Indoor Installation
Corner Installation
21
Installation Notes
-
Insulate cutout with the self-
adhesive insulation elements (2).
The elements are cut to fit the
size of the cutout opening. The
width (400 mm) can be adjusted
to match the wall thickness.
Use a sharp knife to cut the
elements to size. The installation
of the cutout insulation boards is
described in detail below.
-
Attaching the compression belt
(1) around the outer frame of the
enclosure at air intake and outlet.
Important
: The belt must be
attached all the way around the
entire frame without any gaps.
-
As indicated on pages 19 and 20,
the heat pump must push against
the wall up to a distance of 40
mm - with irregular walls the dis
tance is reduced to 20 mm, how
ever, the heat pump should in no
way touch the wall.
Make sure there are no uninsu-
lated wall areas within the airflow
path (thermal bridge). If this is the
case, e.g. if the cutout was in-
correctly done, this wall area
must be insulated separately.
-
Mount air intake cover grating (3)
on exterior wall. Select either a
mesh or protective grating.
Additional noise dampers SI and
SO must be integrated for
AEROTOP T20 to T35!
The defrosting sensor must be posi-
tioned in the airflow. Never place the
sensor in between the plates of the
evaporator.
2
1
3
3
2
1
AEROTOP T20-T35 (optional for AEROTOP T16)
AEROTOP T07-T35