Elbro AG 980 255 909 Manual Download Page 11

 

Detector 3000 

Seite 10 / 11 

Stand: 29.8.19 GB 

 

9. Technical data 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Range 

1…1000V AC (16…800Hz), 

1…1500V DC(±) 

LED nominal 

Voltage 

120

/230/400/690/1000V 

LED tolerances 

EN61243-3 

ELV indication LED  >50VAC, >120VDC 
Response time 

<1s at 100% of each nominal 

value 

LCD Range 

1…1000V, AC (16…800Hz),  

1…1500V DC(±) 

LCD Resolution 

0.1V (1…29.9V),  

1V (30…1500V) 

LCD Accuracy 

±3%±1.5V (1…29.9V) 

±3%±3dgt (30…1500V) 

LCD Overrange 

indication 

“OL” 

Current Test 

0.1…200 A  AC(+/-3%+5Dgt) 

Resolution 0.1A 

 

Frequency range 40…70Hz 

Safety current 

Is<3.5mA (at 1000VAC)  

Measurement Duty 

30s ON (operation time 

<690V), 

10s ON ( operation time  

>690V),  

240s OFF (recovery time) 

Internal battery 

consumption 

Approx. 120mA 

Single-pole phase 

test voltage range 

100…1000V AC (50/60Hz ) 

Phase rotation test  170…1000V phase-to-phase, 

AC (40-70Hz) 

Continuity test 

0…5

00kΩ + 50%

 

Resistance 

measurement 

0…100k

Ω; accuracy: 

±5%±10dgt@25

o

C; 

resolution: 1

 

(1-2000Ω) 

                  1kΩ (2-100kΩ)

 

Frequency 

measurement 

1…800Hz ±5%±5dgt; 

resolution: 1Hz 

Battery 

3V (IEC LR03 1.5V x 2) 

Temperature 

-15…55°C operation; 

 -20…70°C storage;  

No condensation 

Humidity 

Max 85% RH 

Altitude 

up to 2000m 

Overvoltage 

CAT IV/690V CAT III/1000V 

Standard 

EN/IEC 61243-3:2014 

Protection 

IP64 

Summary of Contents for 980 255 909

Page 1: ...Detector 3000 Seite 0 11 Stand 29 8 19 GB CAT III 1000V CAT IV 600V EN 61326 1 IEC 61243 3 2014 EN Manual DETECtOR 3000 universaltester lectrotesteur elettrotester electrical tester...

Page 2: ...9 8 19 GB 1 Opening for current measurement 2 Test leads on back side 3 LED display 4 LCD display 5 On off and function button 6 Torchlight and hold button 7 Battery compartment 8 Sensor for cable bre...

Page 3: ...or in instruction manual Warning of a potential danger comply with instruction manual Reference Please pay utmost attention Caution Dangerous voltage Danger of electrical shock Continuous double or re...

Page 4: ...e and reliable working It complies with the standard for two pole voltage testers EN61243 3 2014 The Detector 3000 is characterized by the following features Designed to meet international safety stan...

Page 5: ...cted to be disconnected of the installation it is highly recommended confirming by another means e g use of an adequate voltage tester visual check of the disconnecting point of the electric circuit e...

Page 6: ...g transport leaking batteries The tester complies with all EMC regulations Nevertheless it can happen in rare cases that electric devices are disturbed by the electrical field of the tester or the tes...

Page 7: ...for tests 6 1 Auto power on switching on The tester switches on when it detects shorten tips or an AC or DC voltage above approx 6V or a live phase on L2 single pole test It can be switched on with a...

Page 8: ...n center of the opening at the height of the markings left and right Make sure that only double insulated cables are measured Store test probes safely to avoid any unintended connection Tester switch...

Page 9: ...y LED lights up buzzer sounds continuously and Con symbol on LCD is on if L1 tip is connected on Anode of diode and L2 tip on Cathode Continuity indication will be off if L1 tip is connected on Cathod...

Page 10: ...s before shortening tips 7 12 HOLD Function Long press 2 seconds on torchlight function button activates HOLD function and freezes display value With short press on torchlight function button freezing...

Page 11: ...40 70Hz Safety current Is 3 5mA at 1000VAC Measurement Duty 30s ON operation time 690V 10s ON operation time 690V 240s OFF recovery time Internal battery consumption Approx 120mA Single pole phase tes...

Page 12: ...est points before cleaning Use a lightly damp cloth with neutral detergent for cleaning the instrument Do not use abrasives or solvents Do not expose the instrument to direct sun light high temperatur...

Reviews: