10
3.11.1 Water drain for floor-standing ovens
The drain pipe is conveyed to an open (grilled) drain on the floor (Fig.1) and should not go into direct contact
with the discharge point: the "air gap" (distance between the drain pipe coming from the appliance and the
open drain) must be at least 25 mm.
Wall-mounted discharge is also allowed as long as the drain pipe maintains the steady gradient of 4-5%.
Fig.3
3.11.2 Water drain for tabletop ovens
The drain pipe can be conveyed to an open (grilled) floor drain (Fig.1); otherwise, between the drain pipe of
the appliance and the drain point with a "collection vessel" (Fig. 2), there must be a height difference of at
least 30 cm in order to facilitate the regular flow of water. In any case, the "air gap" (distance between the
drain pipe from the appliance and the open drain or the “collection vessel” of the drain duct pipe) must be
at least 25 mm.
Wall-mounted discharge is also allowed as long as the drain pipe maintains the steady gradient of 4-5%.
Fig. 4
Fig. 5