background image

3

 

• *Device

 

 

• Devices list

 

• *Output Modules

 

 

• Outputs list

 

• *Bells

 

 

• Bells list

 

• Panel Outputs

 

 

• Zone 1-4 (TAREL24)

 

 

• AUX 1-2

  • 

Bell

  • 

Buzzer

 

• *Extinguishing Module

 

• *GSM

 

• *Repeater

• Events

• Devices

• Test

 

• Zones

 

 

• Zones list (0-44)

 

• Outputs

  • 

Bell

 

 

• Zone 1-4 (TAREL24)

  • 

Fault

 

 

• AUX 1-2

 

• *Loop Outputs

 

 

• Outputs list

 

• *Loop Bells

 

 

• Bells list

 

• Display

 

• LED

 

• Buzzer

• *GSM

• Display Contrast

• Programming

* menu pages that appear only if the corresponding mod-

ules are available.

For TA4000, loop module menu pages include another page 

for the selection of the loop.

6  

 MeNU  PAGes  BROWsiNG

The menu can be used to access several functions, divided 

in sub-menus as shown in section 5 

p. 2.

Press ↓ to go to next item, ↑ to go to previous item.

When icon ▼ appear, press ↓ while cursor is on the last item 

to go to next page.

When icon ▼ appear, press ↑ while cursor is on the first item 

to go to previous page.

•   Use ↑ and ↓ to select one item, press ENTER to enable/

disable it.

•   Press ESC to exit a menu or function page and go to pre-

vious menu.

7  

 LeVeL  2  MeNU

7.1    items  disablement

 Each function in this menu can exclude a different kind of 

element (zones, modules, outputs, single devices).

 Fault and alarm indications from the disabled elements will 

be ignored, excluded outputs won’t activate but the control 

panel will keep monitoring the presence of elements.

 An X at the right of functions indicates the presence of ex-

cluded elements.

7.1.1    Zone

The page displays the list of all conventional and ana-

logue-addressable zones with at least one device.

 

–  press ENTER to enable / disable zones selected

 Disabled zones are marked with an X on the right.

 Note:  if all analogue-addressable devices of a zone are dis-

abled, the control panel will disable the entire zone. 

If you enable a zone disabled in such way, all zone 

devices will be enabled again.

7.1.2    Device

The page displays the list of all devices self-learned on this 

loop (except output and bell modules).

 

–  press ENTER to disable / enable again selected devices.

 Disabled devices are marked with a X on the right.

Note:  item available only if at least one loop module has 

been installed.

7.1.3    Output  modules

The page displays the list of all addresses of self-learned 

output modules.

 

–  press ENTER to disable / enable again selected modules

 Disabled modules are marked with a X on the right.

Note:  item available only if at least one loop module has 

been installed.

7.1.4    Bells

The page displays the list of all bell modules self-learned.

 

–  press ENTER to disable / enable again selected modules

 Disabled modules are marked with a X on the right.

Note:  item available only if at least one loop module has 

been installed.

7.1.5    Panels  output

A list of all Zone (of an optional TAREL24 board), Aux, Bell 

and Buzzer outputs addresses.

 If EXTING extinguishing module is installed, Aux 2 output 

cannot be disabled and will not appear.

 

–  press ENTER to disable / enable again outputs selected

 Disabled outputs are marked with a X on the right.

 Note:  if you disable a Zone output, TAREL24 board relay out-

put and I/O terminals OC output with the corresponding 