Technical data
Sound levels
Performance correction factors
At maximum conditions data
AEROTOP L
Sound power level
Sound
pressurelevel
Sound
power level
Octave band (Hz)
63
125
250
500
1000 2000 4000 8000
dB(A)
dB(A)
54
55
65
67
72
77
70
61
50
67
83
61
55
65
67
72
77
70
61
50
67
83
65
57
67
69
73
79
72
64
51
69
85
79
57
67
69
73
79
72
64
51
69
85
88
57
67
69
73
79
72
64
51
69
85
AEROTOP L
54
61
65
79
88
Cooling capacity factor
Nr
0,930
0,930
0,930
0,930
0,930
Total power input factor
Nr
1,000
1,000
1,000
1,000
1,000
EER factor
Nr
0,930
0,930
0,930
0,930
0,930
Heating capacity factor
Nr
0,950
0,950
0,950
0,950
0,950
Total power input factor
Nr
0,950
0,950
0,950
0,950
0,950
COP factor
Nr
1,000
1,000
1,000
1,000
1,000
Performance correction factors- Silenced Mode
Performance correction factors - Super Silenced Mode
AEROTOP L
54
61
65
79
88
Cooling capacity factor
Nr
0,880
0,880
0,880
0,880
0,880
Total power input factor
Nr
1,020
1,020
1,020
1,020
1,020
EER factor
Nr
0,860
0,860
0,860
0,860
0,860
Heating capacity factor
Nr
0,900
0,900
0,900
0,900
0,900
Total power input factor
Nr
0,900
0,900
0,900
0,900
0,900
COP factor
Nr
1,000
1,000
1,000
1,000
1,000
Sound levels refer to units with maximum test conditions. The sound pressure level refers to a distance of 1 meter from the
outer surface of the unit operating in open field. Noise levels are determined using the tensiometric method (UNI EN ISO
9614-2)