background image

1.

Check room doors for heat or smoke.

Do not open a hot door. Use an
alternate escape route. Close doors
behind you as you leave.

2.

If smoke is heavy, crawl out, staying

close to floor. Take short breaths, if
possible, through a wet cloth or hold
your breath. More people die from
smoke inhalation than from flames.

3.

Get out as fast as you can. Do not

stop for packing. Have a prearranged
meeting place outside for all family
members. Check everybody is there.

4.

Call the Fire Brigade from a

neighbour’s house. Remember to give
your name and address.

5. NEVER

re-enter a burning house.

Limitations of Smoke / Heat Alarms

Smoke / Heat Alarms have significantly helped to reduce the
number of fire fatalities in countries where they are widely
installed.

However independent authorities have stated that they may
be ineffective in some circumstances. There are a number of
reasons for this:

• The Alarms will not work if the mains power is off and the battery

is depleted. On the Ei141/144/146 alarms the batteries should be
replaced every three years as a precaution or if the unit gives a
low battery beep.

• 

NOTE:

Constant exposure to high or low temperatures or

high humidity may reduce the life of the Alkaline battery.

• Smoke / Heat Alarms will not detect fire if sufficient smoke /

heat does not reach the alarm. Smoke / heat may be
prevented from reaching the Alarm if the fire is too far away,
for example, if the fire is on another floor, behind a closed
door, in a chimney, in a wall cavity, or if the prevailing air
draughts carry the smoke / heat away. Installing Smoke /
Heat Alarms on both sides of  closed doors and installing
more than one Smoke / Heat Alarm as recommended in the

INSTALLER INSTRUCTIONS

booklet significantly

improves the probability of early detection.

• The Alarm may not be heard.

• A Smoke / Heat Alarm may not wake a person who has

taken drugs or alcohol.

9

B16009-R0-160RC SERIES-U&C  17/1/07  11:13 AM  Page 8

Summary of Contents for B16009-R0-160RC Series

Page 1: ...E FROM THE BASE PLATE BY MOVING IT VERTICALLY DOWNWARDS TOWARDS THE FLOOR REMOVE ALARM LOCATE REMOVAL SLOT LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW...

Page 2: ...weekly press and hold the test button on the alarm for 10 seconds The alarm will sound loudly and the red light on the cover should flash rapidly All the other interconnected alarms should sound If a...

Page 3: ...it cannot be replaced on the base unless a battery is installed 7 Press and hold the test button horn should sound loudly 8 Reinstate mains power to alarm green light on cover should come on We recomm...

Page 4: ...een indicator light is extinguished Press the test button and ensure the horn sounds loudly for 10 seconds Turn on the mains supply at the distribution board only if the unit passes the above test Not...

Page 5: ...after test hush button has been pressed These two beeps should not be confused with low battery beeps A unit will operate from the mains alone even with a fully depleted or a defective battery and giv...

Page 6: ...n of smoke heat or noise to indicate that there is a fire you should get your family into a safe place before you start investigating Check the house carefully in case there is a small fire smoulderin...

Page 7: ...ion of cobwebs dust or grease If unit has been damaged in any way or does not function properly do not attempt a repair Return the Alarm see GETTINGYOUR ALARM SERVICED section on page 10 This applianc...

Page 8: ...er of reasons for this The Alarms will not work if the mains power is off and the battery is depleted On the Ei141 144 146 alarms the batteries should be replaced every three years as a precaution or...

Page 9: ...or replacement put it in a padded box and send it to Customer Assistance and Information at the nearest address given on the Alarm or in this leaflet Do not snap on to the mounting plate as this conne...

Page 10: ...y is correctly connected and the unit has beeped for over 20 minutes the battery is probably depleted Obtain a new battery disconnect the mains then remove the alarm and replace the depleted battery O...

Page 11: ...nal is transmitted to all units 2 One or more of the connections may not be correctly connected We recommend you consult a qualified electrician Aico Ltd Mile End Business Park Maesbury Rd Oswestry Sh...

Page 12: ...1 REGULAR CHECKS 230V SMOKE HEAT ALARMS USER INSTRUCTIONS Look for Constant green light Red light flash every 40 sec Press test button for 10 sec Alarm will sound loudly Vacuum around side vents to cl...

Reviews: