YELLOW - fault/anomaly indication

RED - alarm/pre-alarm indication

White - setup indication

Fault (or alarm) indications include, at the bottom right, the 

number of the displayed fault (or alarm) and the total num-

ber of faults (or alarms) detected by the control panel.

Example: 001/003 = fault (or alarm) 1 of 3.

The alarmed display shows also, at the bottom left, the num-

ber of the last alarm occurred.

If alarms and faults occur simultaneously, the faults window 

will be hidden.

After 10 seconds in idle mode, the window with faults will 

hide.

4.1    LeD indicators meaning

LED name

Colour Indication

230V

Green 230V power ON

Silencing

Yellow Bells silenced

Pre-alarm

Red

Alarm + pre-alarm check in progress

Investigation

Yellow Acknowledgement / Investigation timer 

ongoing

Day/night

Yellow Day/night mode active

LED name

Colour ON

Blinking

Alarm

Red

Ongoing alarm events 

with silenced bell

Ongoing alarm 

events

GSM ON

Red

Telephone dialler ON Waiting for 

confirmation

Disablement

Yellow Some elements are 

disabled

Test

Yellow Some system 

elements are being 

tested

General fault

Yellow Ongoing fault events 

with silenced buzzer

Ongoing fault 

events

System fault

Yellow CPU fault with silenced 

buzzer

CPU fault 

Bells fault/disabled Yellow Bells disabled

BELLS fault

GSM fault/disabled Yellow GSM disabled

GSM fault

4.2    Buttons  function

Key

Name

Level 1 function

Level 2 function

Enter

---

Enters the selected menu.

Confirms data.

Up (↑)

Displays previous event.

Moves the selection upwards.

Changes a field value (hold it 

pressed for a faster effect).

Down (↓)

Displays the following event.

Moves the selection 

downwards.

Changes a field value (hold it 

pressed for a faster effect).

Escape (ESC)

In case of fault and alarm 

events, it displays fault events 

or goes back to alarm events.

Goes back to previous menu.

Cancels the operation.

Evacuate

During acknowledgement/

investigation (day mode), it 

resets delay timers and sets 

the panel to alarm condition.

Evacuation procedure: it 

generates the Evacuate 

event and sets the panel to 

alarm condition.

During acknowledgement/

investigation, see level 1.

Silencing

Silences the buzzer.

Silences/activates bells.

Switches from 

Acknowledgement to 

Investigation.

Reset

---

Reset procedure: it resets 

the panel when it is in alarm 

or fault condition.

Day/night

---

Enables/disables the day/

night mode.

5  

 MeNU  MAP

• Disablements

 

• Zone

 

 

• Zones list (0-44)