Detector 3000 

Seite 7 / 11 

Stand: 29.8.19 GB 

 

 

 

  AC: AC symbol is on 

  +DC: DC symbol is on 

  -DC: - symbol and DC symbol is on 

 

  Above 120V, the polarity is shown on the LED display as well.  

  AC: both 120V LEDs are on 

  +DC: left 120V LED is on 

  -DC: right 120V LED is on 

 

  Once when tester is power on, it will automatically measure voltage in range 6V-

1000VAC/1500VDC. 

  When the L2 probe + is the positive (negative) potential, the Polarity indication LED 

indicates “+DC” (“-DC”).  

  During voltage test, L or R LED/Symbol may light up. 

  In case of empty batteries, only the ELV LED lights up >50V  

 

 

7.1.1.

 

Low

 

Voltage mode – 1V-1000VAC/1500VDC  

 

  Press 

On/off

/Function button repeated until LCD shows 

<10V

 symbol  

  In Low Voltage mode it is possible to measure AC and DC voltage from 1V. 

  Connect both probes to the object under test. 

  Voltage display is as in 7.1 descriped 

 

  Continuity mode is disabled in Low Voltage Mode. 

 

7.2. Current test 

  Press 

On/off

 /Function button repeated until LCD shows 

A

 symbol  

  In current test mode, currents between 0.1A and 200A can be tested 

  Cable needs to be positioned in center of the opening at the height of the markings left and 

right. 

  Make sure that only double insulated cables are measured 

  Store test probes safely to avoid any unintended connection  

  Tester switch to voltage measurement if voltage is detected during continuity testing >6V 

 

7.3. Single-pole phase test

  

  Function of this test may not be fully achieved if the insulation condition/ grounding 

conditions of user or of the equipment under test aren’t good enough. Verification of live-

circuit shouldn’t be dependent on this Single-pole phase test only, but on the voltage test.  

 

  Hold the tester good in your hand. Connect the “L2 +” probe to the object under test.  

Live circuit LED lights up and buzzer sounds when a voltage of approx. 100V AC or more    

exist

s in the object under test. (Pol≥100VAC)

.  

  Indication of Single Pole is via LED  

 

7.4.

 

Phase rotation test 

 

  L LED (symbol) and R LED (symbol) for Phase rotation test may operate on various wiring 

systems, but effective testing result can be obtained only on three-phase 4-wire system.  

  Hold the tester good in your hand and connect both probes to the object under test.  

  Phase-to-phase voltage is indicated by Voltage LEDs and LCD 

  R LED lights up for Right rotary field  

  L LED lights up for Left rotary field  

Summary of Contents for 980 255 909

Page 1: ...Detector 3000 Seite 0 11 Stand 29 8 19 GB CAT III 1000V CAT IV 600V EN 61326 1 IEC 61243 3 2014 EN Manual DETECtOR 3000 universaltester lectrotesteur elettrotester electrical tester...

Page 2: ...9 8 19 GB 1 Opening for current measurement 2 Test leads on back side 3 LED display 4 LCD display 5 On off and function button 6 Torchlight and hold button 7 Battery compartment 8 Sensor for cable bre...

Page 3: ...or in instruction manual Warning of a potential danger comply with instruction manual Reference Please pay utmost attention Caution Dangerous voltage Danger of electrical shock Continuous double or re...

Page 4: ...e and reliable working It complies with the standard for two pole voltage testers EN61243 3 2014 The Detector 3000 is characterized by the following features Designed to meet international safety stan...

Page 5: ...cted to be disconnected of the installation it is highly recommended confirming by another means e g use of an adequate voltage tester visual check of the disconnecting point of the electric circuit e...

Page 6: ...g transport leaking batteries The tester complies with all EMC regulations Nevertheless it can happen in rare cases that electric devices are disturbed by the electrical field of the tester or the tes...

Page 7: ...for tests 6 1 Auto power on switching on The tester switches on when it detects shorten tips or an AC or DC voltage above approx 6V or a live phase on L2 single pole test It can be switched on with a...

Page 8: ...n center of the opening at the height of the markings left and right Make sure that only double insulated cables are measured Store test probes safely to avoid any unintended connection Tester switch...

Page 9: ...y LED lights up buzzer sounds continuously and Con symbol on LCD is on if L1 tip is connected on Anode of diode and L2 tip on Cathode Continuity indication will be off if L1 tip is connected on Cathod...

Page 10: ...s before shortening tips 7 12 HOLD Function Long press 2 seconds on torchlight function button activates HOLD function and freezes display value With short press on torchlight function button freezing...

Page 11: ...40 70Hz Safety current Is 3 5mA at 1000VAC Measurement Duty 30s ON operation time 690V 10s ON operation time 690V 240s OFF recovery time Internal battery consumption Approx 120mA Single pole phase tes...

Page 12: ...est points before cleaning Use a lightly damp cloth with neutral detergent for cleaning the instrument Do not use abrasives or solvents Do not expose the instrument to direct sun light high temperatur...

Reviews: