PRODUCT MAINTENANCE
06/2022
45
NP-DK50 3x4VR_M-AD-A-EN-3_06-2022
vessel. Tighten any loose terminals.
Inspect the connector and pressure sensor
B1 (on the air tank).
Checking the operating condition of the
AD dryer
Check the service indicator and alarms on
the display screen as specified in Chapter
0 and schedule service or repairs as
needed.
Only a service technician is permitted to
modify program parameters using the
cursor buttons on the LOGO! module and
only after a password is entered.
The operator may monitor the individual
values on the display but has no access to
the parameters of the program.
Indication of an upcoming or expired
service interval
Configuration of a new service interval
Press ESC + ► together and hold for 10
seconds to reset the service interval. Once
complete, the display returns back to the
home screen.
The SET UP function for a new service
interval is only functional if the dryer indicates
an upcoming service interval or that a service
interval has expired. Once complete, the
MAINT
counter
increases
(number
of
completed service operations) by one. See
the screen: Counters.
Information screens
– version AD750 E
Information
screens
are
activated
by
simultaneously pressing and holding down the
ESC key and cursor buttons.
ESC+◄- „COLUMNS TIMING“ screen
-
Information about the defined valve cycling
times
-
INLET_A(INLET_B)
– duration of the
adsorption phase (half-cycle) for chamber A
(chamber B)
-
PURGE_A(PURGE_B)
– duration of the
regeneration phase for chamber A (chamber
B)
ECS+▼ – „COUNTERS“ screen
-
Information about counters, the number of
times service has been performed and the
number of times the solenoid valves have
been activated
-
MAINT
– number of service operations
-
VALVE
– number of times the solenoid valves
have been activated (the number displayed
indicates the number of times the Inlet_A inlet
valve into chamber A has been activated)
-
Version
– software version
Summary of Contents for DK50 3x4VR/M
Page 1: ...DK50 3x4VR M User manual ...
Page 2: ......
Page 13: ...PRODUCT DESCRIPTION 06 2022 13 NP DK50 3x4VR_M AD A EN 3_06 2022 Fig 2 Adsorption dryer ...
Page 14: ...PRODUCT DESCRIPTION NP DK50 3x4VR_M AD A EN 3_06 2022 14 06 2022 Fig 3 Switchboard ...
Page 30: ...INSTALLATION NP DK50 3x4VR_M AD A EN 3_06 2022 30 06 2022 14 PNEUMATIC DIAGRAM DK50 3x4VR M ...
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......