OPERATION 

3.1  THERMOSTAT SET POINTS AND HEATING/COOLING UNITS 

SETTING THE THERMOSTAT 

 

Your EIC air conditioner is equipped with an adjustable thermostat.  The set point you 

choose should be based on the desired internal temperature of the enclosure.  The air conditioner 
will run until the set point temperature is achieved within the enclosure and then the hot side fans 

and the thermoelectric cooling modules will shut down.  The cold side fan will continue to run, 

circulating the air to maintain a uniform temperature within the enclosure. 
HEATING AND COOLING UNITS 
 

If you purchased an HC unit (heating and cooling), the heater operation is controlled by a 

fixed-point thermostat.  This thermostat is set to turn the heaters on when the temperature within 
the enclosure falls to approximately 45

°

 F and turn the heaters off when the temperature rises to 

approximately 55

°

 F.   

 

The cooling operation is controlled by the adjustable thermostat.  To avoid having the 

heating and cooling on at the same time, do not set the cooling thermostat below 70

°

 F. 

 

3.2  MAINTENANCE 

MAINTENANCE 
 

EIC Thermoelectric Air Conditioners are virtually maintenance-free.  The only time 

maintenance is required is when a unit is installed in an extremely dirty environment.  In these 
cases, the hot side heat sinks (outside the enclosure) should be inspected regularly for a build-up 
of dust or dirt.  If a build-up is present on the heat sink fins, it can be easily removed as follows: 

 

1.

 

Disconnect the power from the unit.   

2.

 

Dry dust/dirt can be removed using compressed air to blow out the heat sinks.  Do not 
direct any high-pressure air at the fans.   

3.

 

NEMA 4X models of our air conditioners are designed to allow for water wash down of the 
hot side of the unit, which is outside of the enclosure 

(never the cold side which is inside 

the enclosure).

 

 A pressure washer can be used to carefully clean the hot side heat sink 

fins.  Never direct high-pressure water at the fans or the joint formed by the mounting 
flange, gasket and enclosure.  Never allow the cold side of your unit to get wet.  Always 
check your serial label before proceeding with a water wash down. 

 

Keeping the hot side heat sink fins free from any insulating build-up of dirt or dust will ensure 

long, trouble-free operation of your air conditioner. 

 

NEVER EXPOSE THE COLD SIDE OF ANY AIR CONDITIONER (INSIDE THE ENCLOSURE) TO 

WATER.

 

 

If you have any questions about any aspect of your EIC air conditioner, don’t hesitate to call us at 
the numbers listed below. 

 

 

Summary of Contents for ThermoTEC AAC-146 Series

Page 1: ...UTIONS INC 215 443 5190 EIC SOLUTIONS INC Thermoelectric Air conditioner installation and operation manual FOR 1000 Btu MODEL S AAC 146 4XT E AAC 146 4XT E HC AAC 146 XXXXX Cooling Solutions for Mission Critical Electronics ...

Page 2: ...ENCLOSURE 6 2 4 INSTALLING THE AIR CONDITIONER 6 INSTALL THE DRIP PAN 7 APPLY POWER 7 3 OPERATION 3 1 thermostat set points and heating cooling units 9 3 2 maintenance 9 4 APPENDIX 10 EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com D 20 Rev A 8 19 2015 ...

Page 3: ...Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outside without exposing your delicate electronics to any outside air or co...

Page 4: ...enclosure or horizontally on the top of your enclosure See Figure 2 1 and 2 2 Vertically mounted 1000 Btu units are always mounted with the exposed heatsink fins facing up and down never left and right Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP V depending on a number of factors including internal enclosure temperatures and ambient temperatures humidity l...

Page 5: ...LOSURE DP V DRIP PAN HOT SIDE FANS COLD SIDE FANS HOT SIDE HEAT SINKS COLD SIDE HEAT SINKS COLD SIDE HEAT SINKS HOT SIDE HEAT SINKS HORIZONTAL INSTALLATION OF 1000 BTU UNIT WITH INTERNALLY MOUNTED DP 146H DRIP PAN AND DRAIN TUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FANS HOT SIDE FANS COLD SIDE HEAT SINK FINS HOT SIDE HEAT SINKS HOT ...

Page 6: ... to Appendix B for narrow flange models only Air conditioners that are narrow flange units contain NF in the part number and the mounting flange measures 20 25 x 12 Refer to Appendix C for extension frame models 3 Before cutting or drilling check that the location meets the clearance requirements as specified in the installation manual 4 Using a pencil center punch or other method mark the exact c...

Page 7: ...pan to the air conditioner 4 Attach the supplied PVC drain tube to the hose fitting on the drip pan This tube should be routed to the bottom of the enclosure and fed through a 3 8 hole to the outside 5 If you purchased a horizontal drip pan it is installed at the factory and you will only need to install the hose fitting and PVC drain hose YOU MUST USE THE FACTORY INSTALLED HORIZONTAL DRIP PAN IF ...

Page 8: ...tioner Upon applying power to the air conditioner the fans on the cold side inside the enclosure will come on The hot side fans outside the enclosure may also run depending on where the thermostat is set The cold side fan always runs to circulate air within your enclosure thereby eliminating any hot spots The hot side fans will only run when the air conditioner is cooling they are pumping the heat...

Page 9: ...rtually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed us...

Page 10: ...DIX A and B Enclosure cutout for Standard Flange models only DO NOT use with Narrow Flange models or Extension Frame Drawing A Enclosure cutout for Narrow Flange models only DO NOT use with standard models or Extension Frame Drawing B Holes to be 8 32 TAP ...

Page 11: ...11 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX C Enclosure cutout for 1000 BTU air conditioner EXTENSION FRAME ONLY Holes to be 203 ...

Reviews: