Performances in cooling 

 

 

 

AEROTOP L 79 

 

 

To 

Tae 

Cooling capacity EN14511 

EER EN14511 

 

 

 

 

C° 

C° 

100%  90%  80%  70%  60%  50%  40%  30%  100%  90%  80%  70%  60%  50%  40%  30% 

10 

88,7  80,9  72,5  62,5  52,3  43,1  33,2  29,2  5,57  5,64  5,77  5,89  5,95  5,94  5,85  5,81 

15 

85,8  78,2  70,0  60,3  50,3  41,3  31,5  27,7  4,89  4,98  5,11  5,24  5,34  5,36  5,32  5,29 

25 

80,0  72,8  65,0  55,8  46,2  37,6  28,2  24,7  3,85  3,94  4,07  4,21  4,33  4,38  4,38  4,36 

35 

74,0  67,2  59,9  51,1  42,0  33,8  24,8  21,6  2,96  3,02  3,11  3,21  3,27  3,27  3,19  3,16 

45 

67,7  61,5  54,7  46,4  37,8  30,0  21,5  18,6  2,24  2,27  2,32  2,36  2,35  2,30  2,35  2,38 

10 

93,8  85,5  76,6  66,1  55,2  45,5  34,9  30,7  5,80  5,90  6,04  6,20  6,27  6,27  6,16  6,13 

15 

90,8  82,7  74,0  63,7  53,1  43,5  33,1  29,1  5,10  5,21  5,35  5,52  5,62  5,65  5,60  5,57 

25 

84,8  77,1  68,9  59,0  48,8  39,7  29,6  25,9  4,03  4,13  4,27  4,43  4,56  4,61  4,61  4,59 

35 

78,4  71,4  63,6  54,3  44,5  35,8  26,2  22,8  3,10  3,17  3,27  3,38  3,45  3,45  3,36  3,33 

45 

72,1  65,5  58,2  49,4  40,2  32,0  22,8  19,7  2,36  2,40  2,45  2,50  2,50  2,44  2,49  2,51 

10 

10 

102  92,6  83,0  71,5  59,7  49,1  37,5  33,0  6,00  6,12  6,29  6,46  6,54  6,51  6,36  6,30 

15 

98,6  89,8  80,4  69,1  57,5  47,1  35,7  31,3  5,42  5,55  5,74  5,93  6,08  6,12  6,07  6,04 

25 

92,3  84,0  75,0  64,2  53,0  43,0  32,0  28,0  4,30  4,42  4,59  4,77  4,92  5,00  4,99  4,97 

35 

85,7  77,9  69,5  59,2  48,6  39,0  28,4  24,7  3,33  3,42  3,53  3,65  3,74  3,75  3,65  3,61 

45 

79,0  71,8  63,9  54,3  44,2  35,0  24,8  21,4  2,55  2,60  2,66  2,72  2,73  2,66  2,71  2,73 

15 

10 

116  106  94,7  81,6  68,0  55,8  42,4  37,2  6,57  6,78  7,05  7,32  7,49  7,52  7,38  7,31 

15 

113  103  91,9  79,0  65,6  53,6  40,4  35,4  5,97  6,18  6,44  6,73  6,96  7,06  7,03  7,00 

25 

106  96,5  86,2  73,7  60,8  49,2  36,4  31,8  4,80  4,97  5,18  5,43  5,64  5,76  5,78  5,76 

35 

99,0  90,1  80,3  68,4  56,1  44,9  32,6  28,3  3,77  3,88  4,03  4,19  4,31  4,34  4,25  4,20 

45 

91,9  83,6  74,5  63,3  51,5  40,8  28,8  24,8  2,92  2,99  3,08  3,15  3,18  3,12  3,18  3,20 

18 

10 

125  114  102  88,2  73,4  60,1  45,6  39,0  6,95  7,23  7,56  7,93  8,18  8,28  8,16  8,06 

15 

122  111  99,5  85,5  70,9  57,9  43,5  37,1  6,34  6,60  6,93  7,30  7,60  7,76  7,77  7,72 

25 

115  105  93,6  80,1  66,0  53,3  39,4  33,4  5,14  5,35  5,61  5,91  6,17  6,33  6,38  6,35 

35 

108  95,1  87,6  74,7  61,1  49,0  35,5  29,8  4,02  4,10  4,29  4,46  4,65  4,78  4,70  4,62 

45 

101  91,6  81,6  69,4  56,5  44,8  31,6  26,2  3,19  3,27  3,37  3,47  3,51  3,46  3,54  3,44 

20 

10 

132  120  108  92,8  77,2  63,2  47,9  41,0  7,23  7,56  7,94  8,38  8,71  8,86  8,78  8,67 

15 

128  117  105  90,1  74,7  60,9  45,7  39,0  6,61  6,92  7,29  7,72  8,09  8,30  8,36  8,31 

25 

121  111  98,9  84,6  69,7  56,3  41,5  35,1  5,40  5,63  5,93  6,28  6,58  6,78  6,87  6,84 

35 

114  104  92,8  79,1  64,8  51,8  37,5  31,5  4,30  4,46  4,66  4,89  5,06  5,13  5,06  4,98 

45 

107  97,3  86,8  73,8  60,1  47,6  33,6  27,9  3,39  3,49  3,60  3,72  3,77  3,72  3,82  3,71 

To [°C]=  Leaving internal exchanger water temperature  

Tae [°C]= External exchanger return air temperature 

Performances in function of the return/flow water temperature differential = 5°C  

Cooling capacity and EER calculated according to EN 14511:2018 

Summary of Contents for AEROTOP L

Page 1: ...PLANNER MANUAL Commercial Heat Pump AEROTOP L 07 2021 Art Nr 420011195500 www elco net en...

Page 2: ......

Page 3: ...mination and glycol 16 Overload and control device 16 Operating ranges heating cooling 17 Admissible water flow rates 18 Internal exchanger pressure drop 18 Hydronic assembly Unit with 1 Inverter pump...

Page 4: ...l the main system components are integrated in the unit assu ring the best reliability and an easy installa tion Hydronic assembly with 1 inverter pump Wide operating range Outdoor air temperature max...

Page 5: ...ene EPP antifreeze heater to protect the wa ter side exchanger preventing the formation of frost if the water tem perature falls below a set value flow switch anti ice probe External exchanger c coil...

Page 6: ...w flammability class A2L accord ing to ISO 817 low combustion speed low toxicity The refrigerant quantity is indicated on the unit plate Quantity factory loaded refrigerant and equivalent CO2 tons Phy...

Page 7: ...nned coil protection grill The grilles protect the external coil from accidental contact with objects or persons Ideal for installation in places where persons can pass from such as car parks terraces...

Page 8: ...l keypad 4 Power input 5 Water return 2 Victaulic 6 Water flow 2 Victaulic 7 Pump 8 Functional spaces In modular configuration the water input and output are 4 Victaulic 54 61 Lenght mm 2337 2337 Dept...

Page 9: ...Height mm 2155 2155 2155 Operating weight kg 780 780 780 Shipping weight kg 796 796 796 1 Compressor compartment 2 Electrical panel 3 Control keypad 4 Power input 5 Water return 2 Victaulic 6 Water f...

Page 10: ...ROLL INVERTER Standard power supply 400 3 50 N Maximum inrush current I max 46 46 60 2 60 2 60 2 Sound pressure level dB A 65 65 66 67 67 SCOP W35 4 04 4 03 4 08 4 07 4 06 6 min Buffer dimensioning L...

Page 11: ...d heating capacity and power input in compliance with EN 14511 2013 2 Entering leaving water temperature user side 40 45 C Entering external exchanger air temperature 7 C R H 85 3 Entering leaving wat...

Page 12: ...9 0 9 0 9 Water circuit Maximum water side pressure Mpa 1 1 1 1 1 Minimum circuit water volume in heating l 400 400 620 620 620 2 Minimum circuit water volume in cooling l 150 150 200 200 200 3 Total...

Page 13: ...sually provided by a buffer storage tank In solidly built houses especially in connection with underfloor heating blocking periods can be bridged by the storage mass A buffer tank or second heat gener...

Page 14: ...73 80 73 65 51 62 81 79 59 67 69 72 80 73 65 51 65 84 88 87 77 76 76 79 68 60 53 67 85 AEROTOP L Sound power level Sound pressure level Sound power level Octave band Hz 63 125 250 500 1000 2000 4000 8...

Page 15: ...0 0 950 0 950 Total power input factor Nr 0 950 0 950 0 950 0 950 0 950 COP factor Nr 1 000 1 000 1 000 1 000 1 000 Performance correction factors Silenced Mode Performance correction factors Super Si...

Page 16: ...0 98 The cooling performance values provided in the tables are based on the external exchanger having clean plates fouling fac tor 1 For different fouling factor values multiply the performance by the...

Page 17: ...ROTOP L 65 88kW Outdoor air temperature Tae C Flow temperature Twu C Operating Limits The diagrams on the left show the operating limits of the AEROTOP L heat pumps The temperature differ ence at the...

Page 18: ...mesh mechanical filter that must be placed on the water input line It is a device compulsory for the correct unit operation and it is provided by ELCO as accesso ry Admissible water flow rates Min Qm...

Page 19: ...equirements by setting the inverter frequency The pump will always work at fixed flow Water fittings are Victaulic type by 2 Pump available pressure AEROTOP L 54 61 kW Caution in order to obtain usefu...

Page 20: ...ull load current A 1 90 1 90 2 50 2 50 2 50 F L I Full load power input kW 0 75 0 75 1 1 1 1 1 1 Caution in order to obtain useful head values the head represented in these diagrams must be lowered by...

Page 21: ...63 3 55 5 47 9 38 8 29 5 27 3 5 00 5 01 5 11 5 17 5 16 5 05 4 80 4 70 40 10 11 1 35 4 32 3 28 8 24 6 20 8 16 5 12 8 11 8 2 56 2 44 2 39 2 32 2 25 2 12 2 01 1 91 7 8 38 6 35 6 32 0 27 4 23 3 18 8 14 4...

Page 22: ...1 46 6 41 3 36 8 32 0 25 8 20 0 18 2 2 53 2 58 2 67 2 70 2 68 2 59 2 40 2 37 15 10 84 2 75 4 67 1 60 3 53 1 44 2 35 9 33 3 7 50 7 78 8 23 8 51 8 72 8 89 9 00 9 09 15 81 3 72 7 64 7 58 1 51 1 42 4 34...

Page 23: ...4 65 4 78 4 89 5 04 5 15 5 17 5 09 4 91 40 10 11 1 43 7 38 8 35 3 31 5 27 4 23 0 18 2 14 1 2 66 2 56 2 48 2 43 2 37 2 29 2 19 2 06 7 8 46 9 42 1 38 6 34 8 30 4 25 7 20 4 15 9 2 78 2 71 2 65 2 62 2 58...

Page 24: ...7 6 51 1 45 5 40 2 34 8 28 9 22 4 18 2 2 37 2 49 2 61 2 68 2 70 2 65 2 49 2 37 15 10 93 2 82 6 73 6 65 5 57 4 48 7 39 4 33 3 6 91 7 37 7 88 8 30 8 61 8 80 8 93 9 09 15 90 0 79 7 71 0 63 1 55 2 46 8 37...

Page 25: ...33 5 39 5 34 5 33 5 54 5 45 40 10 11 1 50 8 44 2 42 8 39 2 34 3 29 5 24 5 20 2 2 32 2 45 2 49 2 49 2 46 2 45 2 56 2 56 7 8 55 7 48 3 46 7 42 7 37 2 31 8 26 3 21 5 2 56 2 70 2 74 2 75 2 70 2 68 2 79 2...

Page 26: ...6 57 3 48 6 39 7 30 8 24 9 20 7 2 60 2 64 2 71 2 73 2 70 2 61 2 63 2 75 15 10 108 98 4 85 7 73 9 62 0 50 1 42 1 36 2 6 75 6 96 7 26 7 43 7 53 7 49 7 38 7 70 15 105 95 6 83 0 71 5 59 7 48 0 40 2 34 4 6...

Page 27: ...93 0 85 8 77 6 67 7 55 8 42 2 4 81 4 97 5 13 5 29 5 39 5 35 5 37 5 55 40 10 11 1 55 6 51 2 47 9 44 1 40 0 35 1 29 4 22 9 2 32 2 37 2 43 2 48 2 50 2 46 2 47 2 57 7 8 60 8 56 0 52 3 48 2 43 5 38 1 31 7...

Page 28: ...4 2 35 0 24 8 21 4 2 55 2 60 2 66 2 72 2 73 2 66 2 71 2 73 15 10 116 106 94 7 81 6 68 0 55 8 42 4 37 2 6 57 6 78 7 05 7 32 7 49 7 52 7 38 7 31 15 113 103 91 9 79 0 65 6 53 6 40 4 35 4 5 97 6 18 6 44 6...

Page 29: ...8 4 90 8 82 7 72 2 59 3 45 9 4 79 4 90 5 02 5 19 5 35 5 40 5 23 5 52 40 10 11 1 60 6 55 5 50 8 46 7 42 5 37 3 31 0 24 6 2 27 2 33 2 40 2 45 2 49 2 49 2 40 2 55 7 8 66 3 60 7 55 5 51 0 46 4 40 5 33 6 2...

Page 30: ...5 22 9 2 43 2 52 2 61 2 69 2 74 2 70 2 56 2 69 15 10 126 115 101 89 5 76 7 61 8 47 2 39 3 6 19 6 52 6 85 7 19 7 45 7 53 7 45 7 34 15 122 112 98 1 86 8 74 2 59 5 45 1 37 4 5 61 5 92 6 25 6 58 6 87 7 0...

Page 31: ...s Protect the unit with a suitable fence in order to avoid access to unauthor ised personnel children vandals etc A correct circulation of the air is man datory to guarantee the good unit operating Av...

Page 32: ...s Option AEROTOP L 54 61 65 88 support points Configuration standard standard KIT PE PESM00003 PESM00005 W1 odice PAF 11 SPEC PAF 9 SPEC W2 PAF 11 SPEC PAF 22 SPEC W3 PAF 11 SPEC PAF 4 SPEC W4 PAF 11...

Page 33: ...only with a suitable water flow Each section must then be washed separately Particular atten tion must also be paid to blind spots where a lot of dirt can accumulate due to the reduced water flow The...

Page 34: ...0 7mm max diameter Ferrite hydroxide Fe3O4 black Dose 7 5 mg L 50 of mass with diameter 10 m Iron oxide Fe2O3 red Dose 7 5mg L Diameter 1 m Minimum capacity of the ex changer The minimum water flow is...

Page 35: ...r 3 water temperature probe 4 drain 5 water flow switch 6 vent 7 system loading safety pressure switch 8 Pump 9 pressure relief valve 10 NA 11 shut off valves 12 filter 13 flexible couplings 14 piping...

Page 36: ...IV Shut off valve NRV Non return valve EV Expansion valve Additional documents with hydraulic diagrams circuit diagrams and pa rameter lists for controller settings are available for the following sy...

Page 37: ...separator magnetic filter LLH Low Loss Header PHE Plate Heat Exchanger This schematic is for general guidance and is not to be considered a construction drawing Additional documents with hydraulic dia...

Page 38: ...guidance and is not to be considered a construction drawing Additional documents with hydraulic diagrams circuit diagrams and pa rameter lists for controller settings are available for the following s...

Page 39: ...ansion valve This schematic is for general guidance and is not to be considered a construction drawing Additional documents with hydraulic diagrams circuit diagrams and pa rameter lists for controller...

Page 40: ...System configurations Electric connection Heat Cool Remote On Off Anti snow function Antifreeze heater Signals Domestic hot water...

Page 41: ...nds function from HMI HMI and BMS Modbus ports are equipped with status LED for Rx Tx visual monitoring Wide range AC DC power supply in put compliance From 7 17Vac Vdc Port Definition HMI side CN1 A...

Page 42: ...an be repaired while the system continues to be in operation Handling and simplified installation the compact dimensions of an individ ual module make it easy to pass through doors and elevators The V...

Page 43: ...equal to 30 0 5 mm Every module is identified by a specific address Complete system management is car ried out by the master unit identified by the address 0 Thermoregulation takes place on the supply...

Page 44: ...m If the system is satisfied unit off When the temperature probe T5 sup plied by ELCO and positioned inside the storage calls for production of DHW the unit dedicated to DHW activates changing the set...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Service www elco net UK Importer ELCO HEATING SOLUTION LIMITED 3 Juniper West Fenton Way Basildon SS15 6SJ ELCO GmbH Hohenzollernstra e 31 D 72379 Hechingen...

Reviews: