21
en
RS485 interface
Only for EGO Smart Heater type 29.6x335.0xx!
The EGO Smart Heater needs a own RS485 interface on the
control (remote station), for details see the control manual.
Cable crosssection: 0.2 1.5 mm²
*) shielding unilaterally contacted. Either on the EGO Smart Heater
or on the control (remote station)
even
Protocol
Modbus RTU Slave
1
RS485 interface:
Parity
Stop Bit
19200
Baud rate
LAN interface
Only for EGO Smart Heater type 29.6x335.1xx!
The EGO Smart Heater is connected with a router or a
corresponding remote station via a network cable.
The EGO Smart Heater has no fix IP address, therefore a
DHCP server is necessary for the allocation of the IPaddress.
It is recommended to allocate a fix IPaddress for the EGO
Smart Heater, which can be configured via the router or DHCP
server. For more information please read the user manual of
the router or DHCP server. The EGO Smart Heater has the
name “Cxxxxxx“. The six „x“ are the last six figures of the MAC
address, which is on the label.
Summary of Contents for Smart Heater
Page 79: ...79 pt...