background image

28

Adjusting Instructions

Start-up of Burner Control System Type BCS 300
Flame Detecting System Type FLW 05

Description
The electronic burner control system 
type BCS 300 is a programmable auto-
matic firing controller of modular con-
struction with integrated electronic 
compound controller. It is designed for 
the control and automatic control of oil, 
gas and dual-fuel burners of medium to 
larger outputs.
The automatic firing controller may be 
used for intermittent or continuous 
mode of operation and for furnace 
systems built according to TRD.
The controller consists of the following 
units that communicate via a safety-ori-
ented bus system:
-

burner controller module type 
BCS 300 (attached to burner)

-

flame detector module type BCS-
FLW 05 (attached to burner)

-

fuel and air servomotors

-

operating and display unit type 
BAM (not required for operation of 
furnace system)

The system also incorporates a PID 
firing rate controller with standard or 
servo-control parameterization capabi-
lity and a valve leak tester.

Technical data:

Operating voltage:

230  V a.c.

Frequency:

50-60 Hz

Power input:

BCS incl. BAM:<15 VA
FLW 05:

<1.5 VA

Back-up fuse:

max. 10 AF

Equipment fuse:

6.3 A slow-blow
0.1 A slow-blow

Permissible ambient temperature:

in operation:

0-60 °C

during storage:

-20-70 °C

Starting the burner control system

NOTE: The burner control system is 
allowed to be started by duly qualified 
specialists only. The personnel opera-
ting the system should strictly observe 
the applicable instructions for start-up.

Before proceeding with the pro-
gramming of the system make a check 
of its wiring (especially for compliance 
with the relevant DIN-VDE standards 
and the regulations of the local power 
supply company).

The parameterization of the automatic 
firing controller programs, the valve leak 
test and the firing rate adjustment will 
be handled from the operating and dis-
play module. 

NOTE: For selecting the automatic con-
troller programs and adjusting the pre-
ventilation times care should be taken to 
observe the applicable standards.
The fixed safety time settings are not 
allowed to be extended by external swit-
ching operations.

The fuel-air compound curves may be 
programmed by means of the operating 
and control module or a laptop compu-
ter.
If the compound controller is adjusted 
by means of the operating and display 
module it will only be possible to correct 
the curve point settings.
A completely new curve and the defini-
tion of new curve points can be achie-
ved with the aid of a laptop computer 
only.

After the automatic controller programs 
have been set it will be possible to 
check the inputs and outputs of the bur-
ner control system for proper 
functioning via the operating and dis-
play module.

NOTE: For the tests, all manual fuel 
shut-off valves must be kept in closed 
position in any case.

The compound modules are provided 
with a basic curve when delivered ex 
works. This may be changed by means 
of the operating and control module to 
adjust it to the local conditions. For this 
purpose, it is possible to correct the 
damper positions for the 10 index points 
in the range from 10, 20, 30, etc. to 100.

Flame detecting system
The flame detector module type FLW 05 
is used in conjunction with the burner 
control system.
The following flame sensors may be 
connected to the flame detector 
module:
-

QRA  2

-

QRA 53/55

-

RAR 7/8

-

ionization electrode

-

any flame detector with contact 
output

The sensor to be used will be selected 
by appropriate programming in the bur-
ner control system. The type of sensor 
used will depend on the burner opera-
ting mode (continuous or intermittent).
The flame boosters integrated in the 
flame detector will be checked for pro-
per operation at an interval of 90 
seconds in continuous mode. 
Flame detectors with contact output 
must if run in continuous mode be intrin-
sically safe because only the parts of 
the BCS flame detector are checked for 
safe operation.

The intensity of the flame signals (UV 
sensor, light sensor, ionization elec-
trode) is evaluated in the burner control 
system and indicated on the operating 
and display module.
This allows an exact orientation of the 
flame sensors.
It is not possible to measure the flame 
intensity by means of instruments.

The flame sensors must be checked for 
accumulation of dirt at regular intervals. 
Take care that the sensor window is 
kept free of dust all the time.
The flame intensity display may be used 
as an indicator for the dirt accumulation 
load. 
If the situation cannot be remedied by 
cleaning it will be necessary to replace 
the flame sensor.

Summary of Contents for 6.170 L-E

Page 1: ...Operation Manual for the authorized specialist Oil Burner EK 6 7 8 9 L E 03 2005 102 880 2006...

Page 2: ...6 22 Start up Nozzle Selection Type W2 50 23 Start up Return Nozzle Rod RDG 1250 Burner EK 7 EK 9 24 Nozzle selection Sonic 25 Checking Procedure 26 Adjusting Instructions Elektronic Burner Control w...

Page 3: ...in rooms containing aggressive vapours e g spray perchloroethylene hydro carbon tetrachloride solvent etc or tending to heavy dust formation or high air humidity Adequate ventilation must be provided...

Page 4: ...est values according to EN 267 DIN 4787 at 171 m above sea level Pressure in combustion chamber mbar 6 170 L E 501 1800 kW 42 152 kg h fully modulating Light oil EL BCS LAL 2 LOK 16 QRB 3 RAR 7 400 69...

Page 5: ...st values according to EN 267 DIN 4787 at 171 m above sea level Pressure in combustion chamber mbar 6 240 L E 681 2500 kW 57 210 kg h fully modulating Light oil EL BCS LAL 2 LOK 16 QRB 3 RAR 7 400 690...

Page 6: ...at 171 m above sea level Pressure in combustion chamber mbar 7 350 L E 1115 4500 kW 94 380 kg h fully modulating Light oil EL BCS LAL 2 2 LOK 16 QRB 3 RAR 7 400 690 V 50 Hz 5 5 kW 11 7 A 2800 min KL T...

Page 7: ...267 DIN 4787 at 171 m above sea level Pressure in combustion chamber mbar 8 550 L E 2000 6049 kW 168 510 kg h fully modulating Light oil EL BCS LAL 2 2 LOK 16 QRB 3 RAR 7 400 690 V 50 Hz 11 kW 22 5 A...

Page 8: ...4787 at 171 m above sea level Pressure in combustion chamber mbar 9 850 L E 2574 9596 kW 217 809 kg h fully modulating Light oil EL BCS LAL 2 2 LOK 16 QRB 3 RAR 7 400 690 V 50 Hz 18 5 kW 35 A 2800 mi...

Page 9: ...9 Overview Dimensioned Drawings EK 6 L E EK 6 170 200 L E Dimensions in boiler connection plate EK 6 240 300 L E Dimensions in boiler connection plate...

Page 10: ...10 Overview Dimensioned Drawings EK 7 8 L E EK 7 350 450 L E Dimensions in boiler connection plate Type EK 8 550 700 L E Dimensions in boiler connection plate Type...

Page 11: ...11 Overview Dimensioned Drawings EK 9 L E EK 9 850 1000 L E Dimensions in boiler connection plate Type...

Page 12: ...ition of the oil control valve and air damper and thus adjust the oil flow rate in relation to the air flow rate The stepless control will allow the bur ner to be operated at any desired stage between...

Page 13: ...e load will be controlled at any point within the control range depending on the heat demand The two stage sli ding and the stepless control concepts are different only in the control systems used wit...

Page 14: ...grated in pump 311 Return oil pressure switch 312 Feed oil pressure switch 349 Actuator In case of TRD 604 72 hr control items pos 311 312 need to be tested according to special construc tion design o...

Page 15: ...against torsion and a control shaft As the con trol shaft is turned the contoured confi guration of the bush and shaft will change the open cross section for the oil flowing back and thus vary the oil...

Page 16: ...16 Start up Burner Head Settings EK 6 L R E EK 6 170 L R E EK 6 200 L R E EK 6 240 L R E EK 6 300 L R E...

Page 17: ...17 Start up Burner Head Settings EK 7 8 L R E EK 7 350 L R E EK 7 450 L R E EK 8 550 L R E EK 8 550 L R E EK 8 700 L R E...

Page 18: ...18 Start up Burner Head Settings EK 9 L R E EK 9 850 L R E EK 9 1000 L R E...

Page 19: ...the installation materials termi nals and earth connections must be carried out in accordance with the appli cable regulations For the electrical installation of the burner care must be taken to obser...

Page 20: ...ructions The space between the flame tube of the burner D and the boiler lining D1 must be packed with heat resistant material e g Cerafelt This space is not allowed to be lined with brickwork Burner...

Page 21: ...gau ges are mounted to remain on the bur ner they should be fitted with stop valves Oil pressure control feed The feed pressure is controlled by means of the pressure regulator instal led in the pump...

Page 22: ...DWH WR YDU EHFDXVH WKH QHHGOH SRVLWLRQ KDV DQ LPSDFW RQ WKH RLO UHWXUQ IORZ 5HWXUQ QR OH URG W SH 5 1 6WURNH DGMXVWHU FRQWURO QHHGOH GUDXOLF SLVWRQ V VWHP 2LO UHWXUQ FRQQHFWLRQ 2LO VXSSO FRQQHFWLRQ 5H...

Page 23: ...shows the maximum throughput rates of the return nozzles in dependence of the supply oil pressure Supply oil pressure min 20 bar max 30 bar Nominal supply oil pressure 28 bar Return oil pressure min 8...

Page 24: ...ure would keep the slider open Under normal circum stances both locking mechanisms would open at the same time The oil in the forward flow section would exit through the nozzle head to be mixed with t...

Page 25: ...1000 60 with controlled return Light fuel Oil Feed pressure 28bar Return nozzles of the type Sonic Spray are available in different ratings with an angle of spray of 45 60 or 80 The 45 nozzles are pr...

Page 26: ...ional test of the burner program flow Oil system Open all shut off valves of the oil sup ply system The oil solenoid valve in the feed line disconnect on the terminal strip see Circuit Diagram Start b...

Page 27: ...fer to the documentation supplied with the electronic compound control system for the pre operational work on the burner the checking requirements e g actuators limit switches potentio meters etc and...

Page 28: ...grammed by means of the operating and control module or a laptop compu ter If the compound controller is adjusted by means of the operating and display module it will only be possible to correct the c...

Page 29: ...ND 5 AA MA 6 AB MB NOTE Check the zero position of the servomotors prior to start up Technical documentation BCS 300 Dungs Technical data Maximum torque 15 Nm Gear reduction 745 1 Positioning times at...

Page 30: ...nnec tion with the electronic burner control systems of the firm Lamtec Technical data Voltage 230V AC Frequency 50 Hz Angle of rotation 90 Running time 40 sec for 90 Torque 15 Nm Static holding momen...

Page 31: ...ker attached to the housing side wall Functional test without burner start After the electronic compound controller has been connected electrically pro ceed with adjusting the potentiometers of the ac...

Page 32: ...cc to DIN EN in pumps without quick action stop valve DSF 146 F 0 10 bar 0 5 2 5 bar Return line acc to TRD 604 72h DSB 158 F 3 25 bar 1 0 4 3 bar Feed line acc to TRD 604 72h Air pressure switch The...

Page 33: ...al between voltage on terminal 19 and terminal 20 interval between valve 2 and controller enable t6 After flushing time t7 Interval between start command and voltage on terminal 7 t11 Air damper opera...

Page 34: ...3 flame sensor is mounted to burners with intermittent mode of operation which are shut down within 24 hours Application Burners operated in continuous or inter mittent mode for periods in excess of...

Page 35: ...ped thread Item 3 to act as a forcing screw Tighten this bolt to force off of the bush Remove the loosened disk unit by hand without hammer blows and taking care not to damage it Mounting the fan impe...

Page 36: ...tests Fuel throughput rate adjustment Heating chamber temperature intake temperature Exhaust gas temperature Pressure in combustion chamber and exhaust gas pipe CO2 and O2 contents of exhaust gases C...

Page 37: ...12 97 0 40 15 11 3 40 12 89 0 50 15 03 3 50 12 82 0 60 14 96 3 60 12 75 0 70 14 88 3 70 12 67 0 80 14 81 3 80 12 60 0 90 14 74 3 90 12 53 1 00 14 66 4 00 12 45 1 10 14 59 4 10 12 38 1 20 14 52 4 20 12...

Page 38: ...electrodes Cracked insulator Replace insulator Defective igni tion transformer Replace transformer Defective auto matic furnace controller Replace controller Burnt ignition cable Replace cable search...

Page 39: ...ause Remedy Dirty flame sen sor Clean flame sensor Burner fails to start Check connection of automatic fur nace controller Trouble lamp lights flame trouble Unlock and search for cause Weak flame sen...

Page 40: ...to stop The symbol shown above the reading of the indicator will identify the type of trouble No start e g because the CLOSED signal from the limit change over switch Z or auxiliary switch M is not a...

Page 41: ...illing line 10 Limit transmitter 11 Vent line 12 Pump unit 13 Pressure holding valvel Stepless control with supply pump and ring line system Stepless control direct intake 1 Burner blower 2 Oil filter...

Page 42: ...42...

Page 43: ...43 Customer Service ELCO GmbH D 64546 M rfelden Walldorf ELCO Austria GmbH A 2544 Leobersdorf ELCOTHERM AG CH 7324 Vilters ELCO Rendamax B V NL 1410 AB Naarden ELCO Belgium n v s a B 1731 Zellik...

Reviews: