background image

 

- 4 - 

eFlow6NV Series Installation Guide

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 

in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to terminals marked [– BAT +] 

(Fig. 1g, pg. 5)

. Use two (2) 12VDC batteries 

 

connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 

 

batteries of an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1b, pg. 5)

 supervisory

 

relay outputs.

8.  To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position 

(Fig. 1c, pg. 5)

.

 

To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position 

(Fig. 1c, pg. 5)

.

 

Note: 

Must be set to ON position for Burglar Alarm Applications.

9.  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position 

(Fig. 1c, pg. 5)

.

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position 

(Fig. 1c, pg. 5)

.

10.  Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown 

(Fig. 1d, pg. 5)

.

11.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] 

(Fig. 1e, pg. 5)

.

12.  For Access Control Applications: mount tamper switch (Altronix Model TS112 or equivalent) at the 

 

top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right 

 side 

(Fig. 5, pg. 7 or Fig. 7, pg. 9)

. Connect tamper switch wiring to the Access Control Panel input or the 

 

appropriate reporting device.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions, the DC output voltage should be checked for proper 

 

 

 

voltage level eFlow6NV: 12VDC or 24VDC nominal rated @ 6A max.

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

 

 

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board 

 

 

 

terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.

Note:

 Maximum charging current under discharges is 1.54A.

Note:

 Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Summary of Contents for Altronix eFlow6N16DV

Page 1: ...6A 12VDC or 24VDC Eight 8 PTC Protected eFlow6N16DV eFlow6NX16DV 6A 12VDC or 24VDC Sixteen 16 PTC Protected eFlow6NV Series Power Supply Chargers Models Include Rev 6NVRP052213 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ Installation Guide ...

Page 2: ... Output Range V eFlow6NV 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 6 2 1A 5A 250V 10A 32V 910 N A 1 P eFlow6NXV P eFlow6N8V 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 6 2 1A 5A 250V 10A 32V 910 PD8 8 2 5A P eFlow6NX8V 2 5A P eFlow6N8DV 9 78 13 2 20 0 26 4 10 03 13 2 20 19 26 4 6 2 1A 5A 250V 10A 32V 910 PD8CB 8 2A P eFlow6NX8DV 2A P eFlow6N16V 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 6 2 1A 5A ...

Page 3: ...onnect devices to be powered a For eFlow6NV eFlow6NXV connect devices to terminals marked DC Fig 1h pg 5 b For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked 1P 1N through 8P 8N Fig 3a 3b pg 6 or 1 to 16 marked 1P 1N through 16P 16N Fig 4a 4b pg 6 carefully observing correct polarity For auxiliary device connection this output will not be affected by ...

Page 4: ...e pg 5 12 For Access Control Applications mount tamper switch Altronix Model TS112 or equivalent at the top of the enclosure Slide tamper switch bracket onto the edge or the enclosure approx 2 from the right side Fig 5 pg 7 or Fig 7 pg 9 Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device Wiring Use 18 AWG or larger for all low voltage power connectio...

Page 5: ...resent Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum charge current 1 54A non power limited Fig 1g pg 5 Power Distribution Module Terminal Legend PD8 PD8CB Terminal Legend PD16W PD16WCB Function Description 1P to 8P 1P to 16P Positive DC power outputs 1N to 8...

Page 6: ... COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Fac...

Page 7: ...y Battery Optional Rechargeable Stand by Battery CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL Listed external battery enclosure must be used if using 12AH 40AH or 65AH batteries Switch D...

Page 8: ...e made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 6a Fig 6 Fig 6a 220VAC Input 50 60Hz no...

Page 9: ...TION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using 40AH or 65AH batteries Optional Rechargeable Stand by Battery Optional Rechargeable Sta...

Page 10: ... made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 8a Fig 8 Fig 8a Input 220VAC 50 60Hz non...

Page 11: ... 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm ...

Page 12: ...mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm ...

Page 13: ...c 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 0 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 0 05 23 4WTA B 12 24 volt I3 Photo w Therm Sounder 0 05 35 4WTR B 12 24 volt I3 Photo w Therm Relay 0 05 35 4WITAR B 12 24 volt I3 Pho...

Page 14: ...remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state change and unit temperature Access control and user managment Restrict read write Restrict users to specific resources Two 2 integral network controlled Form C Relays Three 3 programmable inpu...

Page 15: ...Notes Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty IIeFlow6NV Series G23U MEMBER ...

Page 16: ...6A 65AH 6A 6A 1 5A 6A Over 4 Hours 6A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption LED Diagnostics Red DC Green AC AC1 Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is su...

Reviews: