H. GROUND LUG REPLACEMENT:
• Referring to "FIGURE B", loosen the Ground Lug Screw and remove ground wire from the Lug.
• Remove Ground Lug Mounting Screw from the Mounting Plate.
• Replace Ground Lug@ with the appropriate one shown in "TABLE E".
• Torque Ground Lug Mounting Screw to 16-20 lb.- in. to fasten Ground Lug to Mounting Plate.
• Reconnect ground wire to Lug and tighten Lug Screw to 30-40 lb.- in. torque.
TABLE E
MD2SR INTERLOCKED RECEPTACLE REPLACEMENT PARTS
REFERENCE
PART
QUANTITY
NUMBER
AMPACITY
DESCRIPTION
NUMBER
PER
ASSEMBLY
1
30,60, 100
DISCONNECT
LAB10
1
SWIT CH
OPERATING
2
30, 60,100
HANDLE
59308352000
1
3
30, 60,100
SWIT CHING
59312769000
1
MECHANISM
4
30, 60
FUSE COVER
59351030000
1
ASSEMBLY
5
100
FUSE COVER
59351031000
1
ASSEMBLY
6
30
CLASS II RECEPTACLE
59312775000
1
ASSEMBLY
30 AMP; 2 WIRE, 3 POLE
7
30
CLASS II RECEPTACLE
59312766000
1
ASSEMBLY
30 AMP; 3 WIRE, 4 POLE
8
60
CLASS II RECEPTACLE
59312776000
1
ASSEMBLY
60 AMP; 2 WIRE, 3 POLE
9
60
CLASS II RECEPTACLE
59312767000
1
ASSEMBLY
60 AMP; 3 WIRE, 4 POLE
10
100
CLASS II RECEPTACLE
59312777000
1
ASSEMBLY
100 AMP; 2 WIRE, 3 POLE
11
100
CLASS II RECEPTACLE
59312768000
1
ASSEMBLY
100 AMP; 3 WIRE, 4 POLE
12
30,60, 100
GROUND LUG
59350996000
1
ASSEMBLIES
USED IN
MD2SR3034F
MD2SR6034F
MD2SR1034F
MD2SR1034U
MD2SR3034F
MD2SR6034F
MD2SR1034F
MD2SR1034U
MD2SR3034F
MD2SR6034F
MD2SR1034F
MD2SR1034U
MD2SR3034F
MD2SR6034F
MD2SR1034F
MD2SR3023F
MD2SR3023U
MD2SR3034F
MD2SR3034U
MD2SR6023F
MD2SR6023U
MD2SR6034F
MD2SR6034U
MD2SR1023F
MD2SR1023U
MD2SR1034F
MD2SR1034U
MD2SR3034F
MD2SR6034F
MD2SR1034F
MD2SR1034U
Rev. C 07/08/04
Page 9