APPLICATION: 

• Designed to supply three(3) phase,  grounded electrical power to portable or fixed electrical equipment such as welders,

infrared ovens,  batch feeders, conveyors and truck and marine docks.

• Designed to provide an interlocked receptacle for use in hazardous locations, as defined in the  National Electrical Code

(NEC).  In addition,  the receptacle is designed such that a mating plug can only be engaged and disengaged  when the 

switch handle is in the "OFF" position.

• Ideal for use on shipping docks,  ports,  and other "ship to shore" applications.

• Suitable for use in locations that require a degree of protection from the elements indoors and outdoors (NEMA Type  3R

&  12) for the receptacle  flip cover and  (NEMA  3,  3R,  4,  4X and  12) for the receptacle screw  cover.

• Enclosure cover is gasketted to seal cover against the enclosure housing.

• The receptacle face enables the engagement of mating plugs for a weatherproof union.

• MD2SR  Series  Interlocked  Receptacle may be pole mounted or installed on flat  vertical  surfaces.

TABLE B:  "ACP"  PLUGS FOR "MD2SR" RECEPTACLES 

RECEPTACLE 

SWITCH ASSEMBLY 

CAT. NO. 

CAT. NO. 

WRDK3023 

MD2SR3023F 

WRDK3023 

MD2SR3023U 

WRDK3034 

MD2SR3034F 

WRDK3034 

MD2SR3034U 

WRDK6023 

MD2SR6023F 

WRDK6023 

MD2SR6023U 

WRDK6034 

MD2SR6034F 

WRDK6034 

MD2SR6034U 

WRDK1023 

MD2SR1023F 

WRDK1023 

MD2SR1023U 

WRDK1034 

MD2SR1034F 

WRDK1034 

MD2SR1034U 

TABLE C: TIGHTENING 

TORQUE -

DISCONNECT SWITCH LUG 

SCREWS 

ACP 

PLUG 

WIRE SIZE 

(AWG) 

#8 

#4 -#6 

#4/0 - #3 

WARNING 

CURRENT 
RATING 

30 

30 

30 

30 

60 

60 

60 

60 

100 
100 

100 

100 

TORQUE 

(LB-IN) 

40 

45 

50 

Electrical power must be turned 

"OFF" 

before and 

during  installation and maintenance. 

Failure to do so may result in serious 

fatal 

injuries due to electrocution. 

WARNING 

Do not  modify  these devices  in any  way.  Replace 

any  missing  or broken parts  with the proper 

replacement  parts  from  Appleton Electric,  LLC. 

Modification  of these devices or substitution of 

parts with non-standard parts may  result in serious 

/ fatal personal  injury  from electrocution. 

Page 2 

Rev. C  07 /08/04 

APPLETON 
MATING  PLUGS 

ACP3023BC 

APJ3385 

ACP3023BC 

APJ3385 

ACP3034BC 

APJ3485 

ACP3034BC 

APJ3485 

ACP6023BC 

APJ6385 

ACP6023BC 

APJ6385 

ACP6034BC 

APJ6485 

ACP6034BC 

APJ6485 

ACP1023CD 

APJ10387 

ACP1023CD 

APJ10387 

ACP1034CD 

APJ10487 

ACP1034CD 

APJ10487 

TIGHTENING TORQUE 

FUSEHOLDER LUG 

SCREWS 

CROUSE-HINDS 

MATING  PLUGS 

NPJ3383 

NPJ3383 

NPJ3483 
NPJ3483 

NPJ6384 

NPJ6384 

NPJ6484 

NPJ6484 

NPJ10386 

NPJ10386 
NPJ10486 

NPJ10486 

WIRE SIZE 

(AWG) 

#10-#14 

#8 

#4 - #6 

#2/0 - #3 

WARNING 

NPJ3384 

NPJ3384 

NPJ3484 

NPJ3484 
NPJ6385 

NPJ6385 

NPJ6485 

NPJ6485 

NPJ10387 

NPJ10387 

NPJ10487 

NPJ10487 

TORQUE 

(LB-IN) 

35 

40 

45 

50 

The "MD2SR" receptacles are designed and tested 

for use with copper conductors only. 

DO NOT 

use aluminum wiring,  as dangerous 

overheating and fire may  result. 

WARNING 

If any parts of the "MD2SR" unit appear to  be 

missing,  broken or show signs of damage: 

DISCONTINUE USE IMMEDIATELY! 

This condition could cause serious / fatal personal 

injury due to electrocution and / or equipment damage. 

Repair  with the proper  replacement  part(s)  before 

continuing service. 

WARNING 

Not suitable for use as service equipment. 

Summary of Contents for Appleton MD2SR Series

Page 1: ...S VOLTS AMPERES 250 600 30 250 600 30 250 600 60 250 600 60 250 600 100 250 600 100 FIGURE A g H P RATING CATALOG SWITCH AC NUMBERS TYPE STANDARD MAX MD2SR3023F FUSED 7 5 20 MD2SR3034F MD2SR3023U NON...

Page 2: ...NG CURRENT RATING 30 30 30 30 60 60 60 60 100 100 100 100 TORQUE LB IN 40 45 50 Electrical power must be turned OFF before and during installation and maintenance Failure to do so may result in seriou...

Page 3: ...NTACT IDENTIFICATION MARKING TYP CLASS II INTERLOCKED RECEPTACLE ASSEMBLY POWERTITE COMPATIBLE FUSES SHOWN NOT INCLUDED WITH UNIT PADLOCK HOLE FUSE COVER CUT AWAY TO SHOW FUSE HOLDER ASSEMBLY VIEW WIT...

Page 4: ...OVED UNIT SHOW IS CAT NO MD2SR1034F ______ 16 7 42 3 CM CONDUIT ENTRY 0 3 0 7 6 CM 11 0 27 9 CM I CATALOG NUMBER DIMENSION A MD2SR3023F MD2SR3023U MD2SR3034F MD2SR3034U MD2SR6023F 19 3 MD2SR6023U 48 9...

Page 5: ...erring to FIGURE C loosen the housing Cover Bolts G but do not attempt to remove them completely from the Cover because they are designed to be captive B The Cover is now free to swing open on its fac...

Page 6: ...se Holder Use only sand filled non renewable Class J Fuses F Wire Guide allows wiring to be run from the top or bottom of the Enclosure to the opposite end of the Enclosure without interference with t...

Page 7: ...Housing Referring to FIGURE C loosen line side Lugs Screws of the Disconnect Switch and remove line side wires from the Switch On non fused units loosen load side Lug Screws J of the Disconnect Switch...

Page 8: ...rew Cover onto the Receptacle Housing until screw cover gasket is firmly seated against the receptacle housing face Replace the receptacle housing screw secure the free end of the Screw Cover chain to...

Page 9: ...BLY 5 100 FUSE COVER 59351031000 1 ASSEMBLY 6 30 CLASS II RECEPTACLE 59312775000 1 ASSEMBLY 30 AMP 2 WIRE 3 POLE 7 30 CLASS II RECEPTACLE 59312766000 1 ASSEMBLY 30 AMP 3 WIRE 4 POLE 8 60 CLASS II RECE...

Page 10: ...Clean interior of all foreign materials 6 Cover Bolts G must be tightened to 25 30 lb ft torque 7 Make sure the Receptacle Assembly Nameplate located on the outside of the cover remains clean and legi...