TROUBLESHOOTING 

 
 
 

S

YMPTOM

 

C

AUSE

 

R

EMEDY

 

Unit inoperative 

1.  No power to unit 

1.  Check the power from the 
power supply panel. 

Little or no airflow 

1. Loose fan on shaft 
2. Fan motor burnt out 
3. Dirty refrigeration coils 
4. Loose electrical wiring 

1. Tighten fan 
2. Replace the fan motor 
3. See 

Routine Maintenance

  

Section 
4. Check the wiring diagram 
to find fault and repair 

Little or no water 
extraction 

1. Insufficient air flow 
2. Compressor fault 
3. Loss of refrigerant gas 
4.  Blocked filter dryer 

1. Check all of the above 
2. Contact the Factory 
Service Center 
3. Contact the Factory 
Service Center 
4.  Contact the Factory 
Service Center 

Little or no defrost 
when required 

1.  Faulty Timer 
2.  Faulty bypass timer 

1.  Contact the Factory 
Service Center 
2.  Contact the Factory 
Service Center 

Unit vibrates 
excessively 

1.  Loose compressor 
mounts 
2.  Damaged fan 

1.  Tighten the nuts on the 
compressor mounts 
2. Replace fan 

Water flooding inside 
the machine 

1.  Drain pipe blocked/frozen 
2.  Drain pipe too high 

1.  Clear the obstruction 
2.  No section of the drainage 
hose should be above the 
level of the water outlet 

 
 
 

Spare parts available online 

 

www.EIPLDIRECT.com 

Summary of Contents for CD30S

Page 1: ...Page 1 of 12 Drawing TPC499 Issue 1 Date 29 01 20 CD30S INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...Page 2 of 12 Drawing TPC499 Issue 1 Date 29 01 20 CD30S PACKAGE CONTENTS Item Description Quantity 1142000 Dehumidifier 1 3014338 PVC tube 12mm I D 3 M 3086101 Jubilee clip 1 TPC449 Manual 1...

Page 3: ...point Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain The cooled air then passes through the hot condenser coil where it is rehe...

Page 4: ...he Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this u...

Page 5: ...d Leave the machine running for 15 minutes e Observe the evaporator coils to confirm frost formation i If the air temperature is below 70 F an even coating of frost should cover the entire evaporator...

Page 6: ...e 25 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all...

Page 7: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 8: ...oss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center 4 Contact the Factory Service Center Little or no defro...

Page 9: ...R Compressor 1 3944958 Refrigeration Coil Set 1 2139528 Fan Motor 1 3035773 Fan Blade 1 3040129 Timer Board 1 1619519 Humidistat 1 3035145 Humidistat Knob 1 3030421 Solenoid Coil 1 3020421 Defrost By...

Page 10: ...oto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R40...

Page 11: ...Page 11 of 12 Drawing TPC499 Issue 1 Date 29 01 20...

Page 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...

Reviews: