pumps A condens...

Page 8: ...eration The system must be thoroughly flushed before connecting to the heat pump Residues in the heat pipes lead to damages on the heat exchangers und to malfunction of the heat pump Especially if the...

Page 9: ...components listed below An automatic cutout switch or a 3 phase slow blow fuse with neutral conductor must be provided externally in compliance with the technical requirements The low voltage cables...

Page 10: ...p sensor n B21 B71 Heat pump return temp sensor q B71 B91 Source intake temp sensor r B91 B84 Evaporator temp sensor s B84 B92 M19 Fan z UX N24 Flow monitor consumer P EX3 Q9 Condenser pump V Q9 Contr...

Page 11: ...ow temp sensor n B21 B71 Heat pump return temp sensor q B71 B91 Source intake temp sensor r B91 B84 Evaporator temp sensor s B84 B92 M19 Fan z AEROTOP T07 T16 U AEROTOP T20 T35 UX AEROTOP T07 T16 Q8 K...

Page 12: ...sor 1 f B81 B21 Heat pump flow temp sensor n B21 B71 Heat pump return temp sensor q B71 B91 Source intake temp sensor r B91 B84 Evaporator temp sensor s B84 B92 B83 Liquid refrigerant sensor B83 y BX5...

Page 13: ...Soft starter and rotary current relay Electrical Connection Switch box 1 2 3 4 5 6 7 8 Legenda 1 Terminal strip consumer power station blockage 2 Terminal strip Fan Contactor oil sump heater 3 Heat pu...

Page 14: ...fuse F3 8 Soft starter and rotary current relay 9 Fan Contactor 10 Electr heater element fuse F6 1 F6 2 F6 3 11 Compressor fuse Legenda 1 Terminal strip consumer power station blockage 2 Terminal str...

Page 15: ...ly 3 400V 5 Fan fuse control fuse 6 Soft starter and rotary current relay 7 Contactor electric heating element 1 9 4 5 6 7 2 3 8 Electrical Box AEROTOP T20R T35R with LOGON B WP61 1 Terminal block con...

Page 16: ...Use constructional measures to interrupt the flow of noise from the heat pump direct noise propagation Use solid walls fences palisades etc to reduce noise levels Plants however do not reduce noise Co...

Page 17: ...ization The heat pump and the entire system is controlled with the integrated LOGON B WP61 controller Please consult the system documentation for the correct parameter settings After the Initial Start...

Page 18: ...l support if you have any additional questions AEROTOP TC Heat Pump Integrated Thermal Mixing Valve The thermal mixing valve integrated into the compact heat pump routes a part of the flow water back...

Page 19: ...inished floors Statistics to be checked by customer If necessary wall must be reinforced with PUR insulation elements This must be considered for the cutouts The indicated cutouts apply only to the ac...

Page 20: ...igh Dimensions With Noise Dampers Dimensions Of Both Cutouts Without Insulation Minimal Dimensions Light Well a b c A C a2 c2 d2 e2 x a3 c3 a4 c4 T07C T07 995 1525 650 1570 1225 950 600 640 860 635 12...

Page 21: ...indicated on pages 19 and 20 the heat pump must push against the wall up to a distance of 40 mm with irregular walls the dis tance is reduced to 20 mm how ever the heat pump should in no way touch th...

Page 22: ...intake kit How to Install the Cutout Insulation Prepare insulating board Apply adhesive foam onto outside wall side of insulating board The wall side is the side where the leg of the metal section is...

Page 23: ...r screw per insulation element Steps Align in center of cutout insulation Drill hole diameter is 8 5 Wall opening is 4 cm Screw in star screws Installation of Mesh or Protective Grating The protective...

Page 24: ...ex sleeve A to inside frame of unit Attach sealing tape to sheet metal duct on the side that is attached to the sleeve Insert the sheet metal duct into the cutout The sheet metal duct may not touch th...

Page 25: ...IR IN must be considered separately AEROTOP T Rigid Duct Dimension Cutouts without Insulation Distance between Cutouts Partition Wall e1 c1 f1 a2 c2 d2 e2 k1 without partition wall k1 with partition w...

Page 26: ...idges No contact between masonry walls and airflow or air duct incl cover plate Correctly Establishing the Opening for the Air Duct through the Wall Prevent cooling of wall The duct must be pulled thr...

Page 27: ...tach oval duct plate 3 to intake box Attach round duct plate 4 to wall The plate must be centered over the cutout Attach duct 5 to duct plates Adjust duct length if needed Use a wire cutter to shorten...

Page 28: ...that the airflow is not blocked Attach oval duct plate 3 to air outlet panel Attach round duct plate 4 to wall The plate must be centered over the cutout Attach duct 5 to duct plates Adjust duct lengt...

Page 29: ...opening of the controller panel Then connect the ready to use cable to the controller unit The controller panel with integrated control unit is pressed into the slot opening 1 at the heat pump enclo...

Page 30: ...ng winds for example may cause an air short circuit The air intake must be protected from aggressive or corro sive substances such as ammonia chlorinated substances etc The AEROTOP T heat pump is very...

Page 31: ...ocal snow conditions as needed A conduit NW 250 must be installed between building and heat pump for the installation lines electrical hydraulic and condensate Setup Base Pedestal AEROTOP T a1 c1 h1 T...

Page 32: ...l panel We recommend routing the lines this way for the heat pump installed outdoors This involves pulling the heating lines condensate connection and the electrical cables through the opening 1 Water...

Page 33: ...1 1 4 5 3 2 Control unit 3 switch panel 1 control unit bracket and Plexiglas unit cover 2 are supplied with Heat pump in the case of outdoor installa tion 33 The control unit must be mounthed on a in...

Page 34: ...valves don t close A3 Heating or potable water circulation pump not running A4 Overflow valve missing or set incorrectly A5 Heating curve set too steep The module switches the particular unit to the s...

Page 35: ...in such cases 226 Winding protection compressor Affects contact E11 at the LOGON B WP61 A Phase interruption compressor gets hot B Phase reverse incorrect rotary field C Phase loss D Phase asymmetry...

Page 36: ...eck the functioning of the phase monitoring relay The green LED on the phase monitoring relay must be illuminated when there is no disablement by the utility company power station 3 Summer mode 12 PWW...

Page 37: ...h Check soft starter ampere and dip switches set correctly Check rotary field and grounding conductor Correct fuses Fuse protection force with all pole disconnecting circuit breaker installed External...

Page 38: ...circuit green range starts at approx 40 flow no bubbles visible Check noise sound of unit compressor turns over without excessive noise Check solid borne noise transmission flexible connection sound...

Page 39: ...4 804 19 0 1 268 49 0 421 10 0 4 574 20 0 1 218 50 0 407 9 0 4 358 21 0 1 170 8 0 4 152 22 0 1 125 7 0 3 958 23 0 1 081 6 0 3 774 24 0 1 040 5 0 3 600 25 0 1 000 4 0 3 435 26 0 962 3 0 3 279 27 0 926...

Page 40: ...e bar 3 3 3 3 3 Air Heat Exchanger Fan Volume flow m3 h 2 500 3 300 5 300 6 300 6 800 Available pressure 3 Pa 150 92 146 112 82 Power consumption fan kW 0 035 0 100 0 100 0 170 0 210 Max current consu...

Page 41: ...127 167 Current connection V f Hz 400 3 50 Fuse WP A T 32 40 40 40 Condenser heater side Material Chrome steel AISI 316 1 4401 Hydraulic connections IG Zoll 1 1 1 1 Water content incl connection hoses...

Page 42: ...ressure AEROTOP TC2 kPa 51 4 57 9 Max working pressure bar 3 3 Air Heat Exchanger Fan Volume flow m3 h 2 500 3 300 Available pressure 3 Pa 150 92 Power consumption fan kW 0 035 0 100 Rated current con...

Page 43: ...ream cooling operation t 5 K l h 1 150 1 670 2 050 3000 3050 Pressure loss cooling operation kPa 17 4 16 1 18 3 19 4 20 4 Max working pressure p baar 3 3 3 3 3 Evaporator fan Volume stream m3 h 2 500...

Page 44: ...70 5260 5970 6300 Pressure loss cooling operation kPa 14 20 6 14 8 21 8 Max working pressure p baar 10 10 10 10 Evaporator fan Volume stream m3 h 7 300 8 200 10000 11000 Available pressure 2 Pa 149 19...

Page 45: ...3 4 4 32 9 4 1 Minimum volume stream cooling operation t 5 K l h 1 150 1 670 Pressure loss cooling operation kPa 17 4 16 1 Max working pressure p baar 3 3 Evaporator fan Volume stream m3 h 2 500 3 30...

Page 46: ...ucts Air Water Heat Pumps Types EC DECLARATION OF CONFORMITY Address meet the following guidelines and directives EC Directives EC Pressure Equipment Directive EC Low Voltage Directive EC Electromagne...

Page 47: ...ng products Air Water Heat Pumps Types EC DECLARATION OF CONFORMITY Address meet the following guidelines and directives EC Directives EC Pressure Equipment Directive EC Low Voltage Directive EC Elect...

Page 48: ...ng products Air Water Heat Pumps Types EC DECLARATION OF CONFORMITY Address meet the following guidelines and directives EC Directives EC Pressure Equipment Directive EC Low Voltage Directive EC Elect...

Page 49: ...ng products Air Water Heat Pumps Types EC DECLARATION OF CONFORMITY Address meet the following guidelines and directives EC Directives EC Pressure Equipment Directive EC Low Voltage Directive EC Elect...

Page 50: ...ng products Air Water Heat Pumps Types EC DECLARATION OF CONFORMITY Address meet the following guidelines and directives EC Directives EC Pressure Equipment Directive EC Low Voltage Directive EC Elect...

Page 51: ...Notes 51...

Page 52: ...Notes 52...

Page 53: ...Notes 53...

Page 54: ...D 64546 M rfelden Walldorf ELCO Austria GmbH A 2544 Leobersdorf ELCOTHERM AG CH 7324 Vilters ELCO Rendamax B V NL 1410 AB Naarden ELCO Belgium n v s a B 1070 Anderlecht ELCO Italia S p A I 31023 Resan...

Reviews: