Technical data
Fouling and glycol use correction factors,
overload and control device
Overload and control device calibrations
The value entered refers to units supplied with a hydronic group installed on board
Refrigerant side
Open
Close
Value
High pressure safety switch
kPa
4200
3200
-
Low pressure safety switch
kPa
50
130
-
Low pressure safety valve
kPa
-
-
3000
Compressor discharge high temperature safety thermostat
C°
115
75
-
Water side
Antifreeze protection
C°
4
20
-
High pressure safety valve
kPa
-
-
600*
Fouling correction factors
Internal exchanger
m²K/W
F1
FK1
0,44x10(-4)
-
-
0,88x10(-4)
0,96
0,99
1,76x10(-4)
0,93
0,98
The cooling performance values provided in the tables are based on the external exchanger having clean plates (fouling fac-
tor 1). For different fouling factor values, multiply the performance by the coefficients shown in the table.
F1 = Cooling capacity correction factors
FK1 = Compressor power input correction factor
Correction factors for Glycol use
% ethylene glycol by weight
Freezing point
°C
0
-4
-9
-16
-23
-37
Correction factor for unit cooling capacity
Nr
1
0,984
0,973
0,965
0,96
0,95
Correction factor for flow rate
Nr
1
1,019
1,051
1,092
1,145
1,2
Correction factor for system pressure drop
Nr
1
1,118
1,268
1,482
1,791
2,1
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchang-
ers in the water circuit during inactivity in winter.