EIC Solutions ThermoTEC AAC-146 Series Installation And Operation Manual Download Page 3

1

-800-497-4524                   EIC SOLUTIONS, INC

.

                       215-443-5190 

1.  GENERAL INFORMATION 

1.1 PRINCIPLES OF OPERATION 

n 1834 Jean Peltier discovered that by passing a current through two dissimilar conductors the 
junction of those materials will either absorb or release heat depending on the direction of the 

current flow.   Thirteen years earlier Thomas Seebeck had discovered that current would flow 
when you placed a temperature gradient across the junction of two dissimilar metals.  These 

two discoveries were the basis of thermoelectrics.  With the advent of modern semiconductors 

thermoelectric devices became practical for real world applications and are now found in 
everything from consumer goods to spacecraft.   

Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no 

compressor and no expensive, ozone depleting CFC’s.  EIC’s air conditioners use Thermoelectric 
“modules” sandwiched between high performance aluminum heat sinks, high CFM axial fans, and a 
patented electronic design to “pump” the heat from the inside of your enclosure to the outside, 
without exposing your delicate electronics to any outside air or contaminates.  See Figure 1.1.  

EIC uses only the highest quality components in our air conditioners and you can expect 

years of trouble free cooling from these solid-state devices.  Every unit we sell is backed by our 
one year parts and labor warranty. 

 

 

FIGURE 1.1 

AMBIENT AIR 

REMOVES HEAT 

FROM HOT SIDE 

HEAT SINKS

COLD AIR 

CIRCULATED 

WITHIN THE 

ENCLOSURE

HOT
SIDE

HEAT 
SINKS

COLD 

SIDE 

HEAT 
SINKS

COLD AIR 

CIRCULATED 

WITHIN THE 

ENCLOSURE

AMBIENT AIR 

REMOVES HEAT 

FROM HOT SIDE 

HEAT SINKS

HOT
SIDE

HEAT 
SINKS

COLD 

SIDE 

HEAT 
SINKS

FANS

FANS

Summary of Contents for ThermoTEC AAC-146 Series

Page 1: ...UTIONS INC 215 443 5190 EIC SOLUTIONS INC Thermoelectric Air conditioner installation and operation manual FOR 1000 Btu MODEL S AAC 146 4XT E AAC 146 4XT E HC AAC 146 XXXXX Cooling Solutions for Mission Critical Electronics ...

Page 2: ...ENCLOSURE 6 2 4 INSTALLING THE AIR CONDITIONER 6 INSTALL THE DRIP PAN 7 APPLY POWER 7 3 OPERATION 3 1 thermostat set points and heating cooling units 9 3 2 maintenance 9 4 APPENDIX 10 EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com D 20 Rev A 8 19 2015 ...

Page 3: ...Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outside without exposing your delicate electronics to any outside air or co...

Page 4: ...enclosure or horizontally on the top of your enclosure See Figure 2 1 and 2 2 Vertically mounted 1000 Btu units are always mounted with the exposed heatsink fins facing up and down never left and right Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP V depending on a number of factors including internal enclosure temperatures and ambient temperatures humidity l...

Page 5: ...LOSURE DP V DRIP PAN HOT SIDE FANS COLD SIDE FANS HOT SIDE HEAT SINKS COLD SIDE HEAT SINKS COLD SIDE HEAT SINKS HOT SIDE HEAT SINKS HORIZONTAL INSTALLATION OF 1000 BTU UNIT WITH INTERNALLY MOUNTED DP 146H DRIP PAN AND DRAIN TUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FANS HOT SIDE FANS COLD SIDE HEAT SINK FINS HOT SIDE HEAT SINKS HOT ...

Page 6: ... to Appendix B for narrow flange models only Air conditioners that are narrow flange units contain NF in the part number and the mounting flange measures 20 25 x 12 Refer to Appendix C for extension frame models 3 Before cutting or drilling check that the location meets the clearance requirements as specified in the installation manual 4 Using a pencil center punch or other method mark the exact c...

Page 7: ...pan to the air conditioner 4 Attach the supplied PVC drain tube to the hose fitting on the drip pan This tube should be routed to the bottom of the enclosure and fed through a 3 8 hole to the outside 5 If you purchased a horizontal drip pan it is installed at the factory and you will only need to install the hose fitting and PVC drain hose YOU MUST USE THE FACTORY INSTALLED HORIZONTAL DRIP PAN IF ...

Page 8: ...tioner Upon applying power to the air conditioner the fans on the cold side inside the enclosure will come on The hot side fans outside the enclosure may also run depending on where the thermostat is set The cold side fan always runs to circulate air within your enclosure thereby eliminating any hot spots The hot side fans will only run when the air conditioner is cooling they are pumping the heat...

Page 9: ...rtually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed us...

Page 10: ...DIX A and B Enclosure cutout for Standard Flange models only DO NOT use with Narrow Flange models or Extension Frame Drawing A Enclosure cutout for Narrow Flange models only DO NOT use with standard models or Extension Frame Drawing B Holes to be 8 32 TAP ...

Page 11: ...11 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX C Enclosure cutout for 1000 BTU air conditioner EXTENSION FRAME ONLY Holes to be 203 ...

Reviews: